106
Grid monitoring
Yes
Ground fault monitoring
Yes
Insulation monitoring
Yes
Surge protection
Yes
Q at night
Optional
G
Ge
en
ne
erra
all D
Da
atta
a
Dimensions (W x H x D)
2280 x 2280 x 1600 mm
Weight
3200 kg
Topology
Transformerless
Degree of protection
IP55 (optional: IP65)
Night power consumption
< 200 W
Operating ambient
temperature range
-35 to 60 ℃ (> 50 ℃ derating)
Allowable relative humidity
range
0~100%
Cooling method
Temperature controlled forced air cooling
Max. operating altitude
4000 m (> 3000 m derating)
Display
Touch screen
Communication
Standard: RS485, Ethernet
Grid support
Q at night function (optional), L/HVRT , active & reactive
power control and power ramp rate control
S
SG
G3
31
12
25
5H
HV
V--3
30
0//S
SG
G3
34
40
00
0H
HV
V--3
30
0
IIn
np
pu
utt ((D
DC
C))
S
SG
G3
31
12
25
5H
HV
V--3
30
0
S
SG
G3
34
40
00
0H
HV
V--3
30
0
Max. PV input voltage
1500V
Min. PV input voltage
875 V
Startup input voltage
915 V
MPP voltage range
875~1300 V
No. of DC inputs
18(optional: 22/24 inputs negative grounding or
floating; 28 inputs negative grounding)
Max. PV input current
3997 A
Max. DC short-circuit
current
10000 A
O
Ou
uttp
pu
utt ((A
AC
C))
AC output power
3437 kVA@ 45
˚
C
3125 kVA@ 50
˚
C
3437 kVA@ 45
˚
C
Max. AC output current
3308 A
Nominal AC voltage
600 V
System Manual