Contact your dealer
4. System failure
The trouble shooting chart covers most of the difficulties that you may
encounter under normal working conditions. Should the UPS fails to
operate properly, please check the following before calling for service:
1.
Is the UPS plugged into an incorrect wall receptacle?
2.
Is AC Input voltage / frequency out of range?
When calling for service, please offer the following information:
1.
Model No. and Serial No.
2.
Date of occurrence of the problem.
3.
Full description of problem, including condition, environment
which it is installed, devices connected to the UPS.
4.Trouble Shooting
4.Trouble Shooting
Possible Cause
Problem
Trouble Shooting
No light,
No Alarm
switch
1. AC fuse Blown
Replace AC fuse of actual rating
Turn On mains switch
Contact your dealer
Reduce Load
Check load & output side properly for shorting
Battery is low due to excessive load or battery is
consumed.
Wait, until mains returns.
Connect AC power cord to wall rec eptacle
2.Power cord is loose
3. Mains switch is not "ON"
4. System failure
UPS switched off
Automatically or
RED buzzer beeps.
UPS switched off
UPS will not
switch to battery
mode.
1. Overload connected at
UPS’s outlet
2. Short circuit on Inverter
3. Battery Low
1. Mains failure, battery
discharged, battery
depleted.
Wait, until mains returns.
Allow the UPS to recharge the battery
for at least 6 hours
REV. 05-02-08
Trouble
Shooting
(10)
Sine Wave LI UPS