iNSTallaTiON
Preparation
w
ww.stiebel-eltron.com
WPE-I H(K)W 230 Premium |
7
7.3 Accessories
- Brine filling unit WPSF
- Water softening fitting HZEA
- Filter assembly 22 mm (FS-WP 22)
- Filter assembly 28 mm (FS-WP 28)
- FET remote control
- DHW circulation pump UPZ
- TAF PT immersion/contact sensor
8. Preparation
8.1 Safety concept
Never cover the appliance
f
Keep the discharge and intake apertures clear.
2
D
00000
99
76
4
1
1 Discharge aperture
2 Intake aperture
A fan is installed in the appliance, which generates a negative
pressure in the device. If the negative pressure can no longer be
built up (damaged sealing tape), the safety pressure cell shuts
down the appliance. A message appears in the heat pump man-
ager.
Unit
Value
Minimum negative pres-
sure
Pa
30
f
Replace the sealing tape if required.
In the event of a leak, the fan mixes the refrigerant gas into the
air in the room sufficiently.
f
Maintain the minimum installation area of the installation
room.
Minimum installation area
[m²]
WPE-I 04 H(K)W Premium
WPE-I 12 H(K)W Premium
WPE-I 06 H(K)W Premium
WPE-I 15 H(K)W Premium
WPE-I 08 H(K)W Premium
6.0
8.0
Increasing the minimum installation area
If the minimum installation area requirement cannot be met in
the installation room, the installation room can be connected to
a neighbouring room via ventilation apertures. The ventilation
apertures must be located near the ceiling and the floor. If the
ceiling is suspended and there is no wall to the next room, the
upper ventilation aperture can be dispensed with.
≥
20
≥
20
100
200
300
≥
1500
50%
Anv
50%
Anv
D
0000
10
17
39
- The ventilation apertures must not be closed.
- The upper edge of the lower ventilation aperture must be no
more than 300 mm above floor level.
- 50 % of the required ventilation aperture area must be less
than 200 mm above floor level.
- The lower edge of the lower ventilation aperture must be no
more than 100 mm above floor level.
- The ventilation aperture between the rooms must be at least
20 mm wide.
- A second ventilation aperture is required. The ventilation ap-
erture must be no less than 50 % of the required ventilation
aperture area. The lower edge of the ventilation aperture
must be at least 1500 mm above floor level.
f
Calculate the area of the ventilation apertures.
Anv =
m
c
- (0,4335 * A)
50,3
D
00000
95
34
7
A
Room area [m²]
Anv Required aperture surface [m²]
m
c
Refrigerant charge [kg]
f
Install ventilation apertures corresponding to the calculated
area.
Summary of Contents for WPE-I 04 HKW 230 Premium
Page 29: ...Installation Specification www stiebel eltron com WPE I H K W 230 Premium 29 ...
Page 45: ...www stiebel eltron com WPE I H K W 230 Premium 45 NOTES ...
Page 46: ...46 WPE I H K W 230 Premium www stiebel eltron com NOTES ...
Page 47: ...www stiebel eltron com WPE I H K W 230 Premium 47 NOTES ...