SECTION II - GENERAL INFORMATION

A. Purpose
The purpose of this manual is to present a guide for
proper installation, maintenance, and operation of the
Direct Gas-Fired System, and supplement, but not to
replace,
 the services of qualified field service person-
nel to supervise the initial start-up and adjustment of
the unit. Persons without previous experience with
large commercial and industrial heating equipment
should not attempt the initial adjustment and checkout
procedure which is essential before such installations
may be considered ready for operation. This manual
should be made readily available to all operating
personnel as an aid in troubleshooting and proper
maintenance.

B. Shipping
Base Direct Gas-Fired units are shipped completely
assembled where shipping limitations allow. Optional
inlet hoods, filter and/or damper sections, or other
large accessories are assembled and shipped
mounted and wired whenever possible within limita-
tions of shipping and handling. Any optional accesso-
ries shipped separately are shipped as assembled
sections. Any wired accessories which have been
disassembled for separate shipment require no
additional conduit or wire for field reassembly. All wire
leads will be tagged for ease of reconnection in the
field.

Shipments are made F.O.B. Dallas, Texas by flatbed
truck. The unit is securely strapped, tied, and blocked
to prevent shipping damage. All shipments are
checked by an inspector before they are accepted by
the carrier. Parts that are shipped unmounted are
noted on the bill of lading. These parts, where feasible,
are packaged and shipped with the units. Upon receipt
of shipment, all units should be checked against the
bill of lading to insure all items have been received. All
equipment (and any optional accessories) should be
checked carefully for physical damage in the presence
of the carrier’s representative. If parts are missing or
damage has occurred, a claim should be filed immedi-
ately with the carrier.

All Direct Gas-Fired units are given a complete opera-
tions test and control circuit checkout before shipment.
Copies of the wiring diagram, piping diagram and bill
of material are included with each unit shipped. If
correspondence with the factory is necessary, please
provide the unit model and serial number.

C. Optional Factory Service
Periodic service on any piece of mechanical equip-
ment is necessary for efficient operation. A nationwide
service support network is available to provide quick
and dependable servicing of make-up air, heating,
ventilating, or air handling types of equipment. Factory
start-up service is also available which includes the
presence of a service engineer to supervise the initial
start-up and adjustment of the equipment and provide
instructions for the owner’s maintenance personnel in
proper operations and maintenance. Consult factory
for quotations on start-up or periodic service.

SECTION I - FORWARD

As is the case with any fine piece of equipment, care
must be taken to provide the proper attention to the
operation and maintenance details of this machine.

This manual of instructions has been prepared in order
for you to become well-acquainted with those details,
and in doing so, you will be able to give your Direct
Gas-Fired System the care and attention which any
piece of equipment needs and deserves.

Table of Contents

Section I: Forward and Table of Contents ................... 2
Section II: General Information ................................... 2
Section III: Installation ................................................. 3
Section IV: Pre-Start Up .............................................. 5
Section V: Unit Start Up .............................................. 6
Section VI: Unit Shut Down ......................................... 8
Section VII: Troubleshooting Guide ............................ 8
Section VIII: Maintenance Schedule and

Lubrication Requirements ..................... 23

Section IX: Maxitrol Valve Adjustments

and Preliminary Circuit Analysis ............. 27

Section X: Replacement Parts .................................. 29
Section XI: Recirculation ........................................... 31

Summary of Contents for SDFI

Page 1: ...errupteur 3 teindre toute flamme ouverte 4 Appelez imm diatement votre fournisseur de gaz AVERTISSEMENT Une installation d ficiente de m me qu un mauvais r glage modification entretien ou maintenance...

Page 2: ...ould be checked carefully for physical damage in the presence of the carrier s representative If parts are missing or damage has occurred a claim should be filed immedi ately with the carrier All Dire...

Page 3: ...e pillow block ball bearing assemblies in the fan section It is recommended that all nuts and set screws be tightened Turn fan shaft by hand to make certain that blower does not rub against blower hou...

Page 4: ...C Location of Accessories Where applicable standard or optional accessories will be placed inside the fan section of the unit for shipment and must be removed and installed by the mechanical or electr...

Page 5: ...at thermostats especially those with mercury bulb contacts be mounted on a vibration free surface The side of building columns away from the heater or interior walls are usually the location best suit...

Page 6: ...ockwise to decrease pressure Connect test instrument to pilot flame test jack located on flame safeguard relay Set all thermostats to call for heat Set inlet ductstat if applicable above outside air t...

Page 7: ...e pilot and burner a number of times to insure smooth light off Check flame signal with burner cycling through full firing range and burner profile damper operation if applicable Unit Start Up Systems...

Page 8: ...eat switch will have to be turned off for approximately five seconds to reset the ignition control D Air Pressure Switches The high air pressure switch is checked by removing the sensing tube from the...

Page 9: ...terminal is energized RM7895C D EC7895C RM7896C D f Internal system fault occurred g Purge card is removed h Purge card is bad 5 MAIN FLAME ESTABLISHING PERIOD MFEP RM7895C D EC7895C RM7896C D a Airf...

Page 10: ...ain Flame Establishing Period MFEP a After Ignition Trials and with the presence of flame the main fuel valve terminal 9 is pow ered If a flameout occurs the relay module locks out or recycles dependi...

Page 11: ...VII TROUBLE SHOOTING continued SETTINGS AND ADJUSTMENTS Selectable Site Configurable Jumpers The relay module has three site configurable jumper options see Fig 6 and Table 7 If necessary clip the si...

Page 12: ...IRFLOW SWITCH FLAME DETECTOR IGN AIRFLOW SW CHECK OPERATING CONTROLS AND INTERLOCKS INITIATE ALARM ALARM STANDBY POWER POWER PILOT FLAME MAIN TIMED PURGE ALARM POWER PILOT FLAME MAIN RUN STANDBY BURNE...

Page 13: ...ITIATE ALARM ALARM STANDBY POWER POWER PILOT FLAME MAIN TIMED PURGE ALARM POWER PILOT FLAME MAIN ALARM POWER PILOT FLAME MAIN RUN STANDBY BURNER START MAIN VALVE LIMITS AND BURNER CONTROLLER CLOSED 10...

Page 14: ...he appliance nameplate for high pressure The gas control full rate outlet pressure should match this rating 4 With main burner operating check the gas control flow rate using the meter clocking method...

Page 15: ...at or controller above room tempera ture to call for heat 3 Watch for ignition spark or for glow at hot surface igniter either immediately or following prepurge See IP module specifications 4 Time the...

Page 16: ...quired gas pressure 3 No gas through pilot regulator with inlet gas pressure ok 4 No gas through pilot solenoid 1 Check power source 2 Check and replace 3 Close or connect customer interlock 4 Switch...

Page 17: ...in main flame check wiring and flame rod 1 Place in Run position see technical cut sheet on flame safeguard relay 5 Type of gas natural LP supplied different from factory required type Note component...

Page 18: ...ing down the reset button 7 Correct problem Reset both switches 8 Check for power and replace if necessary 1 Low or no voltage 2 Fuse s blown 3 Customer interlock not closed or connected 4 Fan Off On...

Page 19: ...ng or replace if necessary 12 Clean or replace regulator 13 Check vent lines or replace limiters 14 Adjust setting on modulating valve or gas valve 1 See following troubleshooting guide for Maxitrol s...

Page 20: ...20 TROUBLESHOOTING GUIDE P 001004 P 001003...

Page 21: ...Inspect for loose or broken wires between amplifier terminals 1 2 and TD114 terminals 1 3 3 Connect test resistor as described in Preliminary Circuit Analysis in Section IX Follow procedures outlined...

Page 22: ...tor as described in Preliminary Circuit Analysis Turn TD114 selector dial so heater goes through its entire modulating range 3 Temporarily wire each TD114 TS114 and MR212 externally and observe heater...

Page 23: ...If on high fire control can do no more Heater unable to furnish additional heat to raise temperature 1 Replace automatic control valve 2 Correct wiring I Incorrect Discharge Air Temperature J Burned...

Page 24: ...ult Install replacement amplifier 1 Adjust to proper low fire 2 If greater than 1 5 negative pressure check equipment for clogged filters and other inlet air restrictions For other solutions consult f...

Page 25: ...read 6000 ohms 1000 T244 If TS244 TD244 are used meter should read 4500 ohms 1000 TS244 and 2100 ohms 150 TD244 3 Follow procedures outline in Preliminary Circuit Analysis in Section IX 1 Compare sen...

Page 26: ...l circuit 1 Incorrect maximum discharge air temper ature setting A1044 2 Incorrect minimum discharge air temper ature setting A1044 3 Insufficient burner capacity 4 Incorrect space temperature calibra...

Page 27: ...warranty A Maintenance Schedule 1 Weekly a Check that fan belts are tight and sheaves are aligned The fan belts can be checked every 30 days after the first 60 days of new belt run in CAUTION Do not...

Page 28: ...seals and a high operating temperature suggest too much grease Frequency of Lubrication Frequency of lubrication depends upon operating conditions The bearing operating temperature is the best index...

Page 29: ...ompare the force you have applied with the values given in the table below If the force is between the values for normal tension and 1 1 2 times normal tension the belt tension should be satisfactory...

Page 30: ...specific mixing plate or plates involved must be replaced c Put system back into operation and view burner while cycling through full firing range This will give a visual check for blocked burner port...

Page 31: ...inuous low fire 2 Remove cap B and loosen lock screw C Turn D to desired low fire adjustment Clockwise rotation reduces minimum flow rate 3 Tighten screw C replace cap B and reconnect wire to amplifie...

Page 32: ...ructed the problem can be isolated to the electron ics and this may once again be reviewed in the check list After test remove the test resistor and reconnect the Discharge Air Sensor to terminals 3 a...

Page 33: ...igure 1 except have TS144 connected in place of jumper Set A1044 MIN temperature selector at least 10 F above outdoor temperature Set A1044 MAX temperature selector at mid range Heater is now under co...

Page 34: ...s generated by the heater may create hazard ous concentration of carbon monoxide nitrogen dioxide and other combustion products in the heated space If gas fork trucks or other fossil fuel powered equi...

Page 35: ...35...

Page 36: ...4830 Transport Drive Dallas TX 75247 Phone 214 638 6010 Fax 214 905 0806 www sterlinghvac com HVAC PRODUCTS...

Reviews: