SI V3.0 E 

 5 

Adjustments 

 (Not automatic with Twinpower version) 

Standby Level (1) 

The activation of the inverter, when working in 
automatic mode, is dictated by the detection of a 
load. With this function, it is possible to adjust 
the minimum load detected between 0,3 and 20 
Watts. This level is factory adjusted to 2 
watts and so no further adjustment will 
probably be needed. 

Adjustment procedure 

Make sure that no device is connected. 
 
Check for the presence of hidden users such as 
television, fax, video, … which often have a 
standby mode and remain working even after 
being turned off ! 
 
Put the switch in “ Autom. ” position. 
 
Introduce a screw driver N°1 delicately in the 
hole (1) provided and turn gently until you feel 
the screw driver insert in the groove of the 
screw. 

Turn clockwise 

 until tight without pressing 

(do not force!). 
 
Wait until the green LED blinks. 
 
Activate the minimum charge you wish to detect. 

Turn the screw slowly anti-clockwise 

 

without pressing until the inverter activates. 
(green LED illuminated). 
 
Check that the inverter goes back to standby 
mode a couple of seconds after deactivation of 
all charges. 
 
 Warning : In maximum anti-clockwise position 
the inverter continues to work even if there is no 
load

Control 

The tension of the batteries is submitted to 
control. During their use, the tension must be 
between the following ranges : 
 
11.4 V and 16 V in the 12 Volt models, 
22.8 V and 32 V in the 24 Volt models, 
45.6 V and 61 V in the 48 Volt models.  
 
Outside these ranges the inverter is 
automatically disconnected. 

 
These values correspond to a no load situation 
and they are automatically adjusted according to 
the current of the battery. 
 
The internal temperature and the maximum 
power are also submitted to control. 
 
In the case of prolonged overload or deficient 
ventilation it is not possible to restart the inverter 
until it has cooled down. 

Indicators 

Green Run - LED (3) 

Illuminated: the inverter is connected. A 230 V 
tension is present in the outlet. 
Blinking : (only SI version) The inverter is in 
“ Autom. ” mode and no voltage is detected by 
the standby system. 
 

 A 230 V tension is intermittently present! 

Red Fault - LED (2) 

The inverter is stopped : 
The tension of the battery is not correct 
After an overload, overheating or short circuit 
To restart the inverter after a failure, put the 
switch (4) in “ OFF ” position for 10 seconds, 
then connect again

Safety 

The inverter is internally protected against 
overloads and short circuits. Should this 
protection fail, the inverter is equipped with a 
fuse (fire protection). If the fuse is broken, 
qualified technicians should control the 
installation and change the fuse. 

Internal fuse 

 
Fuse 

Inverter SI (mod.) 

40A 648 
50A 

624 - 1248 

60A 

824 – 1448 

80A 

612 – 2348 - 2360 

100A 

812 – 1224 – 3548 - 3060 

2*100A 

1212 – 1624 – 2324  

2*125A 3324 

 

The use of higher fuse value will not improve the 
performance of the inverter and will degrade 
safety protection ! 

Summary of Contents for SI 1212

Page 1: ...User manual SI V3 0 E Sinewave inverter SI SERIES User s and Installer s Handbook STUDER INNOTEC Rue des Casernes 57 CH 1950 Sion Tel 41 0 27 205 60 80 Fax 41 0 27 205 60 88 info studer innotec com www studer innotec com ...

Page 2: ...ment procedure 5 CONTROL 5 INDICATORS 5 Green Run LED 3 5 Red Fault LED 2 5 SAFETY 5 INTERNAL FUSE 5 OPTIONS 6 ALARM CONTACT 6 SOLAR CHARGE CONTROLLER 6 LED Charging 11 6 LED Bat 100 10 6 MAINTENANCE 6 LEGISLATION 6 LIMITATION OF LIABILITY 6 CE DECLARATION OF CONFORMITY 6 DESCRIPTION AND WIRING DIAGRAM 7 WIRING DIAGRAM FOR SI 600 800 S SOLAR CHARGE REGULATOR 8 SI PERFORMANCE ERREUR SIGNET NON DEFI...

Page 3: ...rranty No current or tension generating devices public network generator may be connected to the output of the inverter because this could result in its destruction As for the usage of batteries follow the manufacturer s instructions Important After disconnecting the battery the output tension 230V may still remain for 30 seconds The ventilation of the device should never be obstructed Should the ...

Page 4: ...ing the polarity in order not to damage the device Check that the connections are fixed correctly Use After connecting the inverter make sure the user devices are correctly plugged in and that there is no possible contact between the Line OUT 6 and a person The working device generates high tensions which could be fatal The inverter can be activated by moving the switch to the Auto position The on...

Page 5: ...n the following ranges 11 4 V and 16 V in the 12 Volt models 22 8 V and 32 V in the 24 Volt models 45 6 V and 61 V in the 48 Volt models Outside these ranges the inverter is automatically disconnected These values correspond to a no load situation and they are automatically adjusted according to the current of the battery The internal temperature and the maximum power are also submitted to control...

Page 6: ...on for control Legislation In all cases the assembly and installation must be done by qualified technicians observing the national requirements and rules stipulated You will find complete information about this in the relevant institutions Limitation of liability STUDER INNOTEC cannot control the installation use and maintenance of the inverter Thus we are not responsible for damages costs or loss...

Page 7: ...STUDER INNOTEC SI User manual SI V3 0 E 7 Description and wiring diagram ...

Page 8: ...STUDER INNOTEC SI User manual SI V3 0 E Wiring diagram for SI 600 800 S Solar charge regulator ...

Page 9: ...d together in order to obtain a 3 400V 3 phased grid Connecting 1 Check that the inverters are in OFF position 2 First link together the neutral of all 3 devices by taking care that this connecting point be not further than 1 m from each inverter 3 Link together the battery cables take care to not reverse the polarity The 3 inverters have to be connected together to only one battery bank Commissio...

Page 10: ...imum power 15 min 1 3 1 6 x Pnom 25 C Maximum power 3 min 1 6 2 x Pnom 25 C Peak power 5s 3 5 x Pnom Asymmetric load Up to 2 x Pnom Cos ϕ 0 1 1 Protections Overload Overheat Short circuit Reverse polarity by internal fuse IP protection index IP 20 complies with DIN 40050 IP 23 with top cover Forced ventilation From 45 C 3 C Overheating protection 75 C 3 C Required battery capacity 5x Pnom Unom rec...

Reviews: