EN/
/0915/WLA Compact
/53
Check the presence of leaks:
it is mandatory to check the presence of refrigerant leaks according to European
Standard 842/2006 (F-gas). Qualified companies and personnel (according to Reg. 303/2008) provide regular seal
checks (according to Reg. 1516/2007 and Reg. 1497/2007) and store registration of the maintenance activities in a
specific register containing the various checks performed.
High pressure safety pressure switch:
the pressure switch is a safety device; therefore, check its operation
regularly. Simulate an increase in pressure to perform this verification. If the pressure switch is triggered at a pressure
higher than 40.5 bar, it must be replaced immediately with a new one with the same intervention point.