Helpful Tips

9

To ensure proper ignition make sure the igniter pin is properly positioned

and connected.

- The igniter pin should be pointed straight to the thermocouple.

- The thermocouple should be positioned 5mm away from the burner tube.

Make sure that the pilot housing is unobstructed. 

Clear any debris on top of the pilot housing and make sure there is no debris 

between the igniter pin, thermocouple and the burner tube.

If the burner will not light or stay lit,

please perform the following checks.

Turn the control knob to off and close the LP Gas tank valve. Disconnect the

regulator. Turn the Control Knob to “HIGH”. Wait a minimum of 5 minutes.

Turn burner control knob back to “OFF”. Reconnect the regulator and perform

a leak check at tank connection. Turn the LP Gas tank valve on slowly, wait 30

seconds and then light the outdoor fire table.

It is possible that the Excess Flow Safety Device has been tripped.

Make sure 

the wires are 

fully inserted 

into the 

ignitor box.

If wires are too 

close, or 

tangled, they 

could short. 

Make sure they 

are spaced 

apart from 

each other.