ULTRASONIC
61
Copyright STULZ GmbH 02/1997
INSTALLATION EXAMPLES FOR ENS HUMIDIFIERS
Install the humidifiers at the suction side.
Use an air rectifier in the airflow in front of the humidifier; heat exchangers
also fulfil the rectification function.
During heating process, the air temperature at the humidifier casing must
not exceed 40°C.
The distance to the next object behind the humidifier in airflow direction
should be larger than the humidifier path.
Provide a stainless steel pan corresponding to the lengthof the humidifier
path. The pan must be fitted with a drain, connected to a syphon. The height
of the syphon is dependent on the differential pressure (environment/
suction side in the unit).
To ensure that a sufficient carrier airflow is available for the aerosols that
are getting out the humidifier, a distance of > 10 cm to the pan has to be
provided for the lowest humidifier. The same is applicable on top of the
humidifier and at the sides.
1.
2.
3.
4.
5.
6.