Status messages
Message
Cause
Error elimination
ON/OFF
Standby modus, no regulation
Switch on by key or switching input
Temperature
indication flashes
Refrigerating chamber temperature
beyond alarm limits (parameter A1, A2)
E0
flashes
Refrigerating chamber sensor F1 error,
break or short-circuit
Control sensor. Controller operates
according to with parameter c3.
E1
flashes
Sensor F2 error,
break or short-circuit
Control sensor.
At setting [c3=1] the controller
operates in timed defrosting modus
(defrosting time as set in d3).
At setting [c3=2] see parameter Y6.
"rC", flashing
Data loss real time clock
Adjustment of the clock
"rF", flashing
Error real time clock
If error cannot be eliminated by
switching on/off, the controller must
be repaired.
EP
Data loss at parameter memory (basic
contact 1 and 2 are dead)
If error cannot be eliminated by
switching on/off, the controller must
be repaired.
Error message E0, E1, EP and rC change in the display with the actual value of sensor F1, unless
the latter is defective. This happens independently from the selected indication mode. After the
error is eliminated and confirmed with the DOWN key, the previously set indication mode becomes
active again.
If there is a connection to the buzzer with parameters U1... U4, the buzzer can be switched off with
the DOWN key.