20
02/13424999688
Technical datas
M2 1000N
Execution
./1G/EV1/.
./LA/1G/EV1/. ./SG/1G/EV1/.
./2G/EV1/.
./LA/2G/EV1/. ./SG/2G/EV1/.
Electrical properties
Operating voltage DC
24 V
Permissible voltage range
-15 % / +25 %
Permissible ripple voltage
2 V
ss
Nominal current
0.9 A
1.3 A
Standby power
0.3 W
0.3 W
Switch-off current OPEN
1.1 A
1.65 A
Switch-off current CLOSE
1.1 A
1.65 A
Cut-off OPEN
external
power
cut-off
external
external
power
cut-off
external
Cut-off CLOSE
external
power
cut-off
external
external
power
cut-off
external
Class of protection
III
Mechanical properties
Stroke length
200, 300, 500, 750 and 1000 mm; lengths between available
Pressing force
1000 N
Tractive force
1000 N
Locking force retract
2000 N
Side force
not allowed
Speed
4,2 mm/s
8,3 mm/s
min. Casement height at stroke length
depending on the installation location and the profiles.
To determine the value a configuration is necessary.
Dimensions
M2/.../1G → up stroke 750 mm = ( 228 mm) x 60 x 41 mm
M2/.../1G → from stroke 750 mm = ( 290 mm) x 60 x 41 mm
M2/.../2G → up stroke 750 mm = ( 268 mm) x 60 x 41 mm
M2/.../2G → from stroke 750 mm = ( 330 mm) x 60 x 41 mm
Weight
model stroke 1000 mm = ca. 4,5 kg
Circuit connections and operation
Power cable
2 x 0,75 mm²
2 x 0,75 mm²
2 x 1,5 mm²
3 x 0,5 mm²
2 x 0,75 mm²
2 x 0,75 mm²
2 x 1,5 mm²
3 x 0,5 mm²
Electrical connection
see technical documentation
Terminal connections
see technical documentation
Pause time during change of polarity
> = 100 ms
Start-up time
30 % start-up time relating to 10 min, 3 min ON, 7 min OFF
Cycles
1)
2
Timing according to prEN 12101-9
suited, with change of direction
Service life
> 10.000 cycles
Multiple triggering against end position
suited
Maintenance
see maintenance works
SHE linear drive M2/...-1000N/EV1/.../RWA