AirSense Technology Ltd. 2005
Page 11
Stratos-Micra 100
• INSTALLER’S HANDBOOK • Iss. 3
3.14
Programmed Isolate –
Alarm actions
tab
When this function is ticked the controller will not generate alarms and will not indi-
cate a fault condition on any fire panel which is connected, e.g. for use during detec-
tor maintenance. The “Fault” light will be illuminated on the detector front panel. The
isolated condition will be disabled automatically after 7 days if not manually disabled.
This function is disabled by default.
3.15
Latching alarms –
Alarm actions
tab
When this function box is ticked it requires a reset from the controlling computer to
clear an alarm condition.
If unticked, the alarm signal is extinguished as soon as the alarm condition ends. This
is the factory default setting.
3.16
Latching faults –
Alarm actions
tab
When this function box is ticked it requires a reset from the controlling computer to
clear a fault condition.
If unticked, the fault signal is extinguished as soon as the fault condition ends. This is
the factory default setting.
3.17
Cascading alarms –
Alarm actions
tab
Ticking this function box means that only when the detector’s controller has gone into
Pre-Alarm does the controller start counting down the main Fire delay i.e. the time
delays on Pre-Alarm and Fire 1 are cumulative. The Aux alarm is not included in the
cumulative delay since it may be set to a higher level than either the Pre-Alarm or Fire
1 levels. This function is enabled by default.
3.18
Device type –
Device information
tab
This function is for display purposes only. It shows any special designation for the unit,
which will normally be
Stratos-Micra 100.
3.19
Firmware version –
Device information
tab
This function is for display purposes only. It shows the version number of the fitted
firmware chip.
3.20
Run-time hours –
Device information
tab
This function is for display purposes only. It shows the cumulative total number of hours
that the device has run (
NB
: this is not the time that has elapsed since last power-up, but
the sum total of run time since the detector memory was last reset).