FE Correction

This parameter enables the calibration of the 
actual room temperature.

Room influence for FEK

Standard setting 5; adjustable from ----via 
“0 to 20” dashes (----) in the display:  
When the FEK control module is connected, 
the room temperature sensor 

only serves

 

to capture and display the actual room 
temperature; it has no influence on the actual 
control. With any setting, you can adjust the 
set room temperature for the heating circuit at 
the FEK control module by ±5 K. This set value 
adjustment applies for the then current heating 
time, 

not 

for the setback time. 

At the same time, setting “0 to 20” serves to 
control the room temperature-dependent night 
setback. This means, the heating circuit pump 
is switched OFF at the point of changeover 
from the heating into the setback phase. It 
remains OFF, until the actual room temperature 
first drops below the set room temperature. 
Afterwards the system regulates in weather-
compensated mode.
If you want the room temperature to be taken 
into account, set the room temperature sensor 
influence to 

>

 0. The room sensor influence 

has the same effect as the outside temperature 
sensor has on the return temperature. Only 
this effect is 1 to 20 times greater than the set 
factor.

Room temperature-dependent return 
temperature with weather compensation

With this type of control, a control cascade is 
formed from weather-compensated and room 
temperature-dependent return temperature 
control. In other words, the weather-
compensated return temperature control 
pre-selects the return temperature, which is 
corrected by the overlaid return temperature 
control in accordance with the following 
formula:

∆ϑ

R

 = (

ϑ

Rset

 − ϑ

Ractual

) * S * K

Because a substantial proportion of control 
is already taken care of by the weather-
compensated control, the room temperature 
sensor influence 

K

 can be set lower than with a 

purely room temperature control (

= 20). The 

figure on page 15 indicates the control method 
with the set factor 

= 10 (room influence) 

and a heating curve 

= 1.2.

Room temperature control with weather-
compensation

This type of control offers two substantial 
benefits:
Incorrectly set heating curves are corrected 
by the room temperature sensor influence 

K

, whilst the smaller factor 

K

 provides more 

stable control.

However, observe the following for all control 
units with room temperature sensor influence:
–  The room temperature sensor must capture 

the room temperature accurately.

–  Open doors and windows severely 

influence the control result.

–  All radiator valves in the lead room must 

always be fully open.

–  The temperature inside the lead room is 

decisive for the entire heating circuit.

Set the room temperature sensor influence to 
> 0, if you want the room temperature to be 
taken into account.

LCD test

Pressing 

 once initiates a LCD test. All 

display elements are displayed in sequence.

FEK software

Display of the current software issue.

Summary of Contents for FEK

Page 1: ...26_03_01_0106 270783 26_03_01_0106 FEK Control module Operating and installation instructions...

Page 2: ...1 1 Equipment description 2 1 2 Equipment overview 2 1 3 Important information 2 1 4 Operation 3 1 5 Settings 3 2 Installation instructions 12 for contractors 2 1 Standard delivery 12 2 2 General 12 2...

Page 3: ...control module must only be installed and maintained by quali ed contractors 1 4 Operation The operation is split over three control levels Control levels 1 and 2 are accessible to users and contract...

Page 4: ...erating mode time and day as well as the current room temperature and relative humidity 1 5 1 Operating mode key When connecting a FEK only the operating modes for the pre selected heating circuit are...

Page 5: ...mode 6 Cooling mode 7 Compressor runs 8 Booster in operation Stage 1 2 or 3 9 Fault message flashing 10 BUS connection to the WPMi established 11 WPMI in away mode 12 Standby mode 13 Automatic mode 14...

Page 6: ...you can adjust the heating program The Temperatures parameter enables you to scan the sensor temperatures of the heat pump or heat pump system comparing the actual with the set temperatures the relat...

Page 7: ...emperature Note No display if the corresponding temperature sensor is not connected Room temperature With the Room temp parameters you can adjust the set room temperature for the day and setback mode...

Page 8: ...pump system should heat in day mode Open the control ap At all other times the heat pump operates in setback mode You will already have selected the corresponding set values for day and setback mode u...

Page 9: ...eating circuit 1 and to the mixer flow temperature for heating circuit 2 When adjusting the heating curve the calculated set return or flow temperature which is subject to the outside temperature and...

Page 10: ...peratur C 0 8 Heating curve diagram One heating curve respectively can be adjusted for heating circuit 1 and heating circuit 2 At the factory heating curve 0 6 is set up for heating circuit 1 and heat...

Page 11: ...utside temperature C 20 18 16 14 12 10 8 6 4 2 0 2 4 6 8 10 12 14 16 18 20 Au entemperatur C R cklauf Vorlauftemperatur C 70 60 50 40 30 20 ge nderte Heizkurve 26_03_01_0079 Matching a heating curve t...

Page 12: ...rough curtains or similar External heat influence is prevented e g sun heating system TV set Prevention of direct draughts next to windows and doors For fitting remove the top part of the casing by le...

Page 13: ...ing enables the adjustment of the second digit of the code etc The display shows CODE OK when all four digits have been entered correctly This enables access to control level 3 Closing and re opening...

Page 14: ...scade is formed from weather compensated and room temperature dependent return temperature control In other words the weather compensated return temperature control pre selects the return temperature...

Page 15: ...ngiger Vorlaufsollwert bei A 0 C witterungsabh ngiger Vorlaufsollwert bei A 10 C Raum f hlereinfluss bei K 10 und S 1 2 und Regelabweichung 2 K R R soll R ist 26_03_01_0098 Room in uence Weather compe...

Page 16: ...el eltron hu Internet www stiebel eltron hu Nederland Stiebel Eltron Nederland B V Daviottenweg 36 Postbus 2020 NL 5202 CA s Hertogenbosch 073 6 230000 Fax 073 6 231141 E Mail stiebel stiebel eltron n...

Reviews: