Superior BC-36 Installation Instructions Manual Download Page 16

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

16

Note: A 1"* air space must be preserved for all
combustible materials extending for any con-
tinuous length adjacent to the chimney.

It is especially important to insulate between
the studs of an outside chase cavity and under
the floor if the floor is above ground level. Do
not place insulation directly against the fire-
place or chimney system.

FIREPLACE FINISHES

Mantels and Trim

It is sometimes best to frame your fireplace
after it is positioned and the chimney is in-
stalled. Frame enclosure for chimney and fire-
place with 2 x 4’s (or heavier) lumber.

Note: The header may rest on the two (2) metal
top spacers on top of the unit but the header
must not be notched to fit around the spacers.

These fireplaces may sit directly on a combus-
tible surface. A 1"* air space is required be-
tween combustible framing and the chimney.
A 1" air  space is required between combus-
tible framing and fireplace outer wrapper.  In
Canada, the minimum height for a combus-
tible mantel is 18" (457 mm) above the fire-
place opening.  

Figure 45 shows typical Cana-

dian installations.  Combustible mantels and
trim may be installed 12" above the fireplace
opening as per NFPA 211, Section 7-2.3.3. and
Figure 46. If a mantel is of a noncombustible
material, it is exempt from these requirements
as long as it does not interfere with the instal-
lation or operation of glass doors.

*Note: 2" clearance to combustibles required
in Canada.

Figure 46

If you’re installing a gas line, connect it before
the fireplace is framed and enclosed in the
finished wall. The gas knockout is determined
by the indentation located at the bottom and
slightly off center in the side refractories. THE
KNOCKOUT IS ALWAYS REMOVED FROM IN-
SIDE THE FIREPLACE. DO NOT REMOVE THE
KNOCKOUT UNLESS YOU ARE INSTALLING A
GAS LINE.
 If removal is attempted from the
outer wrapper, side refractory damage may
occur. With a medium-sized hammer, lightly
tap the surface of the indentation. The refrac-
tory material is very thin in this area and is easily
removed. Once a small hole has been made,
continue tapping until you have reached suffi-
cient diameter for the gas line to fit through. The
entire knockout does not have to be removed.
Remove insulation in the gas line channel.

IMPORTANT: REPACK INSULATION MATERIAL
IN SQUARE HOLE AROUND GAS LINE, INTE-
RIOR AND EXTERIOR OF FIREPLACE, TO SEAL.

Glass Doors

If glass doors are to be installed on these
fireplaces, refer to specific installation instruc-
tions packed with the glass doors. Use only the
doors that are listed for use with these fire-
places. Use of other non-listed glass door on
these fireplaces may constitute a potential fire
hazard and is not recommended.

CAUTION: CERTAIN GLASS DOORS OVERLAP
THE BLACK METAL FACING OF THE FIRE-
PLACE. IF THE FIREPLACE HAS BEEN FACED
WITH NONCOMBUSTIBLE MATERIALS, THERE
MIGHT NOT BE SUFFICIENT CLEARANCE TO
INSTALL THE GLASS DOORS OF YOUR
CHOICE. ENSURE ADEQUATE CLEARANCE IS
MAINTAINED AT ALL TIMES SO AS NOT TO
INTERFERE WITH THE INSTALLATION AND
OPERATION OF GLASS DOORS.

COLD CLIMATE INSULATION

If you live in a cold climate, it is especially
important to seal all cracks around the fireplace
opening with noncombustible material and
wherever cold air could enter the room. Sur-
rounding materials must be caulked where it
meets the black metal facing of the fireplace to
avoid cold air intrusion.

Use noncombustible caulking material only on
fireplace facing to seal. Also, the outside air inlet
duct should be wrapped with noncombustible
insulation to minimize the formation of conden-
sation. Do not place insulation materials on top
of fireplace or against chimney sections.

12"*

Min.

8"*

Fireplace

Opening

Spacer

Combustible

Mantel

and Trim

12"

Max.

1 1/2"

Finished

Wall

Typical Installation

Header

*Both Of These Dimensions Must Be At Least 18”
When An Unvented Gas Log Set Rated At 26,000
BTU Or Higher Is Used.  (Maximum 40,000 BTU)

Figure 45

Fireplace

Opening

Spacer

Combustible

Mantel

8" Max.

(203mm)

Finished

Wall

Canadian Installation

Header

18" Min.

(457mm)

Hearth Extensions and Wall Shields

A hearth extension must be installed with
all fireplaces. It is to protect the combustible
floor in front of the fireplace from both radiant
heat and sparks. The hearth extension must
extend 8" beyond both sides of the fireplace
opening and 16" beyond the front (

see Figure

47 ). Use a hearth extension constructed of a
durable noncombustible material having an
equal or better (lower k value) insulating value
of k = .84 BTU IN/FT

HR 

°

F or a thermal

resistance that equals or exceeds r = 1.19 HR

°

F FT

2

/BTU IN.  With these values, determine

the minimum thickness/material required us-
ing the formula and 

Page 17.

Note: Any noncombustible material whose k
value is less than .84 or whose r value is more
than 1.19 is acceptable.

If the fireplace is installed on a combustible
floor, use the metal safety strips (provided)
on the floor extending half under the fire-
place and half under the hearth extension
(refer to 

Figures 6 & 7).

A wall shield is required where a continuous
perpendicular side wall is within 12" of the
fireplace opening (

Figure 48 ). Use a 36" W x

36" H wall shield constructed of a durable,
noncombustible material having an equal or
better (lower k value) insulating value than k =
.54 BTU IN/FT

2

 HR 

°

F.  At no time may a

perpendicular side wall be located closer than
9" from the fireplace opening.

If fireplace is installed diagonally across a 90

°

corner; no wall shields are required.

Summary of Contents for BC-36

Page 1: ...allation Do not alter or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney compon...

Page 2: ...ese items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distributor 16 For additional safety considerations and compl...

Page 3: ...ortant to prevent possible personal injury or fire hazard Forquestions pleasecallyourdistributororthe manufacturer Special restrictions apply to the front and facing of the fireplace and nearby walls...

Page 4: ...m Height Security FTF8 Pipe Vertical Installation 15 0 One Offsets 15 0 Two Offsets 25 0 Figure 3 ASSEMBLY OUTLINE Before You Start Check your inventory list to be sure you have all the necessary part...

Page 5: ...ety strips beneaththefireplaceasillustrated Figures6 7 and8 Thesafetystripsshouldoverlap1 2 for continual coverage of the floor Note Safety strips are not required when fire place rests on a noncombus...

Page 6: ...overing such asdrywallistobeattachedtotherearwall then the 20 5 8 524 mm must be measured from the drywall surface It is important that this dimension be exact If the appliance is to be elevated above...

Page 7: ...Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit Optional Corner Installation J D A E F Back Wall of Chase Enclosure Including Fi...

Page 8: ...the Class 0 metallic air duct may be ex tended into a ventilated attic space at least 18 457 mm above the attic floor Secure the duct hood to a vertical post with the inlet positioned downward Ensure...

Page 9: ...e outer chimney pipe Position for proper clearance through framedopeningandnailstrapssecurely under tension in shear into place on framing Use 8d nails Attach successive lengths of chimney pipe direct...

Page 10: ...llation instructions in cluded with the FTF8 CTDT chase termination for clearance and installation details Using a FTF8 CT1 Chase Termination Refer to specific installation instructions in cluded with...

Page 11: ...n may be the first component used off the top of the fireplace flue collar CTD 18 18 24 24 CTDT CTDT Less Than 10 3 Min 2 Min 10 3 Min MULTIPLE TERMINATIONS If more than one termination is located in...

Page 12: ...et Inches 12 18 36 48 Height Of Number Of FTF8 Chimney Only Chimney Lengths Inches Feet Inches 12 18 36 48 386 32 2 0 1 0 8 390 32 6 2 0 0 8 396 33 0 1 1 0 8 404 33 8 0 0 1 8 414 34 6 1 0 1 8 416 34 8...

Page 13: ...35 69 1 0 0 1 0 1 37 73 1 0 0 2 1 0 38 75 1 0 0 0 2 0 39 77 1 0 2 1 1 0 41 80 1 0 1 4 0 0 43 83 1 0 1 0 2 0 44 85 1 0 0 0 1 1 45 87 1 0 0 3 1 0 46 89 1 0 0 1 2 0 48 91 1 0 2 0 2 0 49 94 1 0 1 0 1 1 50...

Page 14: ...er Consider this when determining the need for a stabilizer Figure 38 Figure 39 Figure 40 Chimney Section Joints No 8 x 1 2 SMS S c r e w s R e q u i r e d A t E v e r y J o i n t P a s t 6 N o S c r...

Page 15: ...ays plumb gas line installation per local codes Check all connections with soap suds leaks will bubble Never test any gas line con nection with a match or open flame Combustion Air Actuator Pull Forwa...

Page 16: ...es may constitute a potential fire hazard and is not recommended CAUTION CERTAIN GLASS DOORS OVERLAP THE BLACK METAL FACING OF THE FIRE PLACE IF THE FIREPLACE HAS BEEN FACED WITHNONCOMBUSTIBLEMATERIAL...

Page 17: ...e Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Common...

Page 18: ...ness if Multiple Materials are Used At times it is important to know what combination of materials are acceptable for use as floor protection The R values are used to determine acceptable combinations...

Page 19: ...L22 FTF8 ES30 INSTALLATION COMPONENTS The following items are available for use in the installation of this appliance Combination Offset Return Elbow 63L28 FTF8 OR15 Cold Climate Kits 63L61 FTF8 CCK1...

Page 20: ...tallation as applicable NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE Printed in U S A 2007 2011 LENNOX HEARTH PRODUCTS P N 700040M Rev B 10 2011 The manufacturer reserves the right to make changes at any...

Reviews: