AirSense Technology Ltd. 2005
Page 13
Stratos-Micra 100
• INSTALLER’S HANDBOOK • Iss. 3
3.30
Aspirator speed –
Flow monitoring
tab
This function has no current use on the Stratos-Micra 100 but is reserved for future expan-
sion purposes.
3.31
Access code –
Miscellaneous
tab
This is the access code required to amend programmable parameters. The default code
is 0102. Once the appropriate code is entered it may be changed here to any four digit
number to limit unauthorised access.
3.32
Chart recording rate –
Miscellaneous
tab
This function controls how frequently the detector and alarm level or flow rates are
stored in the Stratos-Micra 100’s internal chart recorder log.
(See section 4.3, ‘Chart
recording’).
setting
type
storage interval
time per division
on chart log
0
Detector output
1 second
10 seconds
1
Detector output
5 seconds
50 seconds
2
Detector output
12 seconds
2 minutes
3
Detector output
30 seconds
5 minutes
4
Detector output
1 minute
10 minutes
5
Detector output
2 minutes
20 minutes
6
Detector output
5 minutes
50 minutes
7
Detector output
10 minutes
100 minutes
8
Detector output
20 minutes
200 minutes
9
Detector output
50 minutes
500 minutes
10
flow recording
1 second
10 seconds
11
flow recording
5 seconds
50 seconds
12
flow recording
12 seconds
2 minutes
13
flow recording
30 seconds
5 minutes
14
flow recording
1 minute
10 minutes
15
flow recording
2 minutes
20 minutes
16
flow recording
5 minutes
50 minutes
17
flow recording
10 minutes
100 minutes
18
flow recording
20 minutes
200 minutes
19
flow recording
50 minutes
500 minutes
The chart log recording rates are as follows.
In the above table the grayed section indicates flow rate recording while the white sec-
tion indicates detector and alarm level recording.
At the slowest recording rate, one month of data can be recorded. The factory default
setting is 8.