ULTRASONIC
46
Copyright STULZ GmbH 02/1997
ASSEMBLY ENS SERIES
Installation into a Duct
Legend
1.
Duct piece of stainless steel
2.
Water drain (provide syphon)
3.
In case of non-laminar flow, install a perforated plate in direction of
airflow in front of the humidifier
Requirement: open cross section 60%.
4.
Direct connection of safety overflow
To obtain shortest possible humidifier paths it is very important to
distribute the mist as evenly as possible across the total duct or unit cross
section and to keep air speed within the range of 1.5 to 3 m/sec. In the
following, some installations are shown, which are possible by means of
buffle plates or perforated plates.