Chapter 3
Environmental Requirements
11
Computer Room Layout
The location of the Cluster Platform 15K/9960 system on perforated floor tiles, and
the number of tiles available to provide cooling air in a typical computer room
raised floor environment, is critical to the overall cooling performance.
Each tile needs to be capable of delivering 600 cubic feet per minute (cfm) cooling air
at 0.07 inches of water. Review the floor plan layout in
for planning your
solid and perforated tile floor configuration.
FIGURE 3-1
Solid and Perforated Tile Floor Plan
Note –
Casters and leveling feet, located at the corners of each cabinet, are to be
positioned only on solid floor tiles.
Storage
Storage
Server 1
Expansion
Server 2
controller
cabinet
Perforated tiles
Solid tiles
cabinet