17
IIn
nsstta
alllla
attiio
on
n S
Stte
ep
pss
step 1
Unscrew the waterproof terminal "Input AC220V", and lead the external power supply
cable through the terminal.
step 2
Strip the cable with a wire stripper.
step 3
Crimp the cord end terminal, where the recommended terminal model is: LT015008.
step 4
Connect the cord end terminal to the corresponding terminal, and secure it with screw,
where the fastening torque is 2.0N·m.
step 5
Screw the waterproof terminal "Input AC220V".
-- -- E
En
nd
d
4.4.5 PLC Port Connection
W
Wiirriin
ng
g D
Diia
ag
grra
am
m
COM100 can be connected to double-split transformer or double-winding transformer,
as shown in the figures below.