INSTALLATION GUIDELINES 

Installation Guidelines 

For proper operation of the Supera Ice Machine, the following installation guidelines must be 
followed. Failure to do so may result in loss of production capacity, premature part failures, and 
may void all warranties. 

Reference the installation parameters prior to installing the machine: 

Ambient Operating Temperatures 
Minimum Operating Temperature:  50°F (10°C) 
Maximum Operating Temperature 100°F  (38°C), 110°F  (43°C) on 50 Hz. Models

Note: Supera icemakers and dispensers are not approved for outdoor installation. 

Incoming Water Supply (See Electrical and Plumbing Diagrams for line sizing) 
Minimum incoming water temperature:  40°F (4.5°C) 
Maximum incoming water temperature:  100°F (38°C) 
Minimum incoming water pressure: 20 psi (1.4 bar) (0,138MPa)  
Maximum incoming water pressure: 60 psi (4.1 bar) (0.414MPa) 

Note: If water pressure exceeds 60 psi (4.1 bar), a water pressure regulator must be installed. 

Drains 
All drain lines must be installed per local codes. Flexible tubing is not recommended. Route bin 
drain, purge drain and water condenser drain individually to a floor drain. The use of condensate 
pumps for draining water is not recommended by Supera. Supera assumes no responsibility for 
improperly installed equipment. 

Note: The purge drain fitting is plastic; DO NOT apply heat to the purge drain area; DO NOT 
overtighten. 

Water Filtration 
A Supera water filter system should be installed with the ice machine. 

Clearance Requirements 
Self-contained air cooled ice machines must have a minimum of 6 inches (15cm) of clearance at 
the rear, top, and sides of the ice machine for proper air circulation. 

Stacking 
Supera does not endorse stacking ice machines. 

Dispenser Application 
A thermostatic bin control kit should be installed if the Supera Ice Machine is placed on a 
dispenser. A bin top may or may not be required.  

Electrical Specifications 
Refer to the serial plate at the rear of the ice machine to make sure proper voltage and circuit 
breaker size have been supplied. Make sure the machine is on a dedicated circuit. European 
installations require that the electrical supply fixed wiring must be provided with a disconnect 
means having a separation of at least 3mm in all poles. The ice machines are provided without an 
electrical cord set and are designed and agency approved to be permanently connected. 

© Supera      

           September 2015      

3

Summary of Contents for MIM-1000FA

Page 1: ...RUCTION MANUAL This manual contains important information regarding your Supera unit Please read this manual thoroughly prior to equipment set up operation and maintenance Failure to comply with regul...

Page 2: ...one 866 953 3288 E mail Service SuperaCo com Any service communication must include Model Serial Number A detailed explanation of the issue Keep this manual for future reference The Supera Service Par...

Page 3: ...al evidence of loss or damage must be fully described and noted on your freight bill or express receipt and signed by the carrier s agent The claim should be filed on a form available from the carrier...

Page 4: ...idually to a floor drain The use of condensate pumps for draining water is not recommended by Supera Supera assumes no responsibility for improperly installed equipment Note The purge drain fitting is...

Page 5: ...of an electrical fire Adjustments Level the machine within 1 8 inch in all directions Check the bin control for proper adjustment Check the water in the water trough for proper level Check the ice bri...

Page 6: ...tion All water supply lines must be installed per local codes Use 1 4 inch O D minimum on air cooled machines On water cooled machines 3 8 inch O D minimum tubing must be run to the condenser The wate...

Page 7: ...ELECTRICAL AND PLUMBING REQUIREMENTS MIM 500FA MIM 650FA Supera September 2015 6...

Page 8: ...ELECTRICAL PLUMBING REQUIREMENTS MIM 900FA MIM 1000FA Supera September 2015 7...

Page 9: ...r The water purge valve opens and allows the water pump to purge the water remaining in the water trough removing impurities and sediment This allows the machine to produce clear ice cubes and keep mi...

Page 10: ...begins to form on the evaporators check the freeze pattern of the ice Ice should form evenly across the evaporator Bridge Thickness and Timer Adjustment Once the unit has gone through 1 or 2 harvest...

Page 11: ...when ice drops off of the evaporator This releases the pressure of the bin switch actuator arm allowing the switch to open Bin Control Adjustment All Models Check the bin switch for proper adjustment...

Page 12: ...n 2 Check ice bridge thickness 3 Check water level in trough 4 Clean the condenser air cooled machines to insure unobstructed air flow 5 Check for leaks of any kind Water Refrigerant Oil Etc 6 Check t...

Page 13: ...move the splash curtain and inspect the evaporator and water spillway to ensure all mineral residue has been removed 8 If necessary wipe the evaporator spillway and other water transport surfaces with...

Page 14: ...urface of stainless steel that protects it from corrosion 3 Don t use cleaners that use chlorine or chlorides Don t use chlorine bleach or products like Comet to clean the steel Chlorides break down t...

Page 15: ...rvest or wait for cycle completion 3 Place the ICE OFF WASH switch to the OFF position The switch is located in the control box 4 Disconnect the tubing between the water pump discharge and water distr...

Page 16: ...Service History Model Number Serial Number Date Installed...

Page 17: ...d Under This Warranty SUPERA LLC s sole obligation under this warranty is limited to either repair or replacement of parts subject to the additional limitations below This warranty neither assumes nor...

Page 18: ...Supera Customer Care Toll Free Service Line 1 866 953 3288 For additional product and warranty information please visit our website at www SuperaCo com...

Reviews: