background image

Section 2

DESCRIPTION

9

water--flow regulating valve (not shown) which oper-

ates to conserve water during periods of varying

load on the compressor. This same valve automati-

cally shuts off the water supply when the compres-

sor is shut down. In addition, water--cooled models

have a water pressure switch to prevent operation

with inadequate water pressure.

2.5 COMPRESSOR DISCHARGE SYSTEM, FUNC-

TIONAL DESCRIPTION 

.

Refer t o F igur es 

2 -- 3

 and 

2 -- 4

. T he c ompr es s or unit

discharges the compressed air/fluid mixture into the

combination receiver/sump.

The receiver has three basic functions:
1. It acts as a primary fluid separator.

2. Serves as the compressor fluid sump.

3. Houses the final fluid separator.
The compressed air/fluid mixture enters the receiv-

er and is directed against the internal baffle. The

direction of movement is changed and its velocity

significantly reduced, thus causing large droplets of

fluid to form and fall to the bottom of the receiver/

sump. The fractional percentage of fluid remaining

in the compressed air collects on the surface of the

separator element as the compressed air flows

through the separator. A return line (or scavenge

tube) leads from the bottom of the separator ele-

ment to the inlet region of the compressor unit. Fluid

collecting on the bottom of the separator is returned

to the compressor by a pressure differential be-

tween the receiver and the compressor inlet. A visu-

al sight glass is located on the return line to observe

this fluid flow. There is also an orifice in this return

line (protected by a strainer) to assure proper flow.

A secondary separator element with a separate re-

turn line, strainer, sight glass and orifice further re-

duce the fluid carry--over to less than 1 ppm (parts

per million). A gauge, located on the instrument

panel, shows red if abnormal pressure drop through

the separator develops. At this time, separator ele-

ment replacement is necessary. This gauge must

be checked with the compressor running fully

loaded.

A minimum pressure/check valve, located down-

stream from the separator, assures a minimum re-

ceiver pressure of 55 psig (3.8 bar) during loaded

conditions. This pressure is necessary for proper

air/fluid separation and proper fluid circulation.

A terminal check valve is incorporated into the mini-

mum pressure/check valve to prevent compressed

air in the service line from bleeding back into the re-

ceiver on shutdown and during operation of the

compressor in an unloaded condition.

A pressure relief valve (located on the wet side of

the separator) is set to open if the sump pressure ex-

ceeds the sump tank rating. A temperature switch

will shut down the compressor if the discharge tem-

perature reaches 235

_

F (113

_

C).

2.6 CONTROL SYSTEM,

FUNCTIONAL

DE-

SCRIPTION- STANDARD ELECTRO-MECHANI-

CAL

Refer t o F igur e 

2 -- 5

. T he pur pos e of t he c ompr es s or

Control System is to regulate the compressor air in-

take to match the amount of compressed air being

used. At approximately 10 psig (0.7 bar) air line

over--pressure, the control system will automatically

blow down the compressor and greatly reduce the

unload power consumption. The Control System

consists of an

inlet valve

, (located on the compres-

sor air inlet),

blowdown valve

,

solenoid valve

,

pressure switch

, and a

pressure regulator

. The

functional descriptions of the Control System are

given below in four distinct phases of compressor

operation. The following guidelines apply to all

LS--12 and LS--16 Series compressors. For explan-

atory purposes this description will apply to a com-

pressor with an operating pressure range of 115 to

125 psig (7.9 to 8.6 bar). A compressor with any oth-

er pressure range would operate in the same man-

ner excepting stated pressures.

START - 0 TO 50 PSIG (0 TO 3.5 BAR)

When the compressor START button is depressed,

the sump pressure will quickly rise from 0 to 50 psig

(0 to 3.5 bar). During this period both the pressure

regulator and the solenoid valve are closed, the inlet

valve is fully open due to inlet air flow, and the com-

pressor pumps at full rated capacity. The rising com-

pressor air pressure is isolated from the service line

in this phase by the minimum pressure valve, set at

approximately 50 psig (3.5 bar).

NORMAL OPERATING MODE - 50 TO 115 PSIG

(3.5 TO 7.9 BAR )

When the pressure air rises above 50 psig (3.5 bar),

the minimum pressure/check valve opens and deliv-

ers compressed air to the service line. From this

point on, the line air pressure is continually moni-

tored by a line pressure gauge and a pressure

switch usually set at 125 psig (8.6 bar). The pres-

sure regulator and the solenoid valve remain closed

during this phase. The inlet valve remains fully open

for maximum capacity.

MODULATING MODE - 115 TO 125 PSIG (7.9 TO

8.6 BAR)

If less than the rated capacity of compressed air is

being used, the service line pressure will rise above

115 psig (7.9 bar). The pressure regulator valve

gradually opens, applying air pressure through the

control line to the inlet valve piston. This causes the

inlet valve to partially close reducing the amount of

air entering the compressor until it matches the

amount of air being used. The control system func-

tions continually in this manner, between the limits

of 115 to 125 psig (7.9 to 8.6 bar), in response to

varying demands from the service line.
The pressure regulator has an orifice which vents a

small amount of air to the atmosphere when the

pressure regulator controls the inlet valve. The ori-

fice also bleeds any accumulated moisture from the

control lines.

Summary of Contents for LS-10 series

Page 1: ...Part Number 02250126 405 eSullair Corporation OPERATOR S MANUAL KEEP FOR FUTURE REFERENCE LS12 LS16 ELECTRO MECHANICAL ADDENDUM CONTROLLER...

Page 2: ...t Sullair s corporate headquarters in Michigan City Indiana Instruction includes discussion of the function and installation of Sullair service parts troubleshooting of the most common problems and ac...

Page 3: ...DESCRIPTION 9 2 5 COMPRESSOR DISCHARGE SYSTEM FUNCTIONAL DESCRIPTION 9 2 6 CONTROL SYSTEM FUNCTIONAL DESCRIPTION STANDARD ELECTRO MECHANICAL 11 2 7 AIR INLET SYSTEM FUNCTIONAL DESCRIPTION 11 2 8 INSTR...

Page 4: ...DARD CONTINUED ELECTRO MECHANICAL Section 5 OPERATION 25 5 1 GENERAL 25 5 2 PURPOSE OF CONTROLS STANDARD ELECTRO MECHANICAL 27 5 3 INITIAL START UP PROCEDURE 27 5 4 SUBSEQUENT START UP PROCEDURE 27 5...

Page 5: ...t off throttle valve either at the compressor or at any other point along the air line when an air hose exceeding 1 2 13mm inside diameter is to be connected to the shut off throttle valve to reduce p...

Page 6: ...rags trash leaves litter or other com bustibles out of and away from the compressor J DO NOT operate the compressor without proper flow of cooling air or water or with inadequate flow of lubricant or...

Page 7: ...ded with open electrical enclosures If necessary to do so then disconnect lock out and tag all power at source so others will not inadvertently restore power E Disconnect lock out and tag all power at...

Page 8: ...ge enough to hold a person and if it is necessary to enter it to per form service adjustments inform other personnel before doing so or else secure and tag the access door in the open position to avoi...

Page 9: ...brication and cooling system capacity control system instrument panel aftercooler a com bination separator and trap all mounted on a heavy gauge steel frame On air cooled models a fan draws air over t...

Page 10: ...ly open when the fluid temperature is below 170_F 77_C The fluid passes through the thermal valve the main filter and directly to the compressor unit where it lu bricates cools and seals the rotors an...

Page 11: ...Section 2 DESCRIPTION 7 Figure 2 3 Comporessor Fluid Cooling Lubrication and Discharge System Air cooled...

Page 12: ...THERMAL VALVE MINIMUM PRESSURE CHECK VALVE SEPARATOR ELEMENT MOISTURE SEPARATOR SUMP TANK FLUID AIR FLUID AIR AFTERCOOLER FLUID COOLER WATER CONTROL VALVE Figure 2 4 Compressor Fluid Cooling Lubricati...

Page 13: ...e compressor if the discharge tem perature reaches 235_F 113_C 2 6 CONTROL SYSTEM FUNCTIONAL DE SCRIPTION STANDARD ELECTRO MECHANI CAL Refer to Figure 2 5 The purpose of the compressor Control System...

Page 14: ...REGULATOR VALVE PRESSURE SWITCH SOLENOID VALVE TO LINE PRESSURE SWITCH AIR INLET VALVE CHECK VALVE BLOWDOWN VALVE SUMP TANK STRAINER SHUTTLE VALVE TO LINE PRESSURE SWITCH SOLENOID VALVE PRESSURE SWIT...

Page 15: ...lications with varied periods of time when there are no air requirements Supervisor s AUTO MATIC mode allows the compressor to shutdown time delayed when no compressed air require ment is present and...

Page 16: ...strument panel indicates when power to the compressor is supplied S The ON LED indicates when the compressor is running S The AUTO pad is used to enable automatic control S The RUN Status LED indicate...

Page 17: ...ANCE GAUGE STOP DISCHARGE TEMPERATURE GAUGE LINE PRESSURE GAUGE AIR FILTER MAINTENANCE GAUGE STOP PAD POWER ON LED ON LED AUTO MODE LED RUN AUTO AUTO PAD RUN CONTROLS START PAD Locations of pressure a...

Page 18: ...14 NOTES...

Page 19: ...5 80 72 1830 48 1220 60 1524 2350 1066 80 87 XH 50 37 150 4 25 72 1830 48 1220 60 1524 2060 934 80 87 60 45 182 5 15 72 1830 48 1220 60 1524 2350 1066 80 87 LS 16 SERIES 50 Hz MODEL I HP KW CAPACITY...

Page 20: ...l MOTOR VIII STANDARD MODELS Size 50 60 and 75HP Type C Flanged Open Dripproof Premium Efficiency Three Phase 230 460 60 Hz 380 415 400 50 Hz 40_C Maximum Ambient Temperature Options Available 200V an...

Page 21: ...idation and foam inhibitors and good water separation characteristics should be used DO NOT MIX DIFFERENT TYPES OF FLUIDS Contamination of non detergent mineral fluids with traces of detergent motor f...

Page 22: ...Section 3 SPECIFICATIONS 18 Figure 3 1 Wiring Diagram LS12 LS16 Air cooled Water cooled...

Page 23: ...Section 3 SPECIFICATIONS 19 Figure 3 2 Wiring Diagram LS12 LS16 Air cooled Water cooled Wye Delta...

Page 24: ...20 NOTES...

Page 25: ...e With air cooled com pressors it is possible to use this heat for space heating providing no additional pressure drop is created across the fan Consult a Sullair office for assistance in utilizing th...

Page 26: ...ith OSHA National Electrical Code and or any other applicable State Federal and local electrical codes concerning isolation switches fused disconnects etc Sullair provides a wiring diagram for use by...

Page 27: ...el Verify proper rotation by observing the motor shaft from the end opposite the compres sor unit the shaft should be turning clockwise If the motor shaft is not turning clockwise disconnect the power...

Page 28: ...24 NOTES...

Page 29: ...e switch trips to the reload setting Dual control is enabled by pressing the AUTO pad HOURMETER Records cumulative hours of compressor operation useful for planning and logging service schedules LINE...

Page 30: ...E SWITCH discharge temperature reaches 235_F 113_C WATER PRESSURE SWITCH It prevents operation when water pressure of water cooled compressors only compressor is inadequate PRESSURE RELIEF VALVE Opens...

Page 31: ...en made 3 Crack open the shut off valve to the service line 4 Start the compressor by pressing the START I pad 5 Check for possible leaks in piping 6 Slowly close the shut off valve and check that the...

Page 32: ...28 NOTES...

Page 33: ...functioning properly Low Incoming Line Voltage Check voltage Should voltage check low consult power company COMPRESSOR SHUTS DOWN WITH Loss of Control Voltage Reset If trouble persists check that lin...

Page 34: ...necessary kit avail able Plugged Control Line Strainer Clean strainer screen and o ring replacement kit available Defective Blowdown Valve Check that sump pressure is exhausted to the atmosphere when...

Page 35: ...NOTES...

Page 36: ...ichigan City Indiana 46360 U S A Telephone 1 800 SULLAIR U S A Only or 1 219 879 5451 Fax 219 874 1273 Fax 219 874 1835 Parts SULLAIR ASIA LTD Sullair Road No 1 Chiwan Shekou Shenzhen Guangdong PRV PR...

Reviews: