PGA 3510 Operations Manual
Super Systems Inc.
Page 35 of 42
12.
Wait for the “Current Value” displayed on the screen to get as close as possible to the voltage
being delivered by the millivolt sourcing device.
13.
Tap Calibrate. Tap “Yes” when asked if you want to proceed with the calibration. A progress
indicator will appear.
14.
When the process completes, Span calibration is finished.
To perform a temperature calibration (“Cold Junction Trim”):
Needed: Thermocouple wire type “S” and/or “K”, temperature sourcing device
1.
Open the Analog Input Calibration page.
2.
Make sure that the selected input at the top of the screen is T/C K or T/C S, depending on which
thermocouple wire type you are using.