240VAC Heating
Mats
(Maximum 13 amps)
(260 sq ft)
Line - Black
Line - Blue
Ground - Bare or Green
240VAC Heating
Mats
(Maximum 13 amps
(260 sq ft)
Load -
Black
Load -
Red
Mat - Green
Mat -
Black
Mat -
Blue
Control
Black
Control
Red
Upper terminals not used for sensor
Sensor
Sensor Wire (no polarity)
Typical Electrical Wiring Diagram with FloorStat Controller (240V)
All electrical work must be done by a qualified, licensed electrician in accordance with local building and electrical codes, and the
National Electrical Code (NEC), especially Article 424, Part IX of the NEC, ANSI/NFPA 70 and Section 62 of CEC Part I.
Typical Electrical Wiring Diagram with FloorStat Controller and Contactor (240V)
240VAC Heating
Mats
(Maximum 13 amps)
(260 sq ft)
240V
Control
(back)
Line - Black
Line - Blue
Ground - Bare or Green
Load -
Black
Load -
Red
Mat - Green
Mat - Black
Mat - Blue
Control
Black
Control
Red
Upper terminals not used for sensor
Sensor Wire (no polarity)
Sensor
Contactor
(240V Coil)
All electrical work must be done by a qualified, licensed electrician in accordance with local building and electrical codes, and the
National Electrical Code (NEC), especially Article 424, Part IX of the NEC, ANSI/NFPA 70 and Section 62 of CEC Part I.
240V
Control
(back)
(Contactor
provided by
installer)
Dedicated 240V, 20 amp (maximum) circuit (must be GFCI protected unless GFCI FloorStat is used).
Dedicated 240V, 20 amp (maximum) circuits (with GFCI breaker provided by installer on circuits not
protected by a GFCI FloorStat).
Mat - Green
Ground - Bare or Green
Mat - Black
Mat - Blue
Line - Blue
Line - Black
(Contactor
coil may
require
"snubber")
SunTouch Space Warming Manual
17
A
Ap
pp
peen
nd
diix
x:: 2
24
40
0V
V C
Co
on
nttrro
oll W
Wiirriin
ng
g D
Diia
ag
grra
am
mss..