Table 2
pre adjustment settings gas valves
(G27 for Poland)
boiler
type
number of turns open (counter clockwise)
nat. gas G20 / G25 / G27
propane G31
butane G30 (B/P)
S-CB
+
60
1
0,5
0,25
S-CB
+
80
1,5
0,75
0,5
S-CB
+
100
3,5
1,5
1,25
S-CB
+
120
2,25 *
1 *
0,75 *
S-CB
+
150
2,25 *
1 *
0,75 *
S-CB
+
180
4,25 *
2,25 *
2 *
* Both gas valves must be opened this number of turns.
Table 3
Gas valve settings for Ls gas G2.350
(for Poland)
boiler type
number of turns open (counter clockwise)
natural gas Ls G2.350
gas valve class
gas valve part n
o
:
S-CB
+
60
1,25
A + C
No replacement
S-CB
+
80
1,75
B + J
S04.000.393
S-CB
+
100
4
B + J
S04.000.393
S-CB
+
120
*2,5
A + C
No replacement
S-CB
+
150
*2,5
B + J
S04.000.393
S-CB
+
180
*4,5
B + J
S04.000.393
* Both gas valves must be opened this number of turns.
Table 4
Contact you boiler supplier for the right settings when converting to a not mentioned type of gas
Pressure adjustment settings LEFT valve
boiler
type
"
p-out
"
pressure at gas valve
nat. gas G20 / G25
propane G31
butane G30 (B/P)
S-CB
+
120
-2 to 0 Pa
-4 to -2 Pa
-5 to -3 Pa
S-CB
+
150
-2 to 0 Pa
-7 to -5 Pa
-8 to -6 Pa
S-CB
+
180
-2 to 0 Pa
-7 to -5 Pa
-8 to -6 Pa
Maximum fan speed has to be reduced to convert the boiler into a propane or B/P appliance.
Setting of parameter P4BD.
A sticker has to be pasted after converting the boiler into a propane or B/P appliance.
Mark the used gas and the parameter setting on this sticker.
PROPANE
PROPAN
PROPANO
PROPAAN
BUTANE/PROPANE
BUTAN/PROPAN
BUTANO/PROPANO
BUTAAN/PROPAAN
P4BD = 1
P4BD = 2
G31 P
G30/G31 B/P