52
Sun Fire V490 Server Setup and Rackmounting Guide • August 2004
Note –
The system is fully serviceable in a 4-post cabinet when it is extended on its
slide assemblies.
TABLE A-1
4-Post Rack Requirements
Cabinet Feature
Requirement
Load-bearing capacity
The rack must firmly support the weight of as many
Sun Fire V490 servers as you are installing into the
cabinet (each server weighs up to 97 lb/44 kg), plus
the weight of the rackmounting hardware, and the
weight of any other installed devices.
Vertical space requirements
Each server requires five rack units (8.75 in/22.22 cm) of
vertical space for rack installation. A 72-inch (184-cm) Sun
cabinet ships with a power sequencer so that it can hold up
to seven servers (with a power sequencer there are 36 rack
units of usable space).
Note:
If the servers are fully
populated, the cabinet and power sequencer will only
support six servers. See the
Site Planning Guide for Entry-
Level Servers Version 1.5
for more information.
Doors and panels
If you are using a Sun expansion cabinet, you can remove
the front and back doors and the side panels to increase
access to the system. Otherwise, see the instructions
provided with the cabinet.
Anti-tip protection
The cabinet must be bolted securely to the floor or equipped
with two sturdy and extendable anti-tip legs. You must
prevent the cabinet from tilting forward when one or more
systems or devices are fully extended out the front of the
cabinet.
Summary of Contents for Sun Fire V490
Page 6: ...vi Sun Fire V490 Server Setup and Rackmounting Guide August 2004...
Page 10: ...x Sun Fire V490 Server Setup and Rackmounting Guide August 2004...
Page 30: ...20 Sun Fire V490 Server Setup and Rackmounting Guide August 2004...
Page 38: ...28 Sun Fire V490 Server Setup and Rackmounting Guide August 2004...
Page 59: ...Chapter 3 Setup Procedures 49 Allow slack Velcro straps...