UNIQ HEAT BATTERIES REFERENCE MANUAL_V2.3 

2.

 

Technical Specifications 

The standard models of the Sunamp heat batteries are supplied with PCM58 and these heat batteries can be used with 
any heat source which can run at flow temperature greater than 65

o

C. The discharge temperature from these standard 

heat battery models will be between 52 and 55

o

C.  

The overall dimensions and weights of the heat battery models in the 

UniQ 

range are listed in table 2.1 and their technical 

specification is listed in table 2.2. The pressure loss characteristics of the heat batteries are tabulated in tables 2.3a, 2.3b, 
2.3d, 2.3e. The standard and optional equipment supplied with the heat batteries is listed in table 2.4. 

Table 2.1. Overall dimensions and weights of UniQ heat battery range 

 

Overall dimensions [mm] 

Weight

 [1]

 

Width 

Depth 

Height 

[kg] 

UniQ HW 3, UniQ Heat 3, UniQ Dual 3 

365 

575 

410 

55 

UniQ HW 6, UniQ Heat 6, UniQ Dual 6 

365 

575 

605 

105 

UniQ HW 9, UniQ Heat 9, UniQ Dual 9 

365 

575 

815 

155 

UniQ HW 12, UniQ Heat 12, UniQ Dual 12 

365 

575 

1,025 

205 

UniQ HW 3+i, UniQ HW 3+iPV, UniQ eHW 3, UniQ dPV 3 

365 

575 

455 

61 

UniQ HW 6+i, UniQ HW 6+iPV, UniQ eHW 6, UniQ eDual 6 

365 

575 

650 

111 

UniQ HW 9+i, UniQ HW 9+iPV, UniQ eHW 9, UniQ eDual 9 

365 

575 

860 

161 

UniQ HW 12+i, UniQ HW 12+iPV, UniQ eHW 12 

365 

575 

1,070 

211 

[1]     The PCM in standard heat batteries has a phase transition temperature of 58

o

 

Table 2.2: Technical specification of UniQ heat battery range 

 

Size 3 

Size 6 

Size 9 

Size 12 

Storage capacity 

 Standard batteries with PCM58 

[1]

 

[kWh] 

3.5 

7.0 

10.5 

14.0 

Water content 

 Low power circuit (LPC) 

[3]

 

Water content 

 High power circuit (HPC)

 [4]

 

[L] 
[L] 

1.30 
2.24 

2.36 
4.48 

3.46 
6.76 

4.56 
9.04 

Equivalent hot water cylinder size 

[5]

 

[L] 

71 

142 

212 

284 

V

40

, Volume of hot water available at 40

o

[6]

 

[L] 

85 

185 

300 

370 

 

Heat loss rate 

 

Heat loss rate 

 

ErP Rating class 

 Hot water storage vessel 

[kWh/24h] 
[W] 
[ - ] 

0.449 

18.7 

A

+

 

0.649 

27.0 

A

+

 

0.738 

30.7 

A

+

 

0.809 

33.7 

A

+

 

Recommended maximum HW flow rate 

[L/min] 

15 

20 

25 

Minimum cold water supply pressure at inlet to the heat battery 

[bar] 
[MPa] 

1.00 
0.10 

1.50 
0.15 

1.50 
0.15 

1.50  
0.15 

Maximum working pressure: 
High power (HPC) and Low power (LPC) circuits 

[bar] 
[MPa] 

10.0 

1.0 

10.0  

 1.0 

10.0 

1.0 

10.0 

1.0 

Pressure loss characteristics (See tables 2.3) 

 

K

V

 Value for the Low power circuit (LPC) 

 

K

V

 Value for the High power circuit (HPC) 

 
[ - ] 
[ - ] 

 

1.623 
2.871 

 

1.255 
2.356 

 

1.066 
1.951 

 

0.963 
1.451 

Minimum heat source flow temperature 

[7]

 

[

o

C] 

65 

65 

65 

65 

Maximum heat source flow temperature 

[8]

 

[

o

C] 

85 

85 

85 

85 

Hot water outlet temperature at design flow rate 

[9]

 

[

o

C] 

50 - 55 

50 - 55 

50 - 55 

50 - 55 

Heat battery controller  

 

CC power supply rating at 230V, AC, 50Hz 

[10]

 

 

Electric heater supply rating at 230V, AC, 50Hz 

[11]

 

 

Standby power consumption 

 All models 

 

Power rating of the heater at 230V, AC, 50Hz 

(‘e’ models only)

 

 
[A] 
[A] 
[W] 
[W] 

 

16 

2,800 

 

16 

2,800 

 

16 

2,800 

 

32 

2,800 

 

Notes 

 Table 2.2 

1)

 

Batteries  operating  as  hot  water  heaters.    Charged  to  75

o

C  and  then  discharged  using  mains  cold  water  at  10

o

C  until  the  hot  water  outlet 

temperature dropped to 40

o

C.  

2)

 

Batteries  operating  as  hot  water  heaters.    Charged  to  55

o

C  and  then  discharged  using  mains  cold  water  at  10

o

C  until  the  hot  water  outlet 

temperature dropped to 40

o

C.  

3)

 

For UniQ HW and UniQ HW+I heat batteries, the low power circuit (LPC) is connected to external heat source e.g. a boiler. 

4)

 

For UniQ HW and UniQ HW+I heat batteries, the high power circuit (HPC) is connected to the mains cold water supply for producing hot water. 

Summary of Contents for UniQ Dual 12

Page 1: ...L_V2 3 Version 2018_07_19_v2 3 Sunamp Ltd Abstract This is a quick reference guide for selecting the UniQ range of heat batteries for the required application For designing a heating system based on U...

Page 2: ...eneral requirements 11 4 2 Water distribution network design 11 4 3 Hot water circuit expansion vessel sizing 11 4 4 Hot water secondary circulation and trace heating 12 4 5 Hard water areas 12 5 Inst...

Page 3: ...TTERIES REFERENCE MANUAL_V2 3 6 1 Heat batteries fitted with electric element 18 6 2 UniQ HW UniQ Heat and UniQ Dual batteries Error Bookmark not defined 6 3 Heat batteries not fitted with an electric...

Page 4: ...and hot water system in a building It only covers installation and commissioning of the selected heat battery Table 1 1 UniQ Range of heat batteries Generic range Description Models UniQ HW These heat...

Page 5: ...ning costs d Operational needs Smaller space typically 2 3 times smaller than the equivalent hot water cylinders and clean installation 1 1 2 UniQ Heat UniQ eHeat UniQ Dual and UniQ eDual range The ma...

Page 6: ...4 L L 1 30 2 24 2 36 4 48 3 46 6 76 4 56 9 04 Equivalent hot water cylinder size 5 L 71 142 212 284 V40 Volume of hot water available at 40oC 6 L 85 185 300 370 Heat loss rate Heat loss rate ErP Rati...

Page 7: ...3a Pressure loss characteristic of UniQ size 3 batteries All generic types Flow rate Low power circuit LPC High power circuit HPC HPC LPC Circuits in parallel L s m3 h bar kPa bar kPa bar kPa 0 10 0...

Page 8: ...0 360 0 140 13 975 0 062 6 156 0 022 2 224 0 20 0 720 0 559 55 900 0 246 24 622 0 089 8 896 0 30 1 080 1 258 125 775 0 554 55 400 0 200 20 016 0 40 1 440 2 236 223 600 0 985 98 490 0 356 35 584 0 50 1...

Page 9: ...UniQ_SBC_B100 UniQ HW i UniQ Dual i Program No 2 Option 2 Off Figure 6 2 The controller UniQ SBC_B100 with logic program 2 selected and with option 2 set to OFF is designed to control the operation o...

Page 10: ...temperature sensor TS3 heating demand on set point 45 65 65 T_S3_OFF Top temperature sensor TS3 heating demand off set point 75 77 77 T_S3_MAX_OFF Maximum temperature permitted for sensor Off limit TS...

Page 11: ...is approx 90 depleted Option 1 off demand signal generated when battery is approx 50 depleted 3 3 2 Program 2 Thermal store with electric heater Heating from top to bottom with boiler and from bottom...

Page 12: ...use within building and their curtilage c Domestic Building Services Compliance Guide 2013 edition incorporating 2018 amendments d The Water Supply Water Fittings Regulations i e WRAS 4 3 Hot water ci...

Page 13: ...te required in each section to replace the heat loss in that section The Institute of Plumbing IOP guide states that as a rule of thumb the return pipe size for the secondary circulation can be taken...

Page 14: ...es The means of isolation must be accessible to the user after installation f All models of UniQ heat batteries are fitted with 3 temperature sensors as shown in figure 5 1 The UniQ e models are also...

Page 15: ...section 4 of this document a Pipe connections All model in this range 22mm copper b The UniQ HW batteries are not suitable for tank fed hot water systems c The hot water circuit should be connected t...

Page 16: ...4 1 Mains cold water and hot water supplies The UniQ eDual heat batteries are designed for storing heat which then can be used for producing hot water and for space heating in dwellings These models...

Page 17: ...gs Therefore these heat batteries are equivalent to indirect unvented hot water cylinders or hot water only thermal stores The UniQ HW i models are fitted with standby electric heating elements to hea...

Page 18: ...w power port B and C as shown schematically in figure 4 8 d For minimum and maximum working pressures see section 3 1 5 5 2 Electricity supply The UniQ HW i and UniQ HW iPV heat batteries are supplied...

Page 19: ...igure 6 1 Yellow cable Terminal S0 Blue cable Terminal S1 Red cable Terminal S2 Green cable Terminal S3 Battery heater cable These batteries include pre wired heating elements as shown in figure 5 1 C...

Page 20: ...Page 19 of 24 UNIQ HEAT BATTERIES REFERENCE MANUAL_V2 3 Figure 6 1 Wiring for electric storage water heater applications Heat battery...

Page 21: ...rth Run and connect control circuit power supply cable 6A minimum 0x75mm2 CSA from the local 2 pole isolator to the controller as shown in figure 6 2 Brown Live Terminal 1 Live Blue Neutral Terminal 2...

Page 22: ...lue Neutral Terminal 5 Neutral Green Yellow Earth Terminal 6 Earth The control circuit power supply can be run from the same local isolator supplying the solar diversion unit A separate 6A supply shou...

Page 23: ...able Terminal S3 Control circuit power supply Run and connect control circuit power supply cable 6A minimum 0x75mm2 CSA from the local 2 pole isolator to the controller as shown in figure 6 4 Brown Li...

Page 24: ...Page 23 of 24 UNIQ HEAT BATTERIES REFERENCE MANUAL_V2 3 Figure 6 4 Wiring for heat batteries without electric element Power supply 230VAC 6A Heat source control Heat battery...

Page 25: ...available as per the table below but have now been merged Please refer to user manual version 2 2 if you have a version with the old naming convention UniQ_SBC_XX name deprecated UniQ_SBC_BXXX curren...

Reviews: