- 13 -
Pipe
Size
Minimum pipe length required to install the
upstream line-in kit (mm) (A)
22 mm
480 mm
28 mm
580 mm
35 mm
630 mm
40 mm
735 mm
54 mm
820 mm
Note:
Do not
forget if a water softener is to be installed this has to
be included in this pipe run, and additional space must be allocated
for this.
Do not
fit smaller pipework than the upstream line-in kit accepts as
this will impair performance.
Step 2b:
Upstream line-in kit (35mm, 42mm, 54mm)
The upstream line-in kit includes:
1 - inline strainer
2 - pressure gauge (upstream)
3 - double check valve
4 - pressure reducing valve
5 - pressure gauge (fitted to pressure reducing valve)
6 - Mainsboost vessel connector (see step 1)
7 - Isolation valve (see Step 1)
The above components must be installed in the correct order to ensure safe and
satisfactory system operation.
Fig. 10b
5
4
3
2 (T-piece not supplied)
1
Inlet
Outlet
A