13
2.5 FEK commissioning
Only approved contractors may commission
this control module and instruct the owner
in its use.
Not only the adjustments at control level 2
but also the system-specific parameters must
be determined as part of commissioning the
FEK. These parameters are adjusted at control
level 3, access to which is protected by code.
To reach this point, press , until you reach the
“Contractor” parameter, then
press
. Check all parameters in sequence,
Note:
Not all adjustments take immediate
effect. Some adjustments only become effective
in certain situations or after a delay.
Code
1 0 0 0
Enter the correct four-digit code to change
parameters at control level 3.
The factory-set code is 1 0 0 0.
After pressing
(indicator illuminates),
by pressing you can adjust the first digit.
Pressing
again confirms the value, then
the second digit of the code begins to flash.
Pressing enables the adjustment of the
second digit of the code, etc. The display
shows CODE OK when all four digits have
been entered correctly. This enables access
to control level 3. Closing and re-opening the
flap requires that the code is entered again.
Checking settings does not require the code to
be entered.
Language
Press
and select the required language
with . Then confirm your selection by pressing
.
Contrast
Press
and adjust the contrast with or .
SELECT REM CON
You can predetermine with parameter
FE
selection,
to which heating circuit the remote
control applies.
As standard, HC1 is pre-selected. Accordingly,
the parameters room temp., heating curve and
heating program for heating circuit 1 are not
displayed at the WPMi.
2.4 Specification
Supply voltage
12 V DC ± 15 %
Power consumption
~ 25 mA
EN 60529
IP 40
EN 60730
Protection class II
Clock backup
> 10 hours
Permiss. ambient temp. during operation
0 to 50 °C
Permiss. ambient temp. during storage
- 20 to 60 °C
Room temperature sensor resistance
Tolerance in Ohm
Temperature tolerance
Test resistance NTC 5 k
Ω
± 1 % at 25 °C
± 0.2 K at 25 °C