VENTING INSTALLATION

Continued

FIRESTOP SPACERS (FS-10, 

1100EFS-10DM FOR 36" MODELS)

Firestop spacers are required at each point 

where the chimney penetrates a floor space. 

Their  purpose  is  to  establish  and  maintain 

the required clearance between the chimney 

and the combustible materials. When the pipe 

passes through a framed opening into a living 

space above, the firestop must be placed onto 

the ceiling from below as shown in Figure 13.
They also provide complete separation from 

one floor space to another or attic space as 

required by most codes. When the double wall 

pipe passes through a framed opening into an 

attic space, the firestop must be placed into an 

attic floor as shown in Figure 14.

Figure 13 - Firestop Spacer with Living 

Space Above Ceiling

Figure 14 - Firestop Spacer with Attic 

Space Above Ceiling

Existing 

Ceiling 

Frame

Firestop 

Spacer

Screws or 

Staples 

(Min. of 8)

Firestop 

Spacer

Screws or Staples 

(Min. of 8)

PENETRATING ROOF

To maintain a 1" (36" Models) or 2" (42/50" 

Models) clearance to the pipe on a roof with a 

pitch, a rectangular opening must be cut.
1.  Determine center point through which pipe 

will penetrate roof.

2.  Determine  center  point  of  roof.  Pitch  is 

distance the roof drops over a given span, 

usually 12". A 6/12 pitch means that roof 

drops 6" for each 12" measured horizon

-

tally down from roof rafters.

3.  Use roof opening chart (Figure 15, page 

11) to determine correct opening length 

and flashing required.

4.  Remove shingles around opening mea

-

sured. Cut out this section.

Existing 

Ceiling 

Frame

Figure 12 - Typical Offset Terminations

Return 

Elbow

Offset 

Elbow

Return 

Elbow

Offset 

Elbow

6' Max.

6' Max.

6' Max.

6' Max.

6' Max.

6' Max.

Return 

Elbow

Offset 

Elbow

Offset 

Elbow

Return 

Elbow

A

B

C

Offset 

Elbow

Ceiling 

Support Pipe

12S-12DM

Return 

Elbow

Summary of Contents for WRT6036

Page 1: ...cated manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible...

Page 2: ...application in fireplace and refer to fire log warnings and caution markings on packaging prior to use Thisfireplaceisnotintendedtobe used as a substitute for a furnace to heat an entire home Use for...

Page 3: ...MODELS 29 14 1 2 22 1 2 26 5 8 4 1 2 15 5 8 4 1 2 1 58 7 1 4 11 15 1 4 3 1 2 9 1 2 10 1 2 67 61 49 11 7 30 1 45 1 8 36 OUTSIDE AIR ACCESS GAS LINE ACCESS 36 HEARTH 1 1 4 20 1 4 Ref 35 1 4 19 22 1 2 Fi...

Page 4: ...ued 42 MODELS 22 3 4 30 1 2 29 4 3 8 15 3 4 5 8 17 5 8 67 61 49 7 1 30 11 58 42 51 1 8 4 1 2 3 1 2 9 1 2 10 1 2 81 2 13 17 OUTSIDE AIR ACCESS GAS LINE ACCESS 42 HEARTH 1 1 4 23 Ref 41 3 8 26 3 8 21 3...

Page 5: ...ntinued 50 MODELS 38 1 2 28 1 2 43 8 17 5 8 19 1 4 24 49 30 11 61 67 58 7 1 59 50 4 1 2 3 1 2 9 1 2 10 1 2 8 1 2 13 17 GAS LINE ACCESS OUTSIDE AIR ACCESS 50 HEARTH 1 1 4 23 Ref 49 3 8 34 3 8 21 3 4 Fi...

Page 6: ...els 61 36 Models Maintain 1 1 2 Clearance at Sides and Back of Fireplace 1 1 2 Clearance Not Required at Nailing Flanges Figure 5 Corner Installation SELECTING LOCATION To determine the safest and mos...

Page 7: ...oncombustible material see Figure 6 WARNING Hearthextension is to be installed only as shown in Figure 6 FIREPLACE INSTALLATION Continued Figure 6 Hearth Extension Seal Gap Fireplace Front Ember Prote...

Page 8: ...ons Figure 8 Outside Air Kit Secure to Collars with Metal Tape Screws or Straps Min of 1 4 x 20 in size Air Inlet Location Must Allow For Bushes or Snow Vent Hood Required for Wall Installation Air In...

Page 9: ...ney together it is important to assure the joint between the chimney sections is locked Check by pulling chimney upward after locking The chimney will not come apart Figure 10 Elbow Offset B A Screws...

Page 10: ...ing Figure 14 Firestop Spacer with Attic Space Above Ceiling Existing Ceiling Frame Firestop Spacer Screws or Staples Min of 8 Firestop Spacer Screws or Staples Min of 8 PENETRATING ROOF To maintain a...

Page 11: ...t Bottom Overlap Shingles Top and Sides Only Figure 16 Flashing Installation FLASHING INSTALLATION V6F 10DM OR V12F 10DM Determine the flashing to be used with the roof opening chart Slide flashing ov...

Page 12: ...on 10 2 Min 10 3 Min 2 Min 3 Min Level of Flue Gas Outlet Figure 20 10 Foot Rule Terminations Spark Arrestor The fireplace system must be terminated with the listed round top or chase terminations In...

Page 13: ...ipping Brackets 2 Install the left and right firebrick walls There is a bracket with 2 tabs on the bottom of each firebrick wall Angle the wall into the fireplace opening and into the slots on the sid...

Page 14: ...avoid spilling Place a wet towel over the bucket making sure it is directly on the surface of grout mixture This will keep the mixture moist and it will not dry out before use 5 Grout all joints where...

Page 15: ...Parts page 20 This grate has been designed to keep the operation of your fireplace safe and efficient FIREBRICK WALL INSTALLATION Continued Figure 26 Installing Grate Retainers INSTALLING SCREEN 1 Sl...

Page 16: ...is on apply soap and water solution to all connectionsandjoints Bubbles forming show a leak Correct all leaks at once DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPER ATEANYAPPLIANCE IFALEAK...

Page 17: ...ION Continued GLASS DOOR INSTALLATION Figure 30 Installing Bottom Door Frame Hex Screw Bottom Door Frame Figure 29 Installing Top Door Frame Top Door Frame Smoke Shelf Ash Lip Ash Lip DOOR FRAME MODEL...

Page 18: ...rewdriver Tighten screws See Figure 32 OPERATION AND MAINTENANCE GUIDELINES GLASS DOORS Glass doors are optional with the fireplace When fireplace is in operation doors must be fully opened or fully c...

Page 19: ...ting risks of both fire and smoke Cleaning Glass Clean glass with any commercial glass cleaner or soap and water Do not use any abrasive material to clean glass Do not clean glass with any cool water...

Page 20: ...www SuperiorFireplaces US com 126595 01A 20 PARTS MODELS 36 42 AND 50 1 21 20 5 6 7 10 9 11 12 13 16 17 15 14 8 24 23 3 25 18 2 22 19 4...

Page 21: ...09752 01 Conduit One 2 17 109752 02 Conduit Two 2 18 Heat Shield Support 1 19 123298 02 Ash Box Assembly 1 20 Inner Dome Assembly 1 21 Smoke Shield 1 22 Damper Control Bracket 1 23 109457 03 Screen 36...

Page 22: ...www SuperiorFireplaces US com 126595 01A 22 1 6 4 8 7 3 2 5 7 7 7 8 9 PARTS MODELS 36 42 AND 50 Picture may vary from actual Note See pages 23 thru 26 for part numbers...

Page 23: ...erringbone 36 Red 1 125415 01 Right Stacked 42 Red 1 125427 01 Right Herringbone 42 Red 1 125439 01 Right Stacked 50 Red 1 125451 01 Right Herringbone 50 Red 1 6 124214 01 Left Stacked 36 Red 1 124226...

Page 24: ...1 125425 02 Rear Herringbone 42 Ivory 1 125437 02 Rear Stacked 50 Ivory 1 125449 02 Rear Herringbone 50 Ivory 1 5 124212 02 Right Stacked 36 Ivory 1 124224 02 Right Herringbone 36 Ivory 1 125415 02 R...

Page 25: ...EPLACEMENT PARTS If this product is missing a part or has a broken component please do not return it to the store Call INNOVATIVE HEARTH PRODUCTS at 1 800 655 2008 to answer questions and replace part...

Page 26: ...DMO42E 42 Ebony BDMO42G 42 Pewter BDMO42C 42 Oiled Bronze BDMO50E 50 Ebony BDMO50G 50 Pewter BDMO50C 50 Oiled Bronze DOUBLE WALL PIPE 12 12DM 18 12DM 24 12DM 36 12DM 48 12DM 12 12HT 18 12HT 24 12HT 36...

Page 27: ...12 Pitch V12F 10DM 6 12 to 12 12 Pitch ACCESSORIES Continued SQUARE CHASE TOP TERMINATION STL 12D AND STL 12DMP BLACK ROUND TOP TERMINATIONS RLT 12D AND RLT 12HT STORM COLLAR SC2 1 FIRESTOP SPACER FS...

Page 28: ...cannot ship via parcel delivery services IMPORTANT NOTICE A manufactured shroud which has been approved by a national testing agency for use with this fireplace may be used if installed in accordance...

Page 29: ...rmal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning...

Page 30: ...IS WARRANTY Model located on product or identification tag ______________________________ Serial No located on product or identification tag ___________________________ Date Purchased ________________...

Page 31: ...___________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________...

Page 32: ...126595 01 Rev A 01 14 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 www IHP US com P126595 01...

Reviews: