Superior BC-36 Installation Instructions Manual Download Page 10

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

10

Next, slide roof flashing over extended chimney
section that previously has been installed above
the roof opening in Step 4. FTF8 flashings
require flashing spacers. Slide flashing all the
way down until the flashing base rests flat on
the roof (

Figure 29 ). Again, check the vertical

position of the chimney and the 1"* minimum
air space to combustibles.

Locking Band

Waterproof
Caulk

Figure 31

Step 9. Security Chimneys locking bands,
Model FLB, may be required if the chimney
extends too high above the roof flashing. As a
general rule, if the chimney extends more than
6' above the roof flashing, the use of locking
bands is advisable to strengthen the chimney
assembly. Align the locking band at the chim-
ney joint. Locking bands wrap around pipe
joints equally covering the joints of both pipe
sections. Use the nut provided and TIGHTEN
snugly. Do not overtighten as this might dam-
age the chimney section (

refer to Figure 31 ).

Note: If chimney extends more than 8' above
roof surface, guy wires are also recommended.
Use three (3) guy wires, attach to locking band
assembly, extend and secure to roof in a trian-
gular pattern (see Figure 32 ). Guy wires are not
supplied by the manufacturer.

Roof Ridge

120

°

Figure 32

Step 10. Using a FTF8-CTD Round Termination:

1. Hold the FTF8-CTD over top of last chimney
section (

Figure 33 ).

2. Center inner slip section in inner flue pipe-
slip down.

Figure 33

3. Center outer locking section over outer flue
pipe. Push down until locking tabs are firmly
engaged.

4. Pull up slightly on CTD to ensure locking joint
has firmly engaged.

Using a FTF8-CTDT Chase Termination:

Refer to specific installation instructions in-
cluded with the FTF8-CTDT chase termination
for clearance and installation details.

Using a FTF8-CT1 Chase Termination:

Refer to specific installation instructions in-
cluded with FTF8-CT1 chase terminations for
clearance and installation details.

Using a FTF8-CT2 Chase Termination:

Refer to specific installation instructions in-
cluded with FTF8-CT2 chase terminations for
clearance and installation details.

CTD

Termination

Chimney

Step 8. Slide the FTF8 storm collar (ordered
separately) over outer chimney, rest on flash-
ing spacers and align with top surface of
flashing. Insert tab in slot, pull tight and bend
tab back over slot. Seal storm collar to outer
chimney with roof caulking or mastic around
entire circumference of pipe. Also add extra
roof caulking to the tab/slot area to seal com-
pletely against water penetration (

Figure 31 ).

Check all joints very carefully to ensure no
water intrusion can take place.

Note: Do not apply excessive pressure to any
subsequent chimney sections following the
stabilizer when installing. Ensure each subse-
quent chimney section is securely attached by
testing as noted in Step 4.

Step 6. Select the proper Security Chimneys
roof flashing based on pitch of roof. Use chart
below for selection:

Roof Pitch

Model

Flat to 6/12

F8F6

6/12 to 12/12

F8F12

FTF8 Chimney

FTF8 Flashing

Flashing Spacers

Do Not Seal

Figure 30

FTF8-S4 Stabilizer

Figure 28

Figure 29

Note: Do not caulk or seal the ventilating
openings.

Step 7. Secure flashing by nailing along the
perimeter into roof using 8d nails. If shingled
roof, slide upper end and sides of roof flash-
ing under shingles (trim if necessary), seal
the top and both sides of the flashing to the
roof with roof caulking. Cover nail heads with
roof caulking (

Figure 30 ).

*Note: 2" clearance to combustibles required
in Canada.

Summary of Contents for BC-36

Page 1: ...allation Do not alter or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited to the fireplace chimney compon...

Page 2: ...ese items should be inspected by your distributor or qualified factory representative to ensure safe condition When in doubt con sult your distributor 16 For additional safety considerations and compl...

Page 3: ...ortant to prevent possible personal injury or fire hazard Forquestions pleasecallyourdistributororthe manufacturer Special restrictions apply to the front and facing of the fireplace and nearby walls...

Page 4: ...m Height Security FTF8 Pipe Vertical Installation 15 0 One Offsets 15 0 Two Offsets 25 0 Figure 3 ASSEMBLY OUTLINE Before You Start Check your inventory list to be sure you have all the necessary part...

Page 5: ...ety strips beneaththefireplaceasillustrated Figures6 7 and8 Thesafetystripsshouldoverlap1 2 for continual coverage of the floor Note Safety strips are not required when fire place rests on a noncombus...

Page 6: ...overing such asdrywallistobeattachedtotherearwall then the 20 5 8 524 mm must be measured from the drywall surface It is important that this dimension be exact If the appliance is to be elevated above...

Page 7: ...Wall of Chase Enclosure Including Finising Materials if any Rough Framing Face Unfinished Shown FOAK Combustion Air Kit Optional Corner Installation J D A E F Back Wall of Chase Enclosure Including Fi...

Page 8: ...the Class 0 metallic air duct may be ex tended into a ventilated attic space at least 18 457 mm above the attic floor Secure the duct hood to a vertical post with the inlet positioned downward Ensure...

Page 9: ...e outer chimney pipe Position for proper clearance through framedopeningandnailstrapssecurely under tension in shear into place on framing Use 8d nails Attach successive lengths of chimney pipe direct...

Page 10: ...llation instructions in cluded with the FTF8 CTDT chase termination for clearance and installation details Using a FTF8 CT1 Chase Termination Refer to specific installation instructions in cluded with...

Page 11: ...n may be the first component used off the top of the fireplace flue collar CTD 18 18 24 24 CTDT CTDT Less Than 10 3 Min 2 Min 10 3 Min MULTIPLE TERMINATIONS If more than one termination is located in...

Page 12: ...et Inches 12 18 36 48 Height Of Number Of FTF8 Chimney Only Chimney Lengths Inches Feet Inches 12 18 36 48 386 32 2 0 1 0 8 390 32 6 2 0 0 8 396 33 0 1 1 0 8 404 33 8 0 0 1 8 414 34 6 1 0 1 8 416 34 8...

Page 13: ...35 69 1 0 0 1 0 1 37 73 1 0 0 2 1 0 38 75 1 0 0 0 2 0 39 77 1 0 2 1 1 0 41 80 1 0 1 4 0 0 43 83 1 0 1 0 2 0 44 85 1 0 0 0 1 1 45 87 1 0 0 3 1 0 46 89 1 0 0 1 2 0 48 91 1 0 2 0 2 0 49 94 1 0 1 0 1 1 50...

Page 14: ...er Consider this when determining the need for a stabilizer Figure 38 Figure 39 Figure 40 Chimney Section Joints No 8 x 1 2 SMS S c r e w s R e q u i r e d A t E v e r y J o i n t P a s t 6 N o S c r...

Page 15: ...ays plumb gas line installation per local codes Check all connections with soap suds leaks will bubble Never test any gas line con nection with a match or open flame Combustion Air Actuator Pull Forwa...

Page 16: ...es may constitute a potential fire hazard and is not recommended CAUTION CERTAIN GLASS DOORS OVERLAP THE BLACK METAL FACING OF THE FIRE PLACE IF THE FIREPLACE HAS BEEN FACED WITHNONCOMBUSTIBLEMATERIAL...

Page 17: ...e Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111 10 71 10 3 4 Common...

Page 18: ...ness if Multiple Materials are Used At times it is important to know what combination of materials are acceptable for use as floor protection The R values are used to determine acceptable combinations...

Page 19: ...L22 FTF8 ES30 INSTALLATION COMPONENTS The following items are available for use in the installation of this appliance Combination Offset Return Elbow 63L28 FTF8 OR15 Cold Climate Kits 63L61 FTF8 CCK1...

Page 20: ...tallation as applicable NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE Printed in U S A 2007 2011 LENNOX HEARTH PRODUCTS P N 700040M Rev B 10 2011 The manufacturer reserves the right to make changes at any...

Reviews: