background image

OPEraTION 

 

Safety

www.stiebel-eltron.com 

WPE-I H(K) 230 Premium | 

5

Depending on the chosen test method and the extent to which 

this method differs from the test conditions defined in the first 

paragraph of this section, any deviations can be considerable.
Additional factors that have an influence on the test values are the 

measuring equipment, the system configuration, the age of the 

system and the flow rates.
Confirmation of the specified output data can only be obtained if 

the test conducted for this purpose is also performed in accord-

ance with the test conditions defined in the first paragraph of this 

section.

2.  Safety

2.1  Intended use

The appliance is designed for:

 

- Heating rooms

 

- Heating of DHW

 

- Cooling rooms (only WPE-I HK 230 Premium)
Observe the operating limits listed in chapter "Specification".
The appliance is intended for domestic use. It can be used safely 

by untrained persons. The appliance can also be used in non-do-

mestic environments, e.g. in small businesses, as long as it is 

used in the same way.
Any other use beyond that described shall be deemed inappropri-

ate. Observation of these instructions and of instructions for any 

accessories used is also part of the correct use of this appliance.

2.2  Safety instructions

 

- Only recognised, qualified contractors may carry out the 

electrical work and installation of the heating circuit.

 

- The qualified contractor is responsible for adherence to all 

applicable regulations during installation and commission-

ing.

 

- The appliance should only be operated once it is fully in-

stalled and all safety equipment has been fitted.

 

- Protect the appliance from dust and dirt during building 

work.

 

- Observe the safety concept for operation of the appliance 

(see chapter "Preparation / Safety concept").

!

 

WARNING Injury

The appliance may be used by children over 8 years of 

age and persons with reduced physical, sensory or men-

tal capabilities or a lack of experience and expertise, 

provided that they are supervised or they have been 

instructed on how to use the appliance safely and have 

understood the potential risks. Children must never play 

with the appliance. Cleaning and user maintenance must 

not be carried out by children without supervision.

!

 

WARNING Injury

f

f

For safety reasons, only operate the appliance with 

the casing closed.

2.3  Test symbols

See type plate on the appliance.

3.  Appliance description

The appliance is a ground source heat pump suitable for operation 

as a heating heat pump.  The heat pump extracts energy from the 

heat source medium at a low temperature level. This extracted 

energy is then transferred to the heating water at a higher level, 

augmented by the electric energy drawn by the compressor. The 

heating water is heated to a flow temperature of up to 75 °C, 

depending on the heat source temperature.
A heating circulation pump, a multifunction assembly (MFG) with 

safety assembly and a 3-way valve are integrated in the appliance 

for switching between the heating circuit and the DHW circuit. To 

heat the DHW, the heating water that has been heated by the heat 

pump is directed through an indirect coil in the DHW cylinder, 

where it transfers its energy to the DHW.
The appliance is equipped with an electric emergency/booster 

heater (NHZ). To safeguard heating operation and the provision 

of high DHW temperatures, the electric emergency/booster heat-

er is activated as an emergency heater if the dual mode point is 

undershot in mono mode operation. If the same thing happens in 

mono energetic operation, the electric emergency/booster heater 

is activated as a booster heater.
The appliance is controlled with an integral, outside tempera-

ture-dependent heating circuit temperature control unit (WPM 

heat pump manager).
The WPM also controls the DHW heating to the required tem-

perature. DHW heating will be completed automatically by an 

integral electric emergency/booster heater, if either the high 

pressure sensor or the hot gas limiter of the heat pump responds 

during DHW heating, subject to the WW LEARNING FUNCTION 

being deactivated. Also subject to the WW LEARNING FUNCTION 

being activated, the DHW heating will terminate and the set DHW 

value will be overwritten with the actual DHW temperature that 

has been achieved.
The WPM also controls the integral electric emergency/booster 

heater. An additional heat generator can also be controlled.

Screed drying

!

 

Material losses

Incorrect settings can cause damage to the heat pump or 

screed. With ground source heat pumps, the heat source 

can also be damaged.

f

f

If you want to use the heat-up program, observe 

the corresponding chapter in the commissioning in-

structions for the WPM heat pump manager.

WPE-I HK 230 Premium

!

 

Material losses

In cooling mode, condensate can form when the dew 

point temperature is undershot.

f

f

Take suitable measures to prevent the formation of 

condensate.

!

 

Material losses

Condensation caused by the temperature falling below 

the dew point can lead to material losses. The appliance 

is therefore approved exclusively for area cooling.

Summary of Contents for WPE-I 04 H 230 Premium

Page 1: ...eat pump WPE I 04 H 230 Premium WPE I 06 H 230 Premium WPE I 08 H 230 Premium WPE I 12 H 230 Premium WPE I 15 H 230 Premium WPE I 04 HK 230 Premium WPE I 06 HK 230 Premium WPE I 08 HK 230 Premium WPE I 12 HK 230 Premium WPE I 15 HK 230 Premium ...

Page 2: ...9 9 3 Removing the casing parts 9 9 4 Installing the heat source system 10 9 5 Heating water connection 11 9 6 Oxygen diffusion 12 9 7 Filling the heating system 12 9 8 Venting the heating system 13 9 9 DHW heating 13 9 10 Operation with buffer cylinder 13 9 11 Fitting the push fit connectors 13 10 Electrical connection 14 10 1 General 14 10 2 Electrical connection 14 10 3 High limit safety cut ou...

Page 3: ...from the second heat generator may flow through the heat pump Please note that the return water temperature may be a maximum of 60 C Maintenance work such as checking the elec trical safety must only be carried out by a qualified contractor We recommend regular inspection to es tablish the current condition of the system and maintenance by a qualified contractor if required to return the system to...

Page 4: ...information may result in non seri ous or minor injury 1 3 Other symbols in this documentation Note General information is identified by the adjacent symbol f f Read these texts carefully Symbol Meaning Material losses appliance damage consequential losses and environmen tal pollution Appliance disposal f f This symbol indicates that you have to do something The ac tion you need to take is describ...

Page 5: ...heat pump suitable for operation as a heating heat pump The heat pump extracts energy from the heat source medium at a low temperature level This extracted energy is then transferred to the heating water at a higher level augmented by the electric energy drawn by the compressor The heating water is heated to a flow temperature of up to 75 C depending on the heat source temperature A heating circul...

Page 6: ... xxxxxxxxxxxxxxxxxx 1 26_03_01_1570 1 Number on the type plate INSTALLATION 6 Safety Only a qualified contractor should carry out installation commis sioning maintenance and repair of the appliance 6 1 General safety instructions We guarantee trouble free function and operational reliability only if original accessories and spare parts intended for the appliance are used 6 2 Instructions standards...

Page 7: ...red aperture surface m mc Refrigerant charge kg f f Install dilution apertures that correspond to the calculated area 8 2 Installation site Material losses f f Install the appliance only in rooms without a con stant ignition source e g open flames a live gas appliance or an electric heater or without open flue boilers Note The appliance is designed for indoor installation except in damp areas f f ...

Page 8: ...wall or in an electrical conduit on a wall B 16 A Electric emergency booster heater BH 2 5 mm 1 5 mm with only two live cores and routing on a wall or in an electrical con duit on a wall B 16 A Control unit 1 5 mm WPE I 12 H K 230 Premium WPE I 15 H K 230 Premium Fuse protec tion Assignment Cable cross section B 25 A Compressor 4 0 mm when routing in a wall 2 5 mm when routing above the surface B ...

Page 9: ...moving the casing parts Note When you open the appliance check the sealing tape The sealing tape is required for generating the necessary negative pressure f f Replace the sealing tape if required 1 2 D0000082700 f f Remove the screws on both sides of the appliance f f Slide the handles on both sides of the appliance along the guide as far as they will go Removing the cover 1 2 D0000082699 f f Pul...

Page 10: ...ust not exceed 300 ppm Mixing ratio The brine concentration varies depending on whether a geother mal collector or a geothermal probe is used as the heat source For the mixing ratio see the table below Ethylene glycol Water Geothermal probe 25 75 Geothermal collector 33 67 Propylene glycol Water Geothermal probe 27 5 72 5 Geothermal collector 36 5 63 5 Charging the brine circuit Note f f Insulate ...

Page 11: ...ance with the water installation diagrams that are part of the technical guides f f Thoroughly flush the pipework before connecting the heat pump Foreign bodies such as rust sand and sealant can impair the operational reliability of the heat pump We rec ommend installing our filter assembly in the heating return see chapter Appliance description Accessories To facilitate easy connection to the hea...

Page 12: ...er with inhibitors or additives the same limits apply as for desalination Filling the heating system Material losses f f Never switch on the power before filling the system Material losses High flow rates or water hammer can damage the ap pliance f f Fill the appliance at a low flow rate In the delivered condition the diverter valve of the MFG is posi tioned at the centre This ensures the heating ...

Page 13: ...ylinder return are to be hydrau lically interconnected 9 10 Operation with buffer cylinder f f Install the supplied TAF PT immersion contact sensor f f Connect the sensor to the heat pump manager f f Set the parameter on the heat pump manager Parameter Setting BUFFER OPERATION SETTINGS HEATING STANDARD SETTINGS ON 9 11 Fitting the push fit connectors Note The plastic push fit connectors are not su...

Page 14: ... WARNING Electrocution f f Before working on the appliance isolate it from the power supply at the control panel Note The leakage current of this appliance can be 3 5 mA Note In conjunction with the WPM heat pump manager use the HSM mixer servomotor Connection work must only be carried out by a qualified contractor and in accordance with these instructions You must have permission to connect the a...

Page 15: ...le control receiver is fitted install a jumper be tween EVU1 and EVU2 10 2 2 Heat pump manager terminal assignment X2 2 X2 3 X2 4 X2 5 X2 6 X2 7 X2 8 X2 9 X2 10 X2 11 X2 12 X2 13 X2 14 X2 15 X1 1 CAN A X1 19 CAN A X1 18 CAN B X1 17 X1 16 X1 15 X1 14 X1 13 X1 12 X1 2 CAN B X1 3 X1 4 X1 5 X1 6 X1 7 X1 8 X1 9 X1 10X1 11 X2 1 D0000071841 Safety extra low voltage X1 1 CAN A L H L H CAN connection for h...

Page 16: ... settings in the commis sioning instructions for the heat pump manager commission the appliance and instruct the operator in its use Carry out commissioning in accordance with these operating and installation instructions and the instructions for the heat pump manager Our customer support can assist with commissioning which is a chargeable service If this appliance is intended for commercial use o...

Page 17: ... system Heating curve 0 4 0 8 Control dynamic 10 10 Comfort temperature 20 C 20 C f f If the room temperature in spring and autumn is too low approx 10 C outside temperature raise the comfort tem perature Parameter COMFORT TEMPERATURE SETTINGS HEATING HEATING CIRCUIT Note If no remote control is installed raising the comfort tem perature leads to a parallel offset of the heating curve f f If the r...

Page 18: ...nergised for 5 minutes until the inverter capacitors have discharged Note f f Please observe the instructions for the heat pump manager Note The following inspection instructions may only be carried out by a qualified contractor Note When you open the appliance check the sealing tape The sealing tape is required for generating the necessary negative pressure f f Replace the sealing tape if require...

Page 19: ...dual mode operation with an ex ternal second heat generator or as a module with a further heat pump set the DIP switch as shown WP Typ ON 1 2 3 4 D0000057055 DIP switch BA f f Check whether the DIP switch BA is set correctly Heating mode BA ON 1 2 3 4 D0000057052 14 4 LEDs IWS BA D0000063997 1 2 1 Reset button 2 LEDs The following table shows the meaning of the LEDs on the IWS LED indicator Meanin...

Page 20: ...nection from the power supply parts of the appliance may remain energised for 5 minutes until the inverter capacitors have discharged Note When you open the appliance check the sealing tape The sealing tape is required for generating the necessary negative pressure f f Replace the sealing tape if required We recommend a regular inspection to establish the current con dition of the system and maint...

Page 21: ...Installation Maintenance www stiebel eltron com WPE I H K 230 Premium 21 ...

Page 22: ...ion Specification 22 WPE I H K 230 Premium www stiebel eltron com 16 Specification 16 1 Dimensions and connections b01 c12 f02 e01 e22 f01 e23 e02 497 598 695 1270 1300 427 357 287 171 101 51 460 450 D0000034468 ...

Page 23: ...der return Diameter mm 28 28 28 28 28 f01 Heat source flow Diameter mm 28 28 28 28 28 f02 Heat source return Diameter mm 28 28 28 28 28 WPE I 04 HK 230 Premium WPE I 06 HK 230 Premium WPE I 08 HK 230 Premium WPE I 12 HK 230 Premium WPE I 15 HK 230 Premium b01 Entry electrical cables c12 Safety valve drain e01 Heating flow Diameter mm 28 28 28 28 28 e02 Heating return Diameter mm 28 28 28 28 28 e22...

Page 24: ... 3 HD L 1 2 3 4 1 2 3 4 1 2 3 4 5 6 7 X12 9 X12 8 1 2 3 4 5 X12 10 X12 11 X11 2 1 2 X11 3 1 2 N Kühlen X11 4 1 2 N Ölsumpfheizung X11 5 1 2 3 X11 6 1 2 3 X11 7 1 2 3 X11 8 1 2 3 X11 9 1 2 3 X11 10 1 2 3 Netzversorgung Inverter 2 1 2 1 2 1 2 1 5 4 3 2 1 5 4 3 2 1 4 3 2 1 4 3 2 1 6 5 4 3 2 1 2 1 3 2 1 3 2 1 4 3 2 1 X72 KF20 KF21 KF22 X71 X70 X69 X68 X67 X66 X65 X64 X63 X62 X61 X60 AA07 MFG L H PWM G...

Page 25: ...4 X2 13 X2 12 X2 11 X2 10 X2 9 X2 8 X2 7 X2 6 X2 5 X2 4 X2 3 X2 2 X2 1 Heizkreispumpe 1 Mischerpumpe 1 Heizkreispumpe 2 Mischer 1 Solarpumpe Störausgang Pufferfühler Heizkreisfühler 1 Warmwasserfühler 2 Wärmeerzeuger Fühler Solarpumpe PWM 2 Wärmeerzeuger PWM Heizkreisfühler 2 VL Kühlen Kollektor WW unten Analogeingang 0 10V Analogeingang 0 10V MA25 M 1 BT07 AA06 AA01 WPM4 H L N L T BT45 T BT25 ws ...

Page 26: ...Heating cooling diverter valve motor MA10 Circulation pump MA12 DHW heating diverter valve motor MA25 Heat source pump motor MA26 Suction fan RF01 Snap on ferrite bead compressor cable RF02 Snap on ferrite bead control voltage RF03 Snap on ferrite bead emergency booster heater cable RF04 Snap on ferrite bead safety cable XD1 Terminal external emergency booster heater HP power supply XD3 External c...

Page 27: ...Installation Specification www stiebel eltron com WPE I H K 230 Premium 27 ...

Page 28: ... 1 2 3 4 5 6 7 X12 9 X12 8 1 2 3 4 5 X12 10 X12 11 X11 2 1 2 X11 3 1 2 N Kühlen X11 4 1 2 N Ölsumpfheizung X11 5 1 2 3 X11 6 1 2 3 X11 7 1 2 3 X11 8 1 2 3 X11 9 1 2 3 X11 10 1 2 3 Netzversorgung Inverter 2 1 2 1 2 1 2 1 5 4 3 2 1 5 4 3 2 1 4 3 2 1 4 3 2 1 6 5 4 3 2 1 2 1 3 2 1 3 2 1 4 3 2 1 X72 KF20 KF21 KF22 X71 X70 X69 X68 X67 X66 X65 X64 X63 X62 X61 X60 AA07 MFG L H PWM GND M 1 MA10 ws PWM br G...

Page 29: ...X1 19 X2 15 X2 14 X2 13 X2 12 X2 11 X2 10 X2 9 X2 8 X2 7 X2 6 X2 5 X2 4 X2 3 X2 2 X2 1 Heizkreispumpe 1 Mischerpumpe 1 Heizkreispumpe 2 Mischer 1 Solarpumpe Störausgang Pufferfühler Heizkreisfühler 1 Warmwasserfühler 2 Wärmeerzeuger Fühler Solarpumpe PWM 2 Wärmeerzeuger PWM Heizkreisfühler 2 VL Kühlen Kollektor WW unten Analogeingang 0 10V Analogeingang 0 10V MA25 M 1 BT07 AA06 AA01 WPM4 H L N L T...

Page 30: ... assembly MFG MA01 Compressor motor MA04 Electrical expansion valve stepper motor MA07 Heating cooling diverter valve motor MA10 Circulation pump MA12 DHW heating diverter valve motor MA25 Heat source pump motor MA26 Suction fan RF01 Snap on ferrite bead bus cable XD1 Terminal external emergency booster heater HP power supply XD3 External control terminal XD20 Distribution terminal XD21 Distributi...

Page 31: ...Installation Specification www stiebel eltron com WPE I H K 230 Premium 31 ...

Page 32: ...16 3 Output diagrams 16 3 1 WPE I 04 H 230 Premium WPE I 04 HK 230 Premium Heating output 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 33: ... temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 Coefficient of performance COP 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 34: ...on com 16 3 2 WPE I 06 H 230 Premium WPE I 06 HK 230 Premium Heating output 0 1 2 3 4 5 6 7 8 9 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 35: ...t temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 Coefficient of performance COP 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 36: ...n com 16 3 3 WPE I 08 H 230 Premium WPE I 08 HK 230 Premium Heating output 0 1 2 3 4 5 6 7 8 9 10 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 37: ...nlet temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 Coefficient of performance COP 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 38: ...n com 16 3 4 WPE I 12 H 230 Premium WPE I 12 HK 230 Premium Heating output 0 2 4 6 8 10 12 14 16 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 39: ...let temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 Coefficient of performance COP 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 40: ... com 16 3 5 WPE I 15 H 230 Premium WPE I 15 HK 230 Premium Heating output 0 2 4 6 8 10 12 14 16 18 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Heating output kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 41: ...nlet temperature of the WQA medium C Y Power consumption kW Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 Coefficient of performance COP 0 1 2 3 4 5 6 5 4 3 2 1 0 1 2 3 4 5 1 2 3 4 5 6 D0000093976 X Inlet temperature of the WQA medium C Y Coefficient of performance e Flow temperature 35 C 55 C Output RPS 1 1 2 50 3 100 4 1 5 50 6 100 ...

Page 42: ...3 0 3 Min application limit on the heating side C 15 15 15 15 15 Max application limit on the heating side C 75 75 75 75 75 Min application limit heat source C 5 5 5 5 5 Max application limit heat source C 20 20 20 20 20 Shutdown pressure brine pressure switch positive pressure MPa 0 7 0 7 0 7 0 7 0 7 Energy data Energy efficiency class A A A A A A A A A A Electrical data Starting current with wit...

Page 43: ... 12 weeks after filling desalination mg l 0 1 0 1 0 1 0 1 0 1 Heat transfer medium requirements on the heat source side Ethylene glycol concentration geothermal probe Vol 25 25 25 25 25 Ethylene glycol concentration geothermal collector Vol 33 33 33 33 33 Values Available external pressure differential heating system hPa 710 660 620 610 500 Available external pressure differential heat source hPa ...

Page 44: ...eating side C 15 15 15 15 15 Max application limit on the heating side C 75 75 75 75 75 Min application limit heat source C 5 5 5 5 5 Max application limit heat source C 20 20 20 20 20 Shutdown pressure brine pressure switch positive pressure MPa 0 7 0 7 0 7 0 7 0 7 Energy data Energy efficiency class A A A A A A A A A A Electrical data Starting current with without starting current limiter A 25 2...

Page 45: ...0 1 0 1 0 Heat transfer medium requirements on the heat source side Ethylene glycol concentration geothermal probe Vol 25 25 25 25 25 Ethylene glycol concentration geothermal collector Vol 33 33 33 33 33 Values Available external pressure differential heating system hPa 710 660 620 610 500 Available external pressure differential heat source hPa 1020 940 830 710 520 Min heating flow rate m h 0 3 0...

Page 46: ...ed by those subsidiaries Such guarantee is only grant ed if the subsidiary has issued its own terms of guarantee No other guarantee will be granted We shall not provide any guarantee for appliances acquired in countries where we have no subsidiary to sell our products This will not affect warranties issued by any importers Environment and recycling We would ask you to help protect the environment ...

Page 47: ...www stiebel eltron com WPE I H K 230 Premium 47 NOTES ...

Page 48: ...ron cz www stiebel eltron cz Finland STIEBEL ELTRON OY Kapinakuja 1 04600 Mäntsälä Tel 020 720 9988 info stiebel eltron fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz Cédex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL ELTRON Kft Gyár u 2 2040 Budaörs Tel 01 250 6055 Fax 01 368 8097 info stiebel eltron...

Reviews: