2-1
C H A P T E R
2
Rack Options and Placement
This chapter provides details about the racks and cabinets into which you can install
a Sun Fire B1600 blade system chassis, and contains the following sections:
■
Section 2.1, “Rack Options” on page 2-1
■
Section 2.2, “Service Access” on page 2-2
■
Section 2.3, “Rack and Floor Loading” on page 2-3
■
Section 2.4, “Rack and Cabinet Safety” on page 2-3
2.1
Rack Options
You can install the Sun Fire B1600 blade system chassis into these 19-inch and
23-inch racks:
■
19-inch two-post rack with a post depth between 3 in. (76.2 mm) and
6 in. (152.4 mm)
■
19-inch four-post IEC297/EIA310-D rack with a distance between mounting rails
from 24.6 in. (625 mm) to 36.4 in. (925 mm)
■
23-inch two-post rack with a post depth of 5 in. (127 mm). These are intended for
use with telco seismic frames
■
23-inch four-post rack
Note –
You can also install the system into a cabinet, subject to adequate cabinet
ventilation, power and floor loading considerations. Read this chapter for further
details.
Summary of Contents for Sun Fire B1600 Administration
Page 6: ...vi Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 10: ...x Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 14: ...xiv Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 30: ...2 4 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 82: ...5 14 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 94: ...6 12 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...
Page 98: ...Index 4 Sun Fire B1600 System Chassis Hardware Installation Guide August 2003 ...