14
LPG CONVERSION
The boilers are supplied as standard to be run on natural gas. Should it be necessary to convert the boiler to
LPG the following operations must be carried out :
1. Remove jacket front panel.
2. Switch off electrical supply.
3. Turn off main gas cock.
4. Substitute the injectors on the main burner.
5. Nova Sit 822 gas valve : Remove the burner-pressure regulator cover and screw the governor spring fully
in, replace the cover with blank supplied.
Elektrogas VM-l gas valve : Replace the governor spring with the one supplied.
6. Test for soundness.
7. Re-commission boiler as described in section 11. Using LPG burner pressure as stated in Table 1.
NOTE
: The gas supply pressure to the boiler should not exceed the pressure as stated in Table 1.