9.8 Venting the heating system
D
00000
36
346
1
1 Automatic air vent valve
f
f
Vent the pipework by pulling up the red cap on the air vent
valve.
f
f
Close the air vent valve after the venting process.
9.9 DHW heating
For DHW heating, a DHW cylinder with an internal indirect coil is
required. The minimum coil surface area required is 3 m².
An integral 3-way valve is integrated in the appliance for switching
between the DHW heating circuit and the central heating circuit.
f
f
Thoroughly flush the pipework before connecting the heat
pump. Foreign bodies, such as rust, sand and sealant, can
impair the operational reliability of the heat pump. We rec-
ommend installing our filter assembly in the DHW heating
circuit (see chapter "Appliance description / Accessories").
f
f
Connect the DHW flow of the appliance to the upper heat
exchanger coil connection of the DHW cylinder (see "Specifi-
cation / Dimensions and connections").
f
f
Connect the DHW return of the appliance to the lower heat
exchanger coil connection of the DHW cylinder (see "Specifi-
cation / Dimensions and connections").
Note
If no DHW heating is being connected, connections e22
(cylinder flow) and e23 (cylinder return) are to be hydrau-
lically interconnected.
9.10 Operation with buffer cylinder
f
f
Install the supplied TAF PT immersion/contact sensor.
f
f
Connect the sensor to the heat pump manager.
f
f
Set the parameter on the heat pump manager.
Parameter
Setting
BUFFER OPERATION (SETTINGS / HEATING / STANDARD
SETTINGS)
ON
9.11 Fitting the push-fit connectors
Note
The plastic push-fit connectors are not suitable for instal-
lation in the DHW line.
f
f
Only install the push-fit connectors in the heating or
brine circuits.
!
Material losses
f
f
Tighten the screw cap of the push-fit connector by
hand. Never use a tool.
Material losses
To ensure the push-fit connector is held securely, pipes
with a surface hardness > 225 HV (e.g. stainless steel)
must have a groove.
f
f
Using a pipe cutter, cut a groove (depth ap-
prox. 0.1 mm) at a defined distance from the end of
the pipe.
- Pipe diameter 22 mm: 17±0.5 mm
- Pipe diameter 28 mm: 21±0.5 mm
!
Material losses
Support sleeves are required when using plastic pipes.
D
00000
61
24
0
f
f
Remove the protective grey caps from the push-fit connec-
tors.
How the push-fit connectors work
The push-fit connectors are equipped with a retainer with stain-
less steel serrations and an O-ring for sealing. In addition, the
push-fit connectors are equipped with the "twist and lock" func-
tion. Simply turning the screw cap by hand will secure the pipe
in the connector and push the O-ring against the pipe to seal it.
Summary of Contents for WPE-I 04 H 230 Premium
Page 21: ...Installation Maintenance www stiebel eltron com WPE I H K 230 Premium 21 ...
Page 27: ...Installation Specification www stiebel eltron com WPE I H K 230 Premium 27 ...
Page 31: ...Installation Specification www stiebel eltron com WPE I H K 230 Premium 31 ...
Page 47: ...www stiebel eltron com WPE I H K 230 Premium 47 NOTES ...