Selecting a UPS Unit for ftServer Systems
Electrical Power Planning
2-9
Table 2-9. APC Symmetra Models for PDUs or for Multiple Systems
Locale
APC Symmetra Model
UPS
Input
UPS Output
North America
SYH2K6RMT, SYH4K6RMT, SYH6K6RMT
Requires AAP87600 PDU with B50171F power
cord
208V
208V
(L6-20R)
SYH2K6RMT-P1, SYH4K6RMT-P1,
SYH6K6RMT-P1
208V
120/208V
(L6-20R,
5-15R)
SYA8K16RMP, SYA12P16RMP, SYA14K16RMP
Requires APC SYPD7 and AAP87600 PDU
208V
120/208V
(L6-20R,
L6-30R)
Japan
SYH2K6RMJ, SYH4K6RMJ, SYH6K6RMJ
Requires AAP87600 PDU with B50175F power
cord
200V
200V
(L6-20R)
SYH2K6RMJ-P1, SYH4K6RMJ-P1,
SYH6K6RMJ-P1
200V
100/200V
(L6-20R,
5-15R)
SYA8K16RMJ, SYA2K16RMJ, SYA16K16RMJ
Requires APC SYPD7and AAP87600 PDU
200V
100/200V
(L6-20R,
L6-30R)
Rest of the world
SYH2K6RMI, SYH4K6RMI, SYH6K6RMI
Requires AAP87600 PDU with B52700F power
cord
230V
230V
(C20, C19)
SYA8K16RMP, SYA12P16RMP, SYA14K16RMP
Requires AAP87600 PDU with B52700F power
cord
230V
230V
(C20, C19)
Table 2-10. APC UPS Models for a Single Rack-Mountable System
Locale
Smart-UPS
UPS Input
AC Power Output
North America
Model SUA1500RM2U
120V
120V (5-15R)
Japan
Model SUA1500RMJ2UB
100V
100V (5-15R)
Rest of the world
Model SUA1500RMI2U
230V
230V
(C14, C13)
Summary of Contents for ftServer 2600
Page 1: ...Stratus Technologies R638 02 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide...
Page 8: ...Tables viii Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 48: ...Planning for Cables 3 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 70: ...Monitor Requirements 6 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Page 98: ...Index Index 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...