Figure 9 - Lineal Gain

LINEAL GAIN

PART NO.

DESCRIPTION

GAIN

Signature

Fireplace

66 

1

/

2

"

12-12DM

12-12HT

Pipe Section

10 

5

/

8

"

18-12DM

18-12HT

Pipe Section

16 

5

/

8

"

24-12DM

24-12HT

Pipe Section

23 

5

/

8

"

36-12DM

36-12HT

Pipe Section

34 

5

/

8

"

48-12DM

48-12HT

Pipe Section

46 

5

/

8

"

RLT-12D

RLT-12HT Round Termination

3

/

4

"

*

STL-12D Square Chase-Top 

with Slip Section

7"

 to 15

"

*

* The lineal gain for the terminations is mea

-

sured to the flue gas outlet height.

Hemmed 

End

12 

3

/

8

Stainless 

Inner Pipe

15" Galvanized 

Outer Pipe

ASSEMBLY AND INSTALLATION OF 

DOUBLE WALL CHIMNEY SYSTEM

Each double wall chimney section consists of a 

galvanized outer pipe, a stainless steel inner flue 

pipe and a wire spacer. The pipe sections must 

be assembled independently as the chimney is 

installed. When connecting chimney directly to 

the fireplace, the inner flue pipe section must 

be installed first with the lanced side up. The 

outer pipe section can then be installed over 

5 the flue pipe section with the hemmed end 

up. Press down on each pipe section until the 

lances securely engage the hem on the fireplace 

starter. The wire will assure the proper spacing 

between the inner and outer pipe sections.

Figure 8 - Outside Air Kit

Secure to Collars with Metal Tape, 

Screws or Straps (Min. of 1/4" x 20" 

in size)

Air Inlet 

Location 

Must Allow 

For Bushes 

or Snow

Vent Hood 

Required for 

Wall Installation

Air Inlet 

Eyebrow

Vented Crawl Space

(Check Local Codes 

Before Installing in a 

Vented Crawl Space)

CHIMNEY PIPE

The  INNOVATIVE  HEARTH  PRODUCTS 

chimney  system  consists  of  12",  18",  24", 

36" and 48" snap-lock, double-wall pipe seg

-

ments, planned for maximum adaptability to 

individual  site  requirements. Actual  lengths 

gained  after  fitting  overlaps  must  be  taken 

into consideration (lineal gain) and are given 

in the lineal gain chart (see Figure 9). Lineal 

Gain is the actual measurable length of a part 

after two or more parts are connected. For 

Canada, use chimney parts designated "HT".

VENTING INSTALLATION

OPTIONAL OUTSIDE AIR KIT 

(MODEL AK4/AK4F)

The  installation  of  an  outside  air  kit  should 

be  performed  during  the  rough  framing  of 

the fireplace due to the nature of it's location. 

Outside combustion air is accessed through 

a  vented  crawl  space  (AK4F)  or  through  a 

sidewall (AK4).

 CAUTION: Combustion air 

inlet ducts shall not terminate 

in attic space.

The  maximum  height  for  the 

air vent can not exceed 3 feet 

below the flue gas outlet of the 

termination.

 WARNING: The opening in 

the collar around the chimney at 

the top of the fireplace must not 

be obstructed. Never use blown 

insulation  to  fill  the  chimney 

enclosure.

Summary of Contents for WRT6036

Page 1: ...cated manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible...

Page 2: ...application in fireplace and refer to fire log warnings and caution markings on packaging prior to use Thisfireplaceisnotintendedtobe used as a substitute for a furnace to heat an entire home Use for...

Page 3: ...MODELS 29 14 1 2 22 1 2 26 5 8 4 1 2 15 5 8 4 1 2 1 58 7 1 4 11 15 1 4 3 1 2 9 1 2 10 1 2 67 61 49 11 7 30 1 45 1 8 36 OUTSIDE AIR ACCESS GAS LINE ACCESS 36 HEARTH 1 1 4 20 1 4 Ref 35 1 4 19 22 1 2 Fi...

Page 4: ...ued 42 MODELS 22 3 4 30 1 2 29 4 3 8 15 3 4 5 8 17 5 8 67 61 49 7 1 30 11 58 42 51 1 8 4 1 2 3 1 2 9 1 2 10 1 2 81 2 13 17 OUTSIDE AIR ACCESS GAS LINE ACCESS 42 HEARTH 1 1 4 23 Ref 41 3 8 26 3 8 21 3...

Page 5: ...ntinued 50 MODELS 38 1 2 28 1 2 43 8 17 5 8 19 1 4 24 49 30 11 61 67 58 7 1 59 50 4 1 2 3 1 2 9 1 2 10 1 2 8 1 2 13 17 GAS LINE ACCESS OUTSIDE AIR ACCESS 50 HEARTH 1 1 4 23 Ref 49 3 8 34 3 8 21 3 4 Fi...

Page 6: ...els 61 36 Models Maintain 1 1 2 Clearance at Sides and Back of Fireplace 1 1 2 Clearance Not Required at Nailing Flanges Figure 5 Corner Installation SELECTING LOCATION To determine the safest and mos...

Page 7: ...oncombustible material see Figure 6 WARNING Hearthextension is to be installed only as shown in Figure 6 FIREPLACE INSTALLATION Continued Figure 6 Hearth Extension Seal Gap Fireplace Front Ember Prote...

Page 8: ...ons Figure 8 Outside Air Kit Secure to Collars with Metal Tape Screws or Straps Min of 1 4 x 20 in size Air Inlet Location Must Allow For Bushes or Snow Vent Hood Required for Wall Installation Air In...

Page 9: ...ney together it is important to assure the joint between the chimney sections is locked Check by pulling chimney upward after locking The chimney will not come apart Figure 10 Elbow Offset B A Screws...

Page 10: ...ing Figure 14 Firestop Spacer with Attic Space Above Ceiling Existing Ceiling Frame Firestop Spacer Screws or Staples Min of 8 Firestop Spacer Screws or Staples Min of 8 PENETRATING ROOF To maintain a...

Page 11: ...t Bottom Overlap Shingles Top and Sides Only Figure 16 Flashing Installation FLASHING INSTALLATION V6F 10DM OR V12F 10DM Determine the flashing to be used with the roof opening chart Slide flashing ov...

Page 12: ...on 10 2 Min 10 3 Min 2 Min 3 Min Level of Flue Gas Outlet Figure 20 10 Foot Rule Terminations Spark Arrestor The fireplace system must be terminated with the listed round top or chase terminations In...

Page 13: ...ipping Brackets 2 Install the left and right firebrick walls There is a bracket with 2 tabs on the bottom of each firebrick wall Angle the wall into the fireplace opening and into the slots on the sid...

Page 14: ...avoid spilling Place a wet towel over the bucket making sure it is directly on the surface of grout mixture This will keep the mixture moist and it will not dry out before use 5 Grout all joints where...

Page 15: ...Parts page 20 This grate has been designed to keep the operation of your fireplace safe and efficient FIREBRICK WALL INSTALLATION Continued Figure 26 Installing Grate Retainers INSTALLING SCREEN 1 Sl...

Page 16: ...is on apply soap and water solution to all connectionsandjoints Bubbles forming show a leak Correct all leaks at once DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPER ATEANYAPPLIANCE IFALEAK...

Page 17: ...ION Continued GLASS DOOR INSTALLATION Figure 30 Installing Bottom Door Frame Hex Screw Bottom Door Frame Figure 29 Installing Top Door Frame Top Door Frame Smoke Shelf Ash Lip Ash Lip DOOR FRAME MODEL...

Page 18: ...rewdriver Tighten screws See Figure 32 OPERATION AND MAINTENANCE GUIDELINES GLASS DOORS Glass doors are optional with the fireplace When fireplace is in operation doors must be fully opened or fully c...

Page 19: ...ting risks of both fire and smoke Cleaning Glass Clean glass with any commercial glass cleaner or soap and water Do not use any abrasive material to clean glass Do not clean glass with any cool water...

Page 20: ...www SuperiorFireplaces US com 126595 01A 20 PARTS MODELS 36 42 AND 50 1 21 20 5 6 7 10 9 11 12 13 16 17 15 14 8 24 23 3 25 18 2 22 19 4...

Page 21: ...09752 01 Conduit One 2 17 109752 02 Conduit Two 2 18 Heat Shield Support 1 19 123298 02 Ash Box Assembly 1 20 Inner Dome Assembly 1 21 Smoke Shield 1 22 Damper Control Bracket 1 23 109457 03 Screen 36...

Page 22: ...www SuperiorFireplaces US com 126595 01A 22 1 6 4 8 7 3 2 5 7 7 7 8 9 PARTS MODELS 36 42 AND 50 Picture may vary from actual Note See pages 23 thru 26 for part numbers...

Page 23: ...erringbone 36 Red 1 125415 01 Right Stacked 42 Red 1 125427 01 Right Herringbone 42 Red 1 125439 01 Right Stacked 50 Red 1 125451 01 Right Herringbone 50 Red 1 6 124214 01 Left Stacked 36 Red 1 124226...

Page 24: ...1 125425 02 Rear Herringbone 42 Ivory 1 125437 02 Rear Stacked 50 Ivory 1 125449 02 Rear Herringbone 50 Ivory 1 5 124212 02 Right Stacked 36 Ivory 1 124224 02 Right Herringbone 36 Ivory 1 125415 02 R...

Page 25: ...EPLACEMENT PARTS If this product is missing a part or has a broken component please do not return it to the store Call INNOVATIVE HEARTH PRODUCTS at 1 800 655 2008 to answer questions and replace part...

Page 26: ...DMO42E 42 Ebony BDMO42G 42 Pewter BDMO42C 42 Oiled Bronze BDMO50E 50 Ebony BDMO50G 50 Pewter BDMO50C 50 Oiled Bronze DOUBLE WALL PIPE 12 12DM 18 12DM 24 12DM 36 12DM 48 12DM 12 12HT 18 12HT 24 12HT 36...

Page 27: ...12 Pitch V12F 10DM 6 12 to 12 12 Pitch ACCESSORIES Continued SQUARE CHASE TOP TERMINATION STL 12D AND STL 12DMP BLACK ROUND TOP TERMINATIONS RLT 12D AND RLT 12HT STORM COLLAR SC2 1 FIRESTOP SPACER FS...

Page 28: ...cannot ship via parcel delivery services IMPORTANT NOTICE A manufactured shroud which has been approved by a national testing agency for use with this fireplace may be used if installed in accordance...

Page 29: ...rmal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning...

Page 30: ...IS WARRANTY Model located on product or identification tag ______________________________ Serial No located on product or identification tag ___________________________ Date Purchased ________________...

Page 31: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 32: ...126595 01 Rev A 01 14 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 www IHP US com P126595 01...

Reviews: