4-2 

Chapter 4 

Installation and Wiring 

 

 

Regarding to the default setting of parameters for each terminal function, refer to the user

s guide for 

HF-430NEO.   

 

Refer to “4.3 Wiring of HF-TM2” as wiring sample. 

 

External Thermistor (M3 screw terminal) 

 

 
 

FRQ output terminal (M3 screw terminal) 

 

 
 

 

 

Terminal 

symbol 

Terminal 

name 

Description 

Electrical 

characteristics 

Th

erm

is

to

r t

erm

in

al

 

A

na

log

 inp

ut

 

TH 

External 

thermistor 

input 

When an external thermistor is connected, and 

resistance abnormality occurs due to abnormal 

temperature, etc., trip the inverter. 

Connect the thermistor with TH+ and COM.   

The level of detecting resistance abnormality can be 

adjusted from 0 to 10000 

Ω.

 

[Recommended thermistor characteristics] 

Recommended product: SHIBAURA ELECTRONICS 

Co., Ltd. PB-41E 

Allowable rated power: 100 mW or more 

Impedance at abnormal temperature: 3 

 

0 to 5 VDC 

Input circuit

 

COM 

Analog 

power 

common 

 

Terminal 

symbol 

Terminal name 

Description 

Electrical 

characteristics 

FRQ

 ou

tp

our

 t

er

mi

na

FRQ

 out

p

ut

 

M

oni

tor

 out

p

ut

 

FRQ 

Digital monitor 

(Voltage) 

For digital monitor output, you can 
choose the PWM output method at 6.4 
ms  interval or pulse output method 
with about 50  % duty in which 
frequency varies. 

Pulse train output   

0 to 10 VDC 

 

Maximum allowable 
current: 1.2 mA 

 

Maximum frequency: 
3.60 kHz 

BC 

Common for 

digital monitor 

This common terminal is for digital 
monitor. This terminal “BC” is 
combined with the base voltage (0  V) 
against “P24”. 

 

5 VDC   

 

 

TH 

Thermistor 

4-7 

Summary of Contents for HF-430NEO Series

Page 1: ... dell Artigianato 23 20010 Cornaredo MI Italy TEL 39 293 481101 FAX 39 293 481103 Spain SM Cyclo Iberia S L U SMIB C Gran Vía Nº 63 Bis Planta 1 Departamento 1B 48011 Bilbao Vizcaya Spain TEL 34 9448 05389 FAX 34 9448 01550 United Kingdom SM Cyclo UK Ltd SMUK Unit 29 Bergen Way Sutton Fields Industrial Estate Kingston upon Hull HU7 0YQ East Yorkshire United Kingdom TEL 44 1482 790340 FAX 44 1482 7...

Page 2: ...umitomo No patent liability is assumed with respect to the use of the information contained herein Moreover because Sumitomo is constantly striving to improve its high quality products the information contained in this manual is subject to change without notice Every precaution has been taken in the preparation of this manual Sumitomo assumes no responsibility for errors or omissions Neither is an...

Page 3: ...equipment a complete understanding of the equipment specifications safety instructions precautions handling and operation instructions is required Please follow all the specifications and instructions for a proper use Additionally periodically review the HF 430NEO Instruction manual and User s Guide the HF TM2 User s Guide Precautions It is prohibited to reproduce or reform this document partially...

Page 4: ...chapter 4 1 4 2 Installation of HF TM2 4 1 5 1 About this chapter 5 1 5 2 Precaution for using 5 1 Warranty App 1 1 1 3 Symbol explanation 1 2 1 4 Precautions 1 2 2 4 Guide objectives 2 1 2 5 Guide outline 2 1 3 3 Verification after the purchase 3 1 4 3 Wiring of HF TM2 4 3 4 4 HF TM2 Terminal arrangement 4 5 5 3 List of affected parameter modes 5 2 Chapter 1 Safety Precautions Chapter 2 Overview ...

Page 5: ...a dangerous situation that have a high risk of causing death serious injuries and or major property damage Warning This category warns the user that in case of an incorrect or improper handling it leads to a dangerous situation that may cause death serious injuries and or major property damage Caution This category warns the user that in case of an incorrect or improper handling it leads to a dang...

Page 6: ...ns that must be done based on the instructions 1 4 Precautions 1 4 1 Please be careful If handled incorrectly or improperly it might cause death serious physical injuries or damage to the inverter motor or even the entire system Before installation wiring operation inspection or usage please read and fully understand this guide and other references There will be additional warnings about hazards a...

Page 7: ...ctricity like carpets Since the human body can get charged with static electricity as a safety measure please touch a safe metallic surface before handling this device 1 4 3 Precautions during the wiring Risk of an electric shock and or fire Be sure to ground the inverter Entrust the wiring work only to a qualified electrician Before the wiring work make sure to turn off the power supply and wait ...

Page 8: ... and do not let them get damaged Be sure to fix on the wiring and avoid extra burden to the connector and terminal 1 4 4 Precautions during operation and trial operation Risk of an electric shock or fire DO NOT touch the inside of this device check the signal do any wiring or plug unplug the connectors while it energized DO NOT insert any sick or rod like objects inside this device while it is ene...

Page 9: ...ibrations while operating 1 4 5 Precautions during Maintenance Inspection Risk of an electric shock Before the wiring work make sure to turn off the power supply and wait for more than 10 or 15 minutes depending on the inverter model Note Confirm that the charge lamp is OFF and the DC voltage between terminals P and N is 45 V or less Commit only a designated person to maintenance inspection and th...

Page 10: ...ansporter and industrial waste disposal operator Follow all laws and decrees related to procedures of waste management and public cleansing when disposing of this device 1 4 7 Other Precautions Risk of an injury an electric shock and or fire DO NOT modify HF TM2 Note In addition to the precautions described above there are other precautions described in the chapter 8 of the inverter user s guide P...

Page 11: ...stem design and workplace management This guide is written in SI units 2 4 Guide objectives The Guide is meant to provide necessary information for the following Installation and wiring of the product Parameter setting 2 5 Guide outline The guide consists of the following chapters Safety Precautions Chapter 1 includes safety instructions for installation wiring operation maintenance and inspection...

Page 12: ...ckage 3 3 Verification after the purchase Please verify the items written on the right when unpacking In case there is any doubt or trouble with the product please contact your sales agent as soon as possible 3 Chapter 3 Enclosed Items HF TM2 x1 User s guide x1 Check that the items were not smashed or damaged during the delivery Check that there is a HF TM2 there is a User s Guides when unpacking ...

Page 13: ...430NEO and confirm the control terminal like the following picture Fig 1 Regarding the detail they are written in user s guide of HF 430NEO Fig 1 Remove the 2 screws and disconnect the connector between standard control terminal board and logic board to the direction of the arrow Fig 2 Fig 2 4 Chapter 4 Installation and Wiring Control terminal board Standard model Direction to disconnect Screw Con...

Page 14: ...the terminal space after removing the standard control terminal board Fig 3 Align the connector of logic board with the connector of HF TM2 And then connect HF TM2 to the direction of the arrow Fig 4 Fig 4 Fix HF TM2 with the 2 screws Fig 5 Screw Screw Direction to install ...

Page 15: ...oltage input Current input Thermistor RS485 terminal Serial communication Analog input IRF Analog input VF2 Operation part USB RJ45 PC SAFS001 Operator panel OS 44 The signal ground for RS485 terminal is BC FR RR DFL DFM AUT MBS JOG ES RST Input terminal P24 PCS BC DC24 Default jumper position Sink logic Source logic FRQ When using source logic connect the shield to BC When using the terminating r...

Page 16: ... reverse orientation and input of voltage current is reversed short circuit occurs between V and COM wiring of a knob causes short circuit between V and COM at 0Ω etc may cause failure For wiring to the control circuit terminal block use twisted shield wires Recommended diameter is 0 75mm2 and connect the shield films to each common terminal Recommended tightening torque is 0 5 to 0 7 N m for M3 s...

Page 17: ...act signal When using source logic P24 terminal become common terminal for input contact 100 mA output at maximum BC Common for 24 VDC output power supply terminal This is a common terminal for power terminal P24 and digital input terminal FR RR DFL DFM AUT MBS JOG ES RST When using sink logic BC become common terminal for input contact There are two BC terminals PCS Common for Input terminal Swit...

Page 18: ...input output Power supply COM Common for analog power supply Common terminals for analog input terminals VRF IRF VF2 analog output terminals AMV AMI and thermistor terminal TH V Speed setting power supply This is a 10 VDC power supply It is used when using analog input terminals VRF VF2 and variable resistor for inputting voltage Allowable load current 20 mA Analog input VRF Analog input terminal ...

Page 19: ... can be adjusted from 0 to 10000 Ω Recommended thermistor characteristics Recommended product SHIBAURA ELECTRONICS Co Ltd PB 41E Allowable rated power 100 mW or more Impedance at abnormal temperature 3 kΩ 0 to 5 VDC Input circuit COM Analog power common Terminal symbol Terminal name Description Electrical characteristics FRQ outpour terminal FRQ output Monitor output FRQ Digital monitor Voltage Fo...

Page 20: ...4 to 1 0 mm2 Stranded wire with rod terminal 0 25 to 0 5 mm2 Length of stripped wire 5 mm Tightening torque 0 22 to 0 25 N m M2 screw Terminal symbol Terminal name Description Electrical characteristics RS485 communication Serial communication SP SN RP BC RS 485 terminal for serial communication SP terminal RS 485 differential signal SN terminal RS 485 differential signal RP terminal Connect to SP...

Page 21: ...er or any power cables When the emergency stop function is enabled input terminal DFL is used exclusively for this function Configure the input terminal DFL function CA 03 to no 000 Not use When input terminal DFL has other function the inverter may malfunction To enable this function set the slide switch SW1 of HF TM2 to ON With the factory setting slide switch SW1 is set to OFF to disable the fu...

Page 22: ...oard Reset Optional External thermistor TH TH Please note that the common terminal is different between each device Common TH COM RUN command Terminal FR FR Input terminal FR function is corresponding to FR terminal of HF TM2 This terminal has forward rotation function as default Configuration availability Initial setting available Pulse train input DFH DHH Digital output RL Table 2 Invalid termin...

Page 23: ...source selection 1st motor bA201 Upper frequency limit source selection 2nd motor CA 70 Frequency reference selection when F OP is active CA 10 Input terminal DFH function Don t change these parameters due to prevention the malfunction CA 11 Input terminal DHH function CA 30 Input terminal DFH a b NO NC selection CA 31 Input terminal DHH a b NO NC selection CA 50 Input terminal DFH response time B...

Page 24: ...y 1 Installation connection combination or integration of the Product in or to the other equipment or machine that rendered by any person or entity other than the Seller 2 Insufficient maintenance or improper operation by the Buyer or its customers such that the Product is not maintained in accordance with the maintenance manual provided or designated by the Seller 3 Improper use or operation of t...

Page 25: ... dell Artigianato 23 20010 Cornaredo MI Italy TEL 39 293 481101 FAX 39 293 481103 Spain SM Cyclo Iberia S L U SMIB C Gran Vía Nº 63 Bis Planta 1 Departamento 1B 48011 Bilbao Vizcaya Spain TEL 34 9448 05389 FAX 34 9448 01550 United Kingdom SM Cyclo UK Ltd SMUK Unit 29 Bergen Way Sutton Fields Industrial Estate Kingston upon Hull HU7 0YQ East Yorkshire United Kingdom TEL 44 1482 790340 FAX 44 1482 7...

Reviews: