SuperiorFireplaces.us.com
126700-01C
11
INSTALLATION
Continued
Figure 7 - Minimum Mantel Clearances
for Built-In Installation
Supplied
Firebox Hood
Must Be Used
at All Times
Wire-mesh
Screen
Firebox
Noncombustible
Material May
Project Off this
Surface above
the Firebox Hood
Mantel Shelf
Note: Any portion of the
mantel shelf must NOT
extend beyond this profile.
12" 16" 20"
1
1
/
2
"
6
3
/
4
"
12"
Note: All vertical
measurements are
from top of fireplace
hood opening to
bottom of mantel shelf.
These minimum
clearances replace any
other recommended
clearances supplied
with your ANSI Z21.11.2
approved gas logs.
Wall board or facing
material (above
firebox) may be of
combustible material,
including decorative
mantel ornaments or
other similar projec-
tions off of the facing
material.
Framing
Material
Figure 6 - Minimum Clearance for
Combustible to Wall
*Minimum 16" from Side Wall
Example
*
WARNING: Maintain the
minimum clearances. If you can,
provide greater clearances from
floor, ceiling and adjoining wall.
INSTALLATION CLEARANCES
Carefully follow the instructions below. This
will ensure safe installation.
Minimum Wall and Ceiling Clearances
(see Figure 6)
A. Clearances from the side of the fireplace
cabinet to any combustible material and
wall should follow diagram in
Figure 6
.
Example
:
The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3-1/2" from the wall. This com
-
bustible material must be 4" from the side
of the fireplace cabinet
(see
Figure 4
)
.
B. Clearances from the top of the firebox
opening to the ceiling should not be less
than 42".
C. When firebox is installed on carpeting, tile
(other than ceramic) or other combustible
material, other than wood flooring, the
firebox should be installed on a metal or
wood panel extending the full width and
depth of the enclosure.
D. Clearances from the bottom of firebox to
the floor is 0".
These fireboxes can be installed as free
-
standing units against a wall with approved
cabinet mantels that may be available from
your retailer or supplier, or as a built-in unit.
The clearances are the same for either instal-
lation method.
CAUTION: Do not allow the
vent-free gas log appliance to
touch or extend beyond the
firebox screen.
NOTICE: Surface temperatures
of adjacent walls and mantels be-
come hot during operation. Walls
and mantels above the firebox
may become hot to the touch.
If installed properly, these tem-
peratures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
Mantel Clearances for Built-In
Installation
If placing custom mantel above built-in fire
-
box, you must meet the minimum allowable
clearance between mantel shelf and top of
firebox opening shown in
Figure 7
. These
are the minimum allowable mantel clearances
for a safe installation. Use larger clearances
wherever possible to minimize the heating of
objects and materials placed on the mantel.
Maintain adequate clearances for accessibility for purposes
of servicing and proper operation.
Minimum clearance requirements include any projections such
as shelves, window sills, mantels, etc. above the appliance.