To set tripping voltage of digital inputs.

FAULT SENS LOGIC

11

To set differential for  Condenser.

COND. SET DIFF.

11

To set LP fault to Auto or Manual reset.

Enable / disables liquid level sensing .

LP FAULT RESET

LIQ. LEVEL SENSOR

13

13

To set Condenser set temperature.

COND SET TEMP.

11

10

To enable or disable condenser probe.

COND PROBE ACTIVE

To set Ct faults auto or manual reset.

CURRENT FAULT RST

15

This parameter configures pump 
working logic

To enable / Disable Current Sensing

Lower current limit for the compressor .

PUMP RUN LOGIC

CURRENT INPUT

CURRENT LO LIMIT

13

14

15

Higher current limit for the compressor 

15

CURRENT HI LIMIT

No. of retrials before sensing underload 
/ overload fault in auto mode

15

CURRENT RETRIALS

This decides whether controller should 
display faults in stand by mode or not. 

FAULT IN STAND BY

12

NC-120A

NC-120A

To set the cutout point of the Controller.

To set Chiller Set point 

To set compressor restart delay.

To set minimum allowable low 
temperature limit and alarm..

To enable or disable Antifreeze  function.

To set Antifreeze set point. 

To set  Antifreeze differential 

To set Main(Liquid) probe calibration.

To set Antifreeze  probe calibration.

To set Condenser probe calibration .

CHILLER SET TEMP.

To set other parameters

CHILLER SET TEMP.

COMP TIME DELAY.

HIGH TEMP. ALARM

LOW TEMP. ALARM

AFT PROBE STATUS

AFT SET TEMP.

AFT DIFFERENTIAL

LIQ. PROBE CAL.

AFT PROBE CAL.

COND PROBE CAL.

PROGRAM MODE

SET MODE

HT POWER ON DLY

DESCRIPTION

PARAMETER

Pg. 
No. 

06

06

06

06-07

07

07

08

08

08

09

09

09

10

10

DIFFERENTIAL 

To set temperature differential for 
compressor restart.

To set maximum allowable high 
temperature limit & alarm.

This sets Power ON delay for high 
temperature alarm to avoid false 
alarms. 

To set Current calibration.

CURRENT CAL

10

To set LP fault sensing delay 

LP SENSING DLY

12

To set HP and AFT fault to Auto or 
Manual reset. 

HP/AFT RESET

12

This parameter configures condenser 
working logic.

COND RUN LOGIC

14

COND START DLY

14

This parameter set the time delay that 
condenser should start before 
compressor.

It sets normal delay for EWFS fault 
sensing.This avoids false tripping due 
to water splashing.

EWFS NORMAL DLY

16

It sets power on delay for EWFS fault 
sensing.

EWFS SATRTUP DLY

16

This configures AUX i/p as EWFS fault or 
as AUX i/p to switch off whole system.

CONFIG AUX I/P

16

DESCRIPTION

PARAMETER

Pg. 
No. 

Summary of Contents for NANOCHILL NC-120A

Page 1: ...User Manual NANOCHILL NC 120A www pvrcontrols com RST 2 SET NANOCHILL ...

Page 2: ...rameters u Auto Manual reset for HP LP and AFT The Subzero NANO CHILL NC 120 are controllers that integrates all the basic control functions required by a chiller A user friendly Lcd screen displays all parameters status and alarm messages u Range 30 0ºC to 50 0ºC u HP LP Compressor O L SPP Pump O L Auxiliary Fault Introduction Features Items included 01 NC 120A NC 120A 02 NO 1 2 3 4 5 QTY 1No 1No...

Page 3: ...point To set Antifreeze differential To set Main Liquid probe calibration To set Antifreeze probe calibration To set Condenser probe calibration CHILLER SET TEMP To set other parameters CHILLER SET TEMP COMP TIME DELAY HIGH TEMP ALARM LOW TEMP ALARM AFT PROBE STATUS AFT SET TEMP AFT DIFFERENTIAL LIQ PROBE CAL AFT PROBE CAL COND PROBE CAL PROGRAM MODE SET MODE HT POWER ON DLY DESCRIPTION PARAMETER ...

Page 4: ...tart delay Contd Parameter List Min MINIMUM Max MAXIMUM Fact Set FACTORY SETTING DEFAULT Use UP DOWN keys to set desired value parameter press the set key To change Comp Time Delay NC 120A SET MODE PROGRAM MODE INDEX 05 Once the SET key is pressed the control goes into the normal mode and displays the temperature SET EXIT UP DOWN SCROLL 19 To set customer name to be displayed at controller power O...

Page 5: ...er is set to 0 50 0 C then once chiller temperature 0 goes above 50 0 C then controller will show Ht and alarm will be ON Range Min Max Fact Set Range Min Max Fact Set Range Min Max Fact Set AFT SET TEMP Use UP DOWN keys to set desired value EXAMPLE If this parameter is set to 5 0ºC controller will trip the compressor on Antifreeze fault if the AFT sensor goes below 5 0ºC To change AFT SET TEMP pa...

Page 6: ... only when the AFT Temperature goes above 7 0ºC 5 0ºC 2 0ºC 1 0ºC 10 0ºC 2 0ºC Range Min Max Fact Set Range Min Max Fact Set Range Min Max Fact Set Sr No Parameter LCD Message Description of parameters and functions Parameter setting method Use UP DOWN keys to set desired value EXAMPLE Same as Main Probe Cal To change Cond Probe Cal parameter press the set key Range Min Max Fact Set 10Amp 10Amp 0A...

Page 7: ...Set voltage level 230Vac 0Vac Controller will sense faults at 0 230Vac Controller will sense faults at 20 Range Min Max Disable Enable Disable FAULT IN STAND BY Function This decides whether controller should display faults in stand by mode or not To change Fault in Stand By parameter press the set key mode Note Eventhough the fault sensing is disabled in satnd by controller will display High temp...

Page 8: ...e Description of parameters and functions Parameter setting method And if this delay is set to 10seconds then condenser will switch on 10 seconds before compressor Use UP DOWN keys to set desired value If condenser is running with compressor COND RUN LOGIC always on With Comp Condensor will switch on off with compressor Always On Condensor will remain Use UP DOWN keys to set desired value 26 Funct...

Page 9: ...tions Parameter setting method 35 EWFS NORMAL DLY Function It sets normal delay for EWFS fault sensing This avoids false tripping due to water splashing 34 Range Min Max 0Sec 120Sec 10Sec EWFS STARTUP DLY Function It sets power on delay for EWFS fault sensing To change EWFS Startup Dly parameter press the set key Use UP DOWN keys to set desired value Fact Set 33 CONFIG AUX I P Function This config...

Page 10: ...ocked to set parameter press the set key To change Keypad Lock To change Clear Fault Log parameter press the set key 39 40 Function To lock keypad Function To clear last fault history Range Min Max Fact Set Range Min Max Fact Set Use UP DOWN keys to set desired value Store Store fault history Example If this parameter is set to Clear then it will clear all previous faults saved in the memory Store...

Page 11: ...sired value Customer can set service telephone number which will display at power ON 47 Function To set customer service number parameter press the set key To change Enter Your No SET EXIT UP DOWN SCROLL Once the SET key is pressed the control goes into the normal mode and displays the temperature 48 Function To end programming To end Program mode press set key 2 RST Press for 4 seconds to reset H...

Page 12: ...Relay 5A 250Vac Current Input 0 to 20Amp 0 Resolution 0 1 C 0 0 Probe Tolerance 0 3 C AT 25 C 0 0 Storage Temp 20 C to 70 C non condensing 0 Accuracy 1 C Resolution 0 1Amp 0 0 Range 30 0 C to 50 0 C Technical Data 22 NC 120A NC 120A Suggested Wiring Diagram PHASE NEUTRAL 1 2 1 4 8 2 5 9 3 6 10 7 11 14 12 15 13 16 17 24 25 19 23 26 20 27 21 22 LIQUID AFT COND NEUTRAL COMP O L HP LP SPPR PUMP O L AU...

Page 13: ...troller with a soft moist cloth Do not use abrasive detergents petrol alcohol or solvents Fixing and dimensions of panel models To fix the unit slide the side lock 1 through the guides 2 as per the position shown in the figure Move the side lock in the direction of the arrow it permits to move the fastener in the opposite direction of the arrow 3 Fit the screw in the side lock in direction of the ...

Page 14: ...her than by the company This warranty is in lieu of any other warranty expressed or implied In no event shall the company be held liable for incidental or consequential damages such as lost revenue or lost business opportunity arising from the purchase of this product INDIA Ball Valves Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller...

Reviews: