5. Start and Stop

5.1 Start Inverter

When starting the inverter, follow these steps:
1) Turn on the AC breaker first.
2) Turn on the DC switch in the bottom. If the PV string voltage higher than the inverter start-up 
voltage, the inverter will start.
3) When both AC and DC power supply are normal, the inverter is ready to start. The inverter 
will initiate from checking its internal parameters and grid parameters, if it’s within the range, 
the green light on the left side of the screen begins to flash, and the “Waiting” message will be 
displayed on the OLED display.
4) After 30 seconds, the inverter will start generating electricity, the green light will remain on, 
and the OLED display will display real-time power information.

5.2 Stop Inverter

When turning off the inverter, please follow the steps below:
1) Turn off the AC breaker first.
2) Wait 30 seconds and then turn the DC switch to the “OFF” position. At this time, there is 
remaining power in the inverter capacitor. Wait for 5 minutes until the inverter is completely 
de-energized before operating.
3) Disconnect the AC and DC cables.

24

6. General Operation

6.1 Display Operation

When the inverter is turned on, the following interfaces will be displayed on the OLED display, 
and you can check the information and modify the parameters of the inverter by short or long 
pressing the button. Please refer to the following display operation flow for details:

25

Main Window

Waiting

Checking

Normal

Pac

Error Code

Pv Voltage

Pv Current

E-DAY

E-TOTAL

H-TOTAL

Model Name

General Set

Return

Main Window

SysInfo

FM Version

WIFI

Reset

WIFI

Reload

Safety Set

Safety Code

Power Limit

PF Set

History

Error Code

RSSI

Time Set

Language Set

SN

Error Message

Setting

Setting

Setting

XXX%

Setting

Setting

Setting

Setting

Short press(1s),switch window

Long press(3s),enter the lower Menu

Firmware 

Updating

Tip:After every setting completed, wait for 10 seconds and the inverter will automatically save your settings or modifications.

Grid Voltage

Grid Current

Grid Frequent

PowerLimit

OFF

PowerLimit

ON

NOT WIFI

Grid Connect 

Type Set

Four/Three

Wire System

Modbus 

Address Set

1-247

Tip: After every setting completed, wait for 10 seconds and the inverter will 
automaticaly save your settings or modifications.

Summary of Contents for STT-10KTL

Page 1: ...Grid connected PV Inverter Three Phase Dual MPPT STT 6K 8K 10K 12K 15K 17K 20K 25KTL User Manual Ningbo Sunways Technologies Co Ltd...

Page 2: ...3 3 Display Interface 12 3 4 Packing List 13 4 Product Installation 13 4 1 Selection of Installation Location 13 4 2 Mounting the Inverter 15 4 3 Electrical Connection 17 4 4 Monitoring Device Instal...

Page 3: ...rid connected inverter for power generation needs the permission of the local power supply authority 2 1 7 During the operation of the inverter the surface temperature may be higher and there is a ris...

Page 4: ...g needs to be properly grounded Danger Warning Caution Used to warn of urgent dangerous situations if not avoided it could result in death or serious personal injury Description Symbol Used to warn of...

Page 5: ...8 models which are listed below STT 6KTL STT 8KTL STT 10KTL STT 12KTL STT 15KTL STT 17KTL STT 20KTL STT 25KTL 3 1 3 Applicable grid type The applicable grid types for the Sunways STT 6 25kW series ar...

Page 6: ...r side view as shown in Figure 3 3 10 Figure 3 4 Bottom view Figure 3 5 Inverter back view 3 2 3 Inverter bottom view as shown in Figure 3 4 3 2 4 Inverter back view as shown in Figure 3 5 11 410mm 17...

Page 7: ...complete at the first time when receiving the goods See Figure 3 7 for the packing list 4 Product Installation 4 1 Selection of Installation Location The Sunways STT 6 25kW series is designed with IP6...

Page 8: ...ter Warning 14 4 2 Mounting the Inverter 4 2 1 Wall bracket installation Dimensions of wall bracket see Figure 4 4 1 Use the wall bracket as the template to mark the position of 5 holes on the wall Se...

Page 9: ...tage of each PV string does not exceed 1100V 4 3 1 2 DC connector assembly procedures 2 Peel off the DC cable insulation sleeve for 7 mm as shown in Figure 4 8 Cable type Conductor transverse area mm...

Page 10: ...se a multimeter to measure the voltage of the DC input string verify the polarity of the DC input cable and ensure that each string voltage is within 1000V Warning Open end Wrench 18 Figure 4 12 Figur...

Page 11: ...sing Otherwise it may cause electric shock Good grounding is good for resisting surge voltage shock and improving EMI performance Inverters must be well grounded For a system with only one inverter ju...

Page 12: ...fely disconnect the open circuit voltage of the PV array plus a safety reserve of 20 Install a DC switch to each PV string to isolate the DC side of the inverter We recommend the following electrical...

Page 13: ...energized before operating 3 Disconnect the AC and DC cables 24 6 General Operation 6 1 Display Operation When the inverter is turned on the following interfaces will be displayed on the OLED display...

Page 14: ...liably before shipment When a fault occurs the corresponding fault messages will display on the OLED display and in this case the inverter might stop feeding into grid The fault messages and their cor...

Page 15: ...ata Dimensions mm 550W 410H 175D Weight KG 22 25 ProtectionDegree IP65 Self consumptionatNight W 1 Topology Transformerless OperatingTemperatureRange C 30 60 RelativeHumidity 0 100 OperatingAltitude m...

Reviews: