Rack Configuration Planning
6-1
Chapter 6
Rack Configuration Planning
6-
For information about planning a rack configuration and the PDU requirements for the
configuration, see:
“Determining PDU Requirements” on page 6-2
“Sample PDU Usage Calculation” on page 6-4
Using PDUs
ftServer systems have two power receptacles. Correspondingly, two PDUs provide
power to the receptacles.
Use of PDUs is optional unless you have a support agreement with Stratus. If you do
have a support agreement with Stratus, use pairs of PDUs to provide AC power to
systems and components in a cabinet
if six or more power cords would otherwise
exit from the cabinet
.
The A-side (top) PDU provides power to:
The A-side of each system
A rack-mounted LCD monitor unit
An ftScalable Storage system
Any rack-mounted tape-drive enclosures
The B-side (bottom) PDU provides power to the other side of each system and to the
second side of a storage enclosure.
Because the A-side PDU always uses at least as many power cords and consumes at
least as much power as the B-side PDU, plan the cabinet configuration so that the
A-side PDU can support the configuration.
Summary of Contents for ftServer 2500
Page 1: ...Stratus Technologies R609 04A Stratus ftServer 2500 4400 and 6200 Systems Site Planning Guide ...
Page 5: ...Contents Contents v Index Index 1 ...
Page 12: ...Preface xii Stratus ftServer 2500 4400 and 6200 Systems Site Planning Guide R609 ...
Page 29: ...Safety Notices Site Planning for ftServer 2500 4400 and 6200 Systems 1 17 W A R N I N G ...
Page 30: ...Safety Notices 1 18 Stratus ftServer 2500 4400 and 6200 Systems Site Planning Guide R609 ...
Page 56: ...Planning for Cables 4 4 Stratus ftServer 2500 4400 and 6200 Systems Site Planning Guide R609 ...
Page 106: ...Index Index 4 Stratus ftServer 2500 4400 and 6200 Systems Site Planning Guide R609 ...