superior fires ASABA CONTEMPORARY BLACK SLIMLINE CONVECTOR Installation & User'S Instructions Download Page 9

Upon lighting and after the further 10 seconds, release the knob and turn further to the left to the

ON position. The main burner will light and be controlled in accordance with the main burner con-

trol knob setting. Adjust the main burner control knob to the desired setting. 

If the pilot is extinguished during use of the fire, you MUST wait ten minutes before repeating the

ignition procedure.

To turn the main burner OFF whilst keeping the pilot flame lit, turn the ignition control knob to the

pilot position then only the pilot will remain lit.

To shut the fire off completely, press the ignition control  knob down and continue turning to the

right from the pilot position to the OFF position.

A safety interlock prevents re-ignition of the pilot flame until the thermocouple has cooled suffi-

ciently to allow the magnetic valve unit to reset itself.

The remote control unit allows operation of the main burner setting between maximum and pilot

only setting. It does not permanently turn the pilot on or off. 

The remote control handset incorporates an inbuilt safety feature to prevent the main burner being

activated or turned up accidentally. It is necessary to press buttons 1 and 2 (see figure 15) simulta-

neously to turn the fire up. 

To turn the fire down press button 3 only.

The pilot is visible through the left hand side of the matrix. When cold, the coals or pebbles may be

rotated for good viewing.

Push the slide control knob fully downwards to the SPARK position, and hold there for approxi-

mately ten seconds. Now release the knob and the pilot should stay alight. When the pilot light has

established, move the slide control knob upwards to the LOW flame setting.  If the pilot is extin-

guished during use, wait three minutes before repeating the ignition procedure.To achieve the HIGH

setting, move the slide control knob upwards to the HIGH flame setting.  The fire can also be set to

operate anywhere between HIGH and LOW by moving the control knob to an intermediate posi-

tion.

To turn the fire OFF, move the slide control knob upwards fully to the position marked ‘O’.

The spark gap between the spark electrode and the thermocouple should be 3.5 - 4.5mm to produce a good spark. 

There should be no need to adjust this.  If under any circumstances the electric spark fails, the pilot may be lit manually by proceeding

with the ignition sequence as previously described, and after moving the control knob through the spark position, the knob should be

held in (slide control models - down) and the pilot lit with a taper.

Light the fire on the HIGH setting. 

To  commission  the  appliance,  the  operating  pressure

must be in accordance with the figures stated in section

2.0 of these instructions. The fire is factory set to achieve

the correct flow rates at the specified operating pressure.

Any significant variation in the operating pressure could

indicate a supply problem. If the operating pressure is too

high the gas supply meter/governor may be set incorrectly. This should be checked with the fire running and if necessary reset by the

gas supplier.  If the operating pressure is too low, then check the meter/governor pressure with the appliance running.  Upon satisfac-

tory checking of the operating pressure, turn the fire off, disconnect the pressure gauge and refit the test point screw. Light the fire and

check for gas soundness. In the event that the operating pressure is not in accordance with the figures stated in the data section of these

instructions, the appliance must not be commissioned, and the problem investigated and rectified.

This fire is fitted with a flue spillage safety device (ODS). If the fire shuts down during use for no apparent reason then several things

may be suspected. If a door or window has been opened creating a draught, then pilot disturbance is the problem, and removal of the

draught should resolve this. The gas pressure reaching the fire must also be checked (again, recall your installer to check and rectify any

problem). The thermocouple connection into the back of the gas control valve may also have worked loose during installation, simply

get the installer to tighten. If pilot disturbance is not the cause, then the ODS safety system may be in operation. Switch the appliance

OFF, check the flue and carry out any remedial work required. Relight the fire and carry out a spillage test. DO NOT allow the appli-

ance to be used if it continues to fail a spillage test. The aeration hole of the pilot must be carefully cleaned out on each annual service

to ensure continued function of the ODS.The spillage monitoring system shall not be adjusted, modified, or put out of operation by the

installer. Any spare parts fitted MUST be of a type supplied for the purpose by the appliance manufacturer. If the fire is not spilling, then

further guidance should be sought, using the Troubleshooting section as a guide.

9

© 2012 Superior Fires Ltd.

16.4 SPARK GAP

16.5 OPERATING PRESSURE

Fi

 

16.2 OPERATING THE FIRE -  CONTINUED

GB IE

16.6 FLUE SPILLAGE MONITORING SYSTEM

 

    

   

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

1

2

3

Figure 15

16.3 OPERATING THE FIRE - SLIDE CONTROL MODELS

 

    

   

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 16

Control Type

Test point location

Manual

Between burner legs

Remote

Above valve

Slide

Left hand side of burner

Summary of Contents for ASABA CONTEMPORARY BLACK SLIMLINE CONVECTOR

Page 1: ...SLIMLINE RADIANT TC F500479 KINLOCH SLIMLINE RADIANT TC F500480 CHEWTON GROVE SLIMLINE RADIANT TC F500481 CHEWTON SOHO SLIMLINE RADIANT TC F500482 TC TOP CONTROL OR SLIDE CONTROL RADIANT CONVECTOR IN...

Page 2: ...of this appliance This appliance is free from any asbestos material Refractories and fuel bed are constructed from ceramic fibre Remote control models These appliances features a battery operated cont...

Page 3: ...ident at any joints Repair and re test as necessary before the appliance is installed The flue must be connected to only one fireplace and the flue must not vent more than one appliance i e not shared...

Page 4: ...ward projection does not exceed 100mm Any com bustible side walls must be at least 500mm to the side of the radiant heat source As with all heating appliances any decorations soft furnishings and wall...

Page 5: ...llation It is important that the sealing requirements of the appliance are met at all times and that the flue box is well sealed to any back or infill panel Note The DEPTH dimension is inclusive of an...

Page 6: ...M4 nyloc nut provided Affix the Slide control position marking sticker on the trim next to the control knob as shown in figure 16 Before installing the fire check the flue using a smoke pellet All of...

Page 7: ...to pull the appliance tightly against the fireplace opening Visually inspect the seal and reseat if necessary Do not cut off excess cable Surplus cable must not be cut off as it will be impossible to...

Page 8: ...es may be rotated for good viewing The fire features a twin spark ignition system to aid lighting Push the control knob in fully and turn anti clockwise through both of the SPARK positions keep ing fu...

Page 9: ...own and the pilot lit with a taper Light the fire on the HIGH setting To commission the appliance the operating pressure must be in accordance with the figures stated in section 2 0 of these instructi...

Page 10: ...g this time Advise that the fire is fitted with a spillage safety device O D S If the fire shuts down this system may be in operation If spillage is suspected SWITCH APPLIANCE OFF and call in the inst...

Page 11: ...hermocouple nut on the rear of the valve and the two securing screws and lifting away Remove the tubing nut from the valve end of the pilot pipe and blow through to dislodge any debris Clean the pilot...

Page 12: ...Blocked pilot clean out Excessive drafts in the room Excessive flue pull Fire is too close to an air vent Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If the pilot will n...

Page 13: ...ns occur It is NOT a sub stitute for an independently mounted Carbon Monoxide detector This fire is supplied with a particular style of firefront Use of the firefront will ensure an adequate airflow u...

Page 14: ...s before repeating the ignition procedure To turn the main burner OFF whilst keeping the pilot flame lit turn the ignition control knob to the pilot position then only the pilot will remain lit To shu...

Page 15: ...ir sides as shown Place the rear row of four coals making sure that the flat sides are firmly against the brick panel and side cheeks as shown The coals must not be crammed together or inserted into t...

Page 16: ...with the pebbles supplied when assembled according to the instructions Never add to the fifteen pebbles or change them for a different type Never throw rubbish or other matter onto the fuel bed Due t...

Page 17: ...ved by using a damp cloth and mild household detergent Brass parts of the firefront may be cleaned using a suitable brass cleaner Replace the front centrally against the fire after cleaning Do not use...

Page 18: ...pilot 9055 Slide control models F730101 Gas valve Manual control models F730085 Gas valve Remote control models F730011 Gas valve Slide control models F730100 Injector Stereo 78 Manual Slide control m...

Page 19: ...ovement and development we hope therefore you will understand we must retain the right to amend details and or specifications without prior notice 7 F861083 GB IE Date of service Serviced by name GAS...

Reviews: