11 | Appendix
05/2019 | ID 442793.01
89
11.1.2
FMC 1,5 -ST-3,5
Feature
Line type
Value
Contact spacing
—
3.5 mm
Nominal current at ϑ
amb
= 40 °C
—
CE/UL/CSA: 8 A
Max. conductor cross-section
Flexible without end sleeve
1.5 mm²
Flexible with end sleeve without plastic collar
1.5 mm²
Flexible with end sleeve with plastic collar
0.75 mm²
2 conductors, flexible, with double end sleeve with
plastic collar
—
AWG according to UL/CSA
16
Min. conductor cross-section
Flexible without end sleeve
0.2 mm²
Flexible with end sleeve without plastic collar
0.25 mm²
Flexible with end sleeve with plastic collar
0.25 mm²
2 conductors, flexible, with double end sleeve with
plastic collar
—
AWG according to UL/CSA
24
Insulation stripping length
—
10 mm
Tightening torque
—
—
Tab. 100: FMC 1,5 -ST-3,5 specification
11.1.3
BCF 3,81 180 SN
Feature
Line type
Value
Contact spacing
—
3.81 mm
Nominal current at ϑ
amb
= 40 °C
—
CE/UL/CSA:
16 A/10 A/11 A
Max. conductor cross-section
Flexible without end sleeve
1.5 mm²
Flexible with end sleeve without plastic collar
1.0 mm²
Flexible with end sleeve with plastic collar
1.0 mm²
2 conductors, flexible, with double end sleeve with
plastic collar
—
AWG according to UL/CSA
16
Min. conductor cross-section
Flexible without end sleeve
0.14 mm²
Flexible with end sleeve without plastic collar
0.25 mm²
Flexible with end sleeve with plastic collar
0.25 mm²
2 conductors, flexible, with double end sleeve with
plastic collar
—
AWG according to UL/CSA
26
Insulation stripping length
—
10 mm
Tightening torque
—
—
Tab. 101: BCF 3,81 180 SN BK specification