Monitoring and diagnosis on the inverter
Operation manual
ID 441896.05
WE KEEP THINGS MOVING
57
10
Data type:
U32
Value:
–
Index:
2103
hex
Subindex:
2
hex
A260 EtherCAT Synchronization mode
This parameter activates EtherCAT synchronization monitoring mode on the
inverter. The inverter offers the option of monitoring the synchronization between
master and inverter via Distributed Clock. A check is made to determine whether
the time difference between the arrival of the EtherCAT Frame at the inverter and
the point in time of the SYNC0 signal on the inverter is within a tolerable time
range.
When monitoring is activated, Sync errors are counted with an error counter and
indicated in parameter
A261.2
.
Synchronization mode is deactivated and activated by entering the following
values:
0: Synchronization deactivated
1: Synchronization active
Other values are not defined and are therefore not permitted.
Information
When the PLC cycle time is not the SYNC0 cycle time, all synchronization errors
can no longer be detected.
Information
Activation of synchronization mode requires different amounts of run time
depending on the cycle time of the PLC and the inverter. With high-performance
applications are being run on the inverter, activation of synchronization mode
may cause the error "runtime load.
Axis:
Global
Data type:
U16
Value:
0 ... 0 ... 65535
Index:
2104
hex
Subindex:
0
hex