background image

13

CRC1100A

14

CRC1100A

0Min

99Min

30Min

31

Use UP/DOWN key to set 
desired value. 

press the SET key.

To change the 
AL parameter, 

Function : Power on time 
delay for Alarm(HT/LT).

PROGRAMMING MODE 
POWER ON ALM DLY

AL Parameter

0

1

0

32

Use UP/DOWN key to set 
desired value. 
This parameter can lock the 
keypad so that tampering is 
not possible by by-standers.

1 = Activates keypad lock.
0 = De-activates keypad lock.

On activation, all the 
parameters can only be 
viewed but not modified.

press the SET key.

To change the 
LP parameter, 

39

Once the set key is 
pressed,the control goes into 
the normal mode and displays 
the temperature and all 
settings are recorded.

To end 
programming press 
the SET key.

0

1

0

33

Useful to debug setting 
problems.

When set to 1, all parameters 
are programmed to factory set 
vales.

Use UP/DOWN key to set 
desired value. 

1 = Revert to factory set 
parameters. 

FS parameter, 

To change the 

press the SET key.

Function : To lock keypad.

PROGRAMMING MODE 
LOCK KEYPAD

LP Parameter

PROGRAMMING MODE 
END OF PROG.

End Parameter

Function 

: To end 

programming. 

Function: Revert to factory set 
parameters.

PROGRAMMING MODE 
RESET PARAMETERS

FS Parameter

Example : 

If you set this 

parameter to 20min, once the 
power is switch on, the alarm 
for Ht/Lt will not activate for 20 
minutes after the power is 
switched on. This is most 
useful to avoid the nuisance 
alarms when the ambient are 
high when machine is 
switched on after long time. 

Technical Data

Operating Messages and Icon Status

Message

Description

Parameter

Ht

Lt

PP

LP

Defrosting in progress

P7

P2

P3

SP, P4,P6

L1, L4,L2

E3, E4, E5

Temperature above the maximum 
limit of the set point. 

Temperature below the minimum limit 
of the set point. (P3)

Comp. Relay On.
Comp. Relay Off.
Comp. Relay Timedelay.

Probe short circuit, circuit open or 
without probe, or temperature

O

O

> 50 C or <-50 C

heater fault)

Alarm (Ht, Lt, PP, HP/LP trip, 

Keypad locked/unlocked.

Drip time On.

E

Evap. Relay Off.
Evap. Relay Timedelay.

Evap. Relay On.

C

Cond. Relay Off.

Cond. Relay On.

Cond. Relay Timedelay.

P6, d1

* HP/LP TRIP *

OSS

HEATER FAULT

HP/LP/OSS (pressure) has tripped and 
a signal has been sent through the 
Digital Input.

O

Temp of coil has not risen by 10 C 
within 50 % of the defrost time.

Mode

On
Off
flashing

On
Off

On
Off

On

On

On
Off
flashing

On
Off
flashing

Toggle

Toggle

On

Cond. Fan Relay  

8(3)A/250Vac.

Output  

 

Input  

 

2 NTC Probe.

O

Resolution  

1 C

Data Storage  

Non-Volatile EEPROM Memory.

O

Accuracy   

+/-1 C

O

O

Storage temp  

-20 C to 70 C (non-condensing).

O

O

Operating Temp  

5 C to 50 C (non-condensing)

Power Input  

230Vac, 50-60Hz AC, Others on request.

Alarm Relay  

5A/250Vac.

O

O

Range  

 

-50 C to +50 C

Other Relay  

8(2)A/250Vac.

Housing    

ABS Plastic.

Panel Cutout 

92X92mm.

 

 

  

<

 2.5sq mm one wire/ terminal only.

Mounting   

Panel.

Display  

 

:

 2X14.2mm (0.56”) LED + LCD.

Dimensions  

Front - 96 x 96 MM, Depth 85 MM

Connection  

Screw

 

Terminal.

Summary of Contents for SZ-CRC-1100A

Page 1: ...COLD ROOM CONTROLLER SZ CRC 1100A USER MANUAL www pvrcontrols com...

Page 2: ...e 9 COIL PROBE CALIB L5 Parameter Evap fan status during defrost 9 FAN WHEN DEFROST L6 Parameter Index DESCRIPTION PARAMETER Pg No CRC1100A Evap fan status on door open FAN WITH DOOR L7 Parameter 9 Al...

Page 3: ...obe error or temperature alarm the instrument signals the event through acoustic signal and by closing the relay contact By pressing the mute key the buzzer is silenced and the relay contact is opened...

Page 4: ...his mode press QF key for 4 seconds The compressor operates in this mode for time duration set through quick freeze time duration Ct parameter and set pint through Quick freeze set point CS parameter...

Page 5: ...time parameter press the SET key PROGRAMMING MODE COMP IN PRB FAIL P8 Parameter PROGRAMMING MODE CYC ON TIME ON Time Parameter 07 CRC1100A 08 CRC1100A 3Min 20Min 4Min 9B Function If P8 1 Cyclic OFF t...

Page 6: ...PROGRAMMING MODE FAN WITH DOOR L7 parameter 0sec 30sec 10sec 18 Function To set Condenser delay to start before comp Example If this parameter set to 10 sec and P6 3 min then condenser will turn ON 1...

Page 7: ...Parameter 0Min 99Min 30Min 26 Function To set Maximum defrost duration PROGRAMMING MODE MAX DEF DURATION E4 Parameter 11 CRC1100A 12 CRC1100A This is the maximum amount of time allowed for a defrost I...

Page 8: ...This is most useful to avoid the nuisance alarms when the ambient are high when machine is switched on after long time Technical Data Operating Messages and Icon Status Message Description Parameter H...

Page 9: ...Hours DEFROST No Defrost because O coil temp 8 C E5 Parameter UNIT ON UNIT ON 4 Hours DEFROST DEFROST 6 Hrs E3 Parameter Setting Manual Defrost Key Pressed Depends on E4 E5 Parameter whichever achiev...

Page 10: ...ts in materials and workmanship for a period of one year from the date of purchase During the warranty period product determined by us to be defective in form or function will be repaired or at our op...

Page 11: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Reviews: