background image

14

 | WPF  M 

WWW.STIEBEL-ELTRON.COM

INSTALLATION  

 

ShuTTING DOWN

11.1  Checks prior to commissioning the heat pump 

manager

!

 

Damage to the appliance and environment

Observe the maximum system temperature in underfloor 

heating systems.

!

 

Damage to the appliance and environment

With an underfloor heating system, never use the heat 

pump to dry the screed as this places such a high demand 

on the heat source that the frost protection function may 

respond.

f

f

Check whether the heating system is charged to the correct 

pressure and the quick-action air vent valve is open.

f

f

Check whether the outside temperature sensor is correctly 

placed and connected.

f

f

Check whether the power supply is connected correctly.

f

f

Check whether the connecting cable to the heat pump (BUS 

cable) is connected correctly.

11.2  Commissioning the heat pump manager

Commission the heat pump manager and make all settings in ac-

cordance with the operating and installation instructions for the 

heat pump manager.

11.3  Heating curve adjustment

The efficiency of a heat pump decreases as the flow temperature 

rises. The heating curve should therefore be adjusted with care. 

Heating curves that are set too high cause the zone valves and 

thermostatic valves to close, which may lead to the minimum flow 

rate required for the heating circuit not being achieved.

f

f

Observe the WPM operating and installation instructions.

The following steps will help you to adjust the heating curve cor-

rectly:

 

- Fully open thermostatic or zone valves in a lead room (e.g. 

living room and bathroom). 

We do not recommend installing thermostatic or zone valves 

in the lead room. Control the temperature for these rooms 

via remote control.

 

- At different outside temperatures (e.g. –10 °C and +10 °C), 

adjust the heating curve so the required temperature is set in 

the lead room.

Standard values to begin with:

Parameter

Underfloor heating system Radiator heating system

Heating curve

0.4

0.8

Control response time 5

15

Comfort temperature 20 °C

20 °C

If the room temperature in spring and autumn is too low (approx. 

10 °C outside temperature), the value of parameter COMFORT TEM-

PERATURE must be raised in the heat pump manager menu under 

SETTINGS / HEATING / HEATING CIRCUIT.

 

Note

If no remote control is installed, raising the parameter 

“COMFORT TEMPERATURE” leads to a parallel offset of 

the heating curve.

Increase the parameter “heating curve” if the room temperature 

is not high enough when outside temperatures are low.
If the parameter “heating curve” has been raised, adjust the zone 

valve or thermostatic valve in the lead room to the required tem-

perature at high outside temperatures.

!

 

Material losses

Never reduce the temperature in the entire building by 

closing all zone or thermostatic valves, instead use the 

setback programs.

When everything has been implemented correctly, the system 

can be heated to its maximum operating temperature and vented 

once again.

!

 

Material losses

With underfloor heating systems, observe the maximum 

permissible temperature for the system.

11.4  Appliance handover

Explain the appliance function to users and familiarise them with 

its operation.

 

Note

Hand over these operating and installation instructions 

to the user for safe-keeping. Carefully observe all infor-

mation in these instructions. They provide information 

on safety, operation, installation and maintenance of the 

appliance.

11.5  Operation and control

!

 

Appliance and system damage

Never interrupt the power supply, not even outside the 

heating season. The system’s active frost protection is not 

guaranteed if the power supply is interrupted. 

The system should not be switched off in summer. The heat pump 

manager has an automatic summer / winter changeover.

12.  Shutting down

If the system is taken out of use, set the heat pump manager to 

standby. This way the safety functions that protect the system 

remain enabled, e.g. frost protection.

!

 

Appliance and system damage

If the heat pump and frost protection are completely 

switched off, drain the system on the water side. 

Summary of Contents for WPF 10 M

Page 1: ...OPERATION AND INSTALLATION BRINE WATER HEAT PUMP WPF 10 M WPF 13 M WPF 16 M WPF 7 MS WPF 10 MS ...

Page 2: ...stallation 7 10 1 Transport 7 10 2 Positioning 7 10 3 Removing the casing panels 8 10 4 Installing the heat source system 8 10 5 Heating water connection 9 10 6 Safety temperature controller for underfloor heating system 10 10 7 Power supply 10 10 8 Fitting casing components 13 11 Commissioning 13 11 1 Checks prior to commissioning the heat pump manager 14 11 2 Commissioning the heat pump manager ...

Page 3: ...he power supply by an isolator that disconnects all poles with at least 3 mm contact separation Maintain the minimum clearances to ensure trou ble free operation of the appliance and facilitate maintenance work Maintenance work such as checking the electri cal safety must only be carried out by a qualified contractor We recommend an annual inspection to establish the current condition of the syste...

Page 4: ...zontal lines above and below the text General information is identified by the symbol shown on the left f f Read these texts carefully Symbol Damage to the appliance and environment Appliance disposal f f This symbol indicates that you have to do something The ac tion you need to take is described step by step 1 4 Units of measurement Note All measurements are given in mm unless stated oth erwise ...

Page 5: ...appliance or perform user maintenance unless they are supervised 2 3 Test symbols See type plate on the appliance 3 Appliance description The WPF M is a heating heat pump designed to operate as a ground source heat pump The heat pump extracts energy from the heat source medium i e brine at a low temperature level This extracted energy is then transferred to the heating water at a higher level enri...

Page 6: ... supplied with the appliance 9 Preparations 9 1 General information Note The heat pump is designed for installation in interiors except in wet areas Never install the heat pump immediately below or adjacent to bed rooms Insulate pipes through walls and ceilings against structure borne noise transmission The room in which the appliance is to be installed must meet the following conditions No risk f...

Page 7: ...le for the BUS Note Provide separate fuses for the two power circuits of the appliance and the control unit 9 3 Buffer cylinder A buffer cylinder is recommended to ensure a trouble free ap pliance operation The buffer cylinder not only provides hydraulic separation of the flow in the heat pump and heating circuit 10 Preparing for installation 10 1 Transport f f Transport the appliance in its packa...

Page 8: ...must be taken into consideration see Specification An adequate flow rate must be safeguarded at every possible brine temperature i e Nominal flow rate at a brine temperature of 0 C with a tolerance of 10 10 4 2 Connection and filling with brine Prior to connecting the heat pump check the heat source circuit for possible leaks and flush thoroughly Calculate the volume of the heat source circuit You...

Page 9: ... source parameter in the commissioning report must be set to ethylene glycol otherwise the frost stat will stop the heat pump at temperatures below 7 C Note You can check the source outlet temperature on the heat pump manager display under system menu item TEM PERATURES 10 5 Heating water connection The heat pump heating system must be installed by a qualified contractor in accordance with the wat...

Page 10: ...and flushing heating systems can be obtained via trade suppliers Note If you treat the fill water with inhibitors or additives the same limits as for desalination apply 10 5 4 Venting the heating system f f Vent the pipework thoroughly 10 6 Safety temperature controller for underfloor heating system Material losses In case of failure in order to prevent an excessively high flow temperature in the ...

Page 11: ...he compressor starts Brine pump power supply L1 L2 L3 N PE 3 N PE 400 V 50 Hz After connecting all electrical cables refit and seal the cover over the mains terminal strip Terminals X4 Control 26_03_01_1596 Mains supply L N PE 1 N PE 230 V 50 Hz Terminals X2 Low voltage 26_03_01_1597 H BUS high L BUS Low BUS ground BUS Sensor No function Circulation pumps Connect the circulation pumps in accordanc...

Page 12: ...upply compressor L N PE Power supply heat pump with WPAB R RC N PE After connecting all electrical cables refit and seal the cover over the mains terminal strip Terminals X4 Control D0000040630 Mains supply L N PE Outputs S Control output for the WPAB ON Compressor signal Terminals X2 Low voltage D0000040631 1 BUS High H 2 BUS Low L 3 BUS ground 4 and 5 Temperature sensors ...

Page 13: ...of the control panel f f Secure the cover by firmly tightening the fixing screws with serrated washers f f Fit the cover to the appliance f f After attaching the front cover fix it to the side panels with screws as shown in the diagram When attaching the front cover fit the tab with its screws and serrated washers The tab screws and serrated washers can be found in the pack f f When attaching the ...

Page 14: ...ating system Heating curve 0 4 0 8 Control response time 5 15 Comfort temperature 20 C 20 C If the room temperature in spring and autumn is too low approx 10 C outside temperature the value of parameter COMFORT TEM PERATURE must be raised in the heat pump manager menu under SETTINGS HEATING HEATING CIRCUIT Note If no remote control is installed raising the parameter COMFORT TEMPERATURE leads to a ...

Page 15: ...BA 14 1 1 Checking the HP type DIP switch on the IWS f f Check whether the HP type DIP switch 3 marked WP Typ is set as follows WP Typ ON 1 2 3 4 D0000057058 If the appliance is to be used as a module together with a further WPF M the DIP switch must remain in the same position 14 1 2 DIP switch BA These DIP switches have no function 14 1 3 LEDs Red LED Fault Cause Remedy Appliance stops and resta...

Page 16: ...F 13 M WPF 16 M WPF 7 MS WPF 10 MS b02 Entry electrical cables I b03 Entry electrical cables II c11 Safety assembly e01 Heating flow Male thread G 1 1 4 G 1 1 4 G 1 1 4 G 1 1 4 G 1 1 4 e02 Heating return Male thread G 1 1 4 G 1 1 4 G 1 1 4 G 1 1 4 G 1 1 4 f01 Heat source flow Male thread G 1 1 4 G 1 1 4 G 1 1 4 G 1 1 4 G 1 1 4 f02 Heat source return Male thread G 1 1 4 G 1 1 4 G 1 1 4 G 1 1 4 G 1 ...

Page 17: ...ENGLISH WWW STIEBEL ELTRON COM WPF M 17 INSTALLATION Specification ...

Page 18: ...2 13 K2 14 14 K1 13 X1 1 2 X4 F2 p 2 3 2 1 4 5 X23 X29 X35 X30 1 2 i p P1 P3 i p B5 T 12 18 V 1 2 1 A2 A1 K4 1 2 4 6 M1 M 3 K2 5 3 1 X3 K1 6 4 2 1 3 5 L1 L2 L3 X23 C T1 S T2 R T3 N R2 R3 R1 K4 6 4 2 1 3 5 X23 Z3 br sw ws br sw ws L1 L2 L3 N 3 N PE AC 50Hz 400V WP Netz 3 N PE AC 50Hz 400V Anschluss Solepumpe 1 2 3 5 4 6 7 8 3 2 1 Ext Steuer 4 5 6 Störung L N PE 1 2 3 7 4 ON 1 N PE AC 50Hz 230V K4 L...

Page 19: ...tactor compressor start K4 Contactor brine pump M1 Compressor motor P1 High pressure sensor P3 Low pressure sensor R1 Start up resistance R2 Start up resistance R3 Start up resistance X1 Terminals X2 LV terminals X3 Power terminals X4 Control terminals X23 Power supply earth block X29 Plug in connector IWS 12 PIN X30 Plug in connector IWS 3 PIN X35 Plug in connector IWS 6 PIN Z3 EMI capacitors ...

Page 20: ...20 WPF M WWW STIEBEL ELTRON COM INSTALLATION Specification 15 3 Wiring diagram WPF 7 MS WPF 10 MS 85_03_12_0006 ...

Page 21: ...t gas temperature limiter K2 Contactor compressor start M1 Compressor motor X1 Terminals X2 LV terminals X3 Power terminals X4 Control terminals X23 Power supply earth block X28 Socket terminal strip support point X29 Plug in connector IWS 12 PIN X30 Plug in connector IWS 3 PIN X33 Plug in connector IWS 5 PIN Y1 Diverter valve defrost Z1 Compressor capacitor ...

Page 22: ...ms Y Heating output kW power consumption kW coefficient of performance e X Inlet temperature of the WQA medium C 1 Flow temperature 35 C 2 Flow temperature 50 C 3 Flow temperature 60 C Heating output 12 13 11 7 8 9 10 6 5 0 5 10 15 20 3 2 1 84_03_01_0152 Power consumption 2 1 3 4 5 0 5 10 15 20 3 2 1 84_03_01_0153 ...

Page 23: ...ENGLISH WWW STIEBEL ELTRON COM WPF M 23 INSTALLATION Specification Coefficient of performance COP 0 1 2 3 4 5 6 7 8 5 0 5 10 15 20 3 2 1 84_03_01_0154 ...

Page 24: ...ting output kW power consumption kW coefficient of performance e X Inlet temperature of the WQA medium C 1 Flow temperature 35 C 2 Flow temperature 45 C 3 Flow temperature 55 C 4 Flow temperature 60 C Heating output 5 7 9 11 13 15 17 19 5 0 5 10 15 20 1 2 3 4 D0000033331 Power consumption 2 3 4 5 5 0 5 10 15 20 1 2 3 4 D0000033331 ...

Page 25: ...ENGLISH WWW STIEBEL ELTRON COM WPF M 25 INSTALLATION Specification Coefficient of performance COP 0 1 2 3 4 5 6 7 8 5 0 5 10 15 20 1 2 3 4 D0000033331 ...

Page 26: ...output kW power consumption kW coefficient of performance e X Inlet temperature of the WQA medium C 1 Flow temperature 35 C 2 Flow temperature 45 C 3 Flow temperature 55 C 4 Flow temperature 60 C Heating output 9 11 13 15 17 19 21 5 0 5 10 15 20 1 2 3 4 D0000033331 Power consumption 2 3 4 5 6 5 0 5 10 15 20 1 2 3 4 D0000033331 ...

Page 27: ...ENGLISH WWW STIEBEL ELTRON COM WPF M 27 INSTALLATION Specification Coefficient of performance COP 0 1 2 3 4 5 6 7 8 5 0 5 10 15 20 1 2 3 4 D0000033331 ...

Page 28: ...sumption kW coefficient of performance e X Inlet temperature of the WQA medium C 1 Flow temperature 35 C 2 Flow temperature 45 C 3 Flow temperature 55 C 4 Flow temperature 60 C Heating output 13 15 17 19 21 23 25 27 5 0 5 10 15 20 1 2 3 4 D0000033331 Power consumption 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 7 5 8 0 5 0 5 10 15 20 1 2 3 4 D0000033331 ...

Page 29: ...ENGLISH WWW STIEBEL ELTRON COM WPF M 29 INSTALLATION Specification Coefficient of performance COP 0 1 2 3 4 5 6 7 8 5 0 5 10 15 20 1 2 3 4 D0000033331 ...

Page 30: ... 35 25 35 25 35 Energy data Energy efficiency class average climate W55 W35 A A A A A A A A A A Electrical data Frequency Hz 50 50 50 50 50 MCB fuse protection controller A 1 x B 16 1 x B 16 1 x B 16 1 x B 16 1 x B 16 Compressor fuse MCB A 1 x C 25 1 x C 25 3 x C 16 3 x C 16 3 x C 16 Rated voltage controller V 230 230 230 230 230 Rated voltage compressor V 230 230 400 400 400 Phases controller 1 N...

Page 31: ...ENGLISH WWW STIEBEL ELTRON COM WPF M 31 CONTENTS Specification ...

Page 32: ...32 WPF M WWW STIEBEL ELTRON COM CONTENTS ...

Page 33: ... other guarantee will be granted We shall not provide any guarantee for appliances acquired in countries where we have no subsidiary to sell our products This will not affect warranties issued by any importers Environment and recycling We would ask you to help protect the environment After use dispose of the various materials in accordance with national regulations KYOTO R410A This device is fille...

Page 34: ...cz Finland STIEBEL ELTRON OY Kapinakuja 1 04600 Mäntsälä Tel 020 720 9988 info stiebel eltron fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz Cédex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL ELTRON Kft Gyár u 2 2040 Budaörs Tel 01 250 6055 Fax 01 368 8097 info stiebel eltron hu www stiebel eltron hu ...

Reviews: