SPECIFICATIONS
MODEL
SXU 40
SXU 50
SXU 80
SXU 120
ELECTRICAL
240V
240V
240V
240V
50hz
50hz
50hz
50hz
AMPS
1.8
2.3
2.5
3.0
REFRIGERANT
R134a
R404a
R404a
R404a
CHARGE
260g
280g
300g
300g
WATER
All models
Minimum:
200kpa
PRESSURE
Maximum:
350kpa
OPERATING
All models
Minimum:
10
o
C
TEMPERATURES
Maximum:
43
o
C
WATER
CONNECTION
All models
3/4”
BSP male stop cock
REQUIREMENTS
DRAINAGE
All models
Floor waste or tundish
below drain outlet on machine
It is recommended that during the 15 minute cleaning cycle you should re-
move any existing ice from the storage bin and pour in at least 1
-
2 litres of
warm water to flush out any dust from the bin and drain hose.
In some areas where there is a high calcium content in the water supply it may
also be necessary to clean the water spray nozzles.
This will usually be evidenced by irregular ice cubes. (some not fully formed)
1.
Remove water curtain assembly
2.
Remove the wire ice slide
3.
Unscrew the plastic spray nozzle retaining nut and remove from the
spray bar
4.
Clean the nozzles and nuts. A dilute solution of white vinegar and water
will help break down the calcium in extreme cases.
5.
Wipe out the bottom of the water trough with a clean cloth
6.
When completed reverse the above process to re
-
assemble
Water curtain assem-
Wire ice slide
Spray bar