PRE-INSTALLATION PREPARATION
Continued
Through exterior wall
enclosed in a chase
Corner
Installation
Flush with a wall
Figure 2 - Common Fireplace Locations
25"
(63.5 cm)
36"
(91.4 cm)
36"
(91.4 cm)
Figure 3 - Fireplace Bottom Dimensions
• Your fireplace is designed to be used in zero clearance installations.
Wall or framing material can be placed directly against any exterior
surface on the back, sides or top of your fireplace, except when
clearances are required from flue vent pipe, see Clearances.
• If recessed into a wall, you can avoid extra framing by positioning
your fireplace against an already existing framing member.
• A hearth extension is not required with this appliance. If one is
installed, it is for aesthetic purposes only and does not have to
meet standard requirements for hearth extensions.
• If you plan on installing a television or entertainment center recessed
above your fireplace, it is recommended that you maintain a mini-
mum 18" (45.7 cm) above the top of louver opening.
• When locating the termination cap, it is important to observe the
minimum vent height and clearances required under code, see
Venting Installation Instructions, page 8.
• Do not recess termination cap into a wall or siding.
• You may paint the termination cap with 450° F (232° C) heat
resistant paint to coordinate with the exterior finish.
PACKAGING AND REMOVAL
The BCT2536 series vented decorative gas fireplaces are packaged
with the following items:
• one box containing a 4 piece log set located on the burner in the
firebox.
• one bag containing the owner’s manual with installation instruc
-
tions, operator’s guide, and warranty information.
• one bag of glowing ember material.
• one bag of vermiculite hearth treatments.
1. Remove shrink wrap securing 2 carton trays to unit.
2. Lift top carton tray off and remove four corner posts.
3. Discard bottom tray once unit is moved into position.
Note:
To prevent damage to ceramic logs and glass panels you may
want to remove them before positioning and framing the unit. To
access firebox, see Louver Panels and Glass Door, page 15.
Figure 4 - Unpacking Fireplace
Carton
Tray
Glass
Panel
Log
Carton
Corner
Post
CLEARANCES
Minimum clearances to combustibles for fireplace:
Back, Sides, Floor and Top
0" (0 mm)
Perpendicular walls 10" (25.4 cm)
Ceiling to Louver & Front 42" (106.68 cm)
B-Vent Surfaces 1" (26 mm) (See venting instructions
for specifics on vent clearances.)
Mantel Clearances (See Mantel Clearances, page 7, for
specific clearances to combustible mantels.)
Combustible material with a maximum thickness of 5/8" (16 mm)
may be flush with top and sides of front face of fireplace.