DLY

LP SENSING 

Use UP/DOWN keys to set desired value. 

To change  LP Sensing Dly 
parameter, press the set key.

18

Function: To set LP fault sensing delay 
on compressor on.

Sr.No. 

Parameter 

(LCD Message)

Description of parameters and functions.

Parameter setting

 method. 

Manual

Auto

Auto

HP / AFT RESET

Use UP/DOWN keys to set desired value. 

Auto     = It sets the HP- AFT faults for 

           

Manual = It sets the HP- AFT faults for 
  

   manual reset.

 

  auto  reset. 

To change  HP / AFT reset
Parameter, press the set key.

19

Function: This parameter will set HP and 
AFT fault to Auto or Manual reset.

Range

Min 

Max 

   Fact. Set 

Manual

Auto

Auto

Range

Min 

Max 

   Fact. Set 

LP FAULT RESET

20

Function: This parameter will set LP fault 
to Auto or Manual reset.

To change  LP Fault Reset
Parameter, press the set key.

Manual = It sets the LP fault for manual   
 

    reset.

Use UP/DOWN keys to set desired value. 

Auto  

= It sets the LP fault for auto reset.

1 SEC

90 SEC

30 SEC

Range

Min 

Max 

   Fact. Set 

EXAMPLE:

 If this parameter is set at 30 

seconds,  the  system  will  ignore  low 
pressure  alarm  for  30  sec  from 
compressor  on.  In  this  manner,  a  false 
alarm can be avoided due to low pressure 
at compressor start up.

12

Sr.No. 

Parameter 

(LCD Message)

Description of parameters and functions.

Parameter setting

 method. 

Always On With Comp With Comp

PUMP RUN LOGIC

Use UP/DOWN keys to set desired value. 

With Pump =In this case pump will switch 

Always On = It sets the pump to always on 
 

     mode.

                     On and off with compressor.

Parameter, press the set key.

To change Pump Run Logic

24

Function : This parameter configures 
pump to keep always ON or OFF with 
compressor.

Range

Min 

Max 

   Fact. Set 

Disable = This parameter disables Liquid 

                level sensing in the controller.

                level sensing in the controller.
Enable  = This parameter enables Liquid 

Range

Min 

Max 

   Fact. Set 

Disable

Enable

Disable

Parameter, press the set key.

To change Liq Level Sensor

LIQ LEVEL SENSOR

21

Function:  This  parameter  enable/ 
disables liquid level sensing.

Use UP/DOWN keys to set desired value. 

If set to 

Use UP/DOWN keys to set desired value.

Disable = Controller will start in stand by 
mode at power ON press start 

               power ON.

Enable = Will start the system when  

    

Parameter, press the set key.

To change System Autostart

Range

Min 

Max 

   Fact. Set 

Disable

Enable

Enable

SYSTEM AUTOSTART

23

Function:  This  parameter  configures 
system to auto start or manual start   on 
power on.

If set to
ON HI LVL : This sets level fault on High

 

   level.

 

   level.

ON LO LVL : This sets level fault on low

Range

Min 

Max 

   Fact. Set 

ON LO

LVL

LVL

ON HI

ON LO

LVL

To change Liq Level Fault
Parameter, press the set key.

LIQ LEVEL FAULT

22

Function:  This  parameter  is  used  to  set 
Liquid level fault on high level or low level.
Use UP/DOWN keys to set desired value. 

Summary of Contents for MICRO CHILL

Page 1: ...www pvrcontrols com INDIA...

Page 2: ...nical Data 15 Suggested Wiring Diagram 16 Panel Cutout Dimensions 17 2 LIQ LEVEL FAULT To set liquid level fault on high level or low level 12 1 Index Index Introduction Get to Know Your Controller Pa...

Page 3: ...on for Compressor FEATURES The MICRO CHILL is a Single compressor chiller controller This integrates all the required functions of the chiller It is very user friendly due to the LCD provided which gi...

Page 4: ...arameter setting method 01 Press and hold set key for 2 seconds and release Range Min Max Fact Set Lt 0 5 C Ht 0 5 C 10 0 C PROGRAM MODE To set other parameters Hold key for 2 seconds and release LCD...

Page 5: ...age Description of parameters and functions Parameter setting method 1 0 C 10 0 C 2 0 C EXAMPLE If this parameter is set at 3 minutes the compressor will cut off at the set temperature but will not re...

Page 6: ...0 C 10 0 C 0 0 C 9 Sr No Parameter LCD Message Description of parameters and functions Parameter setting method AFT SET TEMP Use UP DOWN keys to set desired value To change AFT SET TEMP parameter pres...

Page 7: ...On With Comp With Comp PUMP RUN LOGIC Use UP DOWN keys to set desired value With Pump In this case pump will switch Always On It sets the pump to always on mode On and off with compressor Parameter pr...

Page 8: ...e Parameter press the set key 32 Function To end programming 13 Sr No Parameter LCD Message Description of parameters and functions Parameter setting method RELAY3 LOGIC Use UP DOWN keys to set desire...

Page 9: ...Panel Cutout 91 X 91 MM ALL Relay 5A 250VAC 2 5 sq mm one wire terminal only O O Range 30 C to 70 C Data storage Non volatile EEPROM memory Digital Input Potential 230Vac O O Probe tolerance at 25 C 0...

Page 10: ...on water and corrosive gasses and where ambient temperature does not exceed the values specified in the technical data Probe To give a correct reading the probe must be installed in a place protected...

Page 11: ...e purchase of this product 19 Specifications are subject to change due to continuous improvements of our products No consequential damage or field labour is included in the sales of products mentioned...

Reviews: