Troubleshooting - Quick Guide 

 

Problem 

Possible cause 

Solution 

Unit does not run. 

No power. 

Check main disconnect, fuses, wiring, and 
power lead to unit. 

Wrong voltage supplied to unit. 

Voltage must be within plus or minus 10% of 
nameplate rating. 

Defective display. 

Replace. 

Control circuit fuse blown. 

Replace control circuit fuse. 
Check transformer. 
Check for a short circuit. 

Defective control transformer. 

Replace. 

Piping flow switch circuit open. 

Add water or water/glycol solution as 
required. 

Pump motor off on overload. 

Reset and test. 

Pump runs; compressor does not. 

Leaving fluid setpoint

 

set higher than 

temperature of liquid in system. 

Lower the leaving fluid temperature below the 
leaving temperature you desire. 

Compressor internal overload or MCP is 
open. 

Allow time to cool and reset, then check for 
high/low voltage. It must be within plus or 
minus 10% of the nameplate rating. 
Check for open loose compressor electrical 
connections. 
Failed compressor motor 

Compressor contactor holding coil open. 

Repair or replace. 

Defective compressor auxiliary contact. 

Repair or replace. 

Broken wire in the compressor control 
circuit. 

Locate and repair. 

Pump runs, compressor cycles at short 
intervals. 

Plugged Y-strainer 

Clean 

Hot gas not coming on 

Check hot gas analog output value through 
status screen.  Contact Service if output value 
remains at 0% throughout compressor cycle. 

Low water flow 

Install bypass between to-and-from process 
line 

Water temperature is too high. 

 
Water/glycol mixture inadequate for 
process. 

Make sure that the water/glycol mixture 
protection is right for the process. 

Improperly set leaving fluid temperature, 
warning, or fault set point 

Adjust. 

Refrigerant charge is low. 

Call service to find and repair the leak, then 
have refrigerant added. 

Pump process pressure low (refer to 
curves for normal pressure for various 
pumps). 

Pump running in reverse. 

Verify rotation; if running in reverse rotation, 
reverse any two main power leads. Re-verify 
for correct pump rotation. 

Check for foreign matter. 

Clean the system strainer. 

Pump process pressure is too high. 

Restricted water flow. 

Check for partially closed valves etc. Make 
sure that all lines are properly sized. 

Unit runs continuously, but not enough 
cooling power

.

 

Restricted condenser air flow. 

Clean filters. 
Clean condenser. 

Unit low on refrigerant. 

Check the refrigerant charge by viewing sight 
glass on liquid line upstream of the expansion 
valve. 

Compressor not operating efficiently. 

Call service. 

Unit under-sized for application. 

Call sales rep. 

 