background image

8

PIPE INSTALLATION

Figure 4 - Pipe Installation, Standard Controls

 Never use an open fl ame to detect 

gas leaks. Explosive conditions may exist which 
may result in personal injury or death!

The appliance and its individual shutoff valve must be 
disconnected from the gas supply piping system during 
any pressure testing of that system in excess of 1/2 psig 
(3.5 kPa).

The appliance must be isolated from the gas supply 
piping system by closing its individual manual shutoff 
valve during any pressure testing of the gas supply 
piping system at test pressures equal to or less than 
1/2 psig (3.5 kPa).

Table 4 - Gas Piping Requirements

SINGLE STAGE GAS PIPING REQUIREMENTS*

GasType  

 

Natural Gas  

Propane (LP) Gas

Manifold

 

 

3.5 in. W.C. 

10.0 in. W.C.

Pressure

 

 

(0.9 kPa) 

(2.5 kPa)

 

 

14.0 in. W.C. Max. 

14.0 in. W.C. Max.

Supply Inlet

   

(3.5 kPa) 

(3.5 kPa)

Pressure

 

 

5.0 in. W.C. Min. 

11.0 in W.C. Min.

 

(1.2 kPa) 

(2.7 kPa)

*

For single stage application only at normal altitudes.

   

1.  Install the gas piping in accordance with applicable 

local codes.

2.  Check gas supply pressure. Each unit heater must 

be connected to a manifold pressure and a gas 
supply capable of supplying its full rated capacity 
as specified in Table 4. A field LP tank regulator 
must be used to limit the supply pressure to a 
maximum of 14 in. W.C. (3.5 kPa). All piping should 
be sized in accordance with the latest edition of 
ANSI Standard Z223.1, National Fuel Gas Code; 
in Canada, according to CGA B149. See Tables 
1 & 3 for correct gas piping size. If gas pressure 
is excessive on natural gas applications, install a 
pressure regulating valve in the line upstream from 
the main shutoff valve.

3.  Adequately support the piping to prevent strain on 

the gas manifold and controls.

4.  To prevent the mixing of moisture with gas, run the 

take-off piping from the top, or side, of the main.

5.  Standard Unit Heaters, optional two-stage units are 

supplied with a combination valve which includes:

 

a. Manual "A" valve

 

b. Manual "B" valve

 

c. Solenoid valve

 

d. Pressure regulator

 

Pipe directly into the combination valve (see Figure 
4).

6.  Gas valve has a pressure test post requiring a 

3/32" hex head wrench to read gas supply and 
manifold pressures. Open 1/4 turn counterclockwise 
to read, turn clockwise to close and reseat. A 5/16" 
ID hose fi ts the pressure post.

7.  Provide a drip leg in the gas piping near the gas 

unit heater. A ground joint union and a manual gas 
shutoff valve should be installed ahead of the unit 
heater controls to permit servicing. The manual 
shutoff valve must be located external to the jacket 
(See  Figure 4).

8.  Make cer tain that all connections have been 

adequately doped and tightened.

 Do not over tighten the inlet gas 

piping into the valve. This may cause stresses that 
will crack the valve!

NOTICE: Use pipe joint sealant resistant to the 
action of liquefied petroleum gases regardless of 
gas conducted.

 Check all pipe joints for leakage 

using a soap solution or other approved method.  
Never use an open flame or severe personal 
injury or death may occur!

Summary of Contents for GF-150

Page 1: ...en test fired and inspected It has been shipped free from defects from our factory However shipment and installation problems such as loose wires leaks or loose fasteners may occur It is the installer...

Page 2: ...bustion Air 5 6 Proper Clearances 5 6 Suspension of Units 5 6 Gas Piping 7 8 ELECTRICAL CONNECTIONS 9 10 11 VENTING 12 13 14 15 16 OPERATION Explanation of Controls and Operation 17 Main Burner Orific...

Page 3: ...t Start Up Sheet located in this manual Use only the fuel for which the heater is designed see rating plate Using LP gas in a heater that requires natural gas or vice versa will create risk of gas lea...

Page 4: ...30 5 8 30 5 8 48 5 8 48 5 8 48 5 8 473 473 473 778 778 778 1235 1235 1235 F Discharge Opening Width 18 3 4 18 3 4 18 3 4 30 3 4 30 3 4 30 3 4 48 3 4 48 3 4 48 3 4 476 476 476 781 781 781 1238 1238 12...

Page 5: ...st be equipped with an OSHA approved fan guard Refer to the latest edition of NFPA 88A Parking structures In Canada installation must be in accordance to the latest edition of CGA B149 Installation Co...

Page 6: ...cent materials Make certain that the lifting methods used to lift the heater and the method of suspension used in the field installation of the heater are capable of uniformly supporting the weight of...

Page 7: ...ity Gas Nominal Iron Internal Length of Pipe Feet meters Pipe Size Dia 10 20 30 40 50 60 70 80 90 100 125 150 175 200 in in 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0 1 2 0 622...

Page 8: ...Code in Canada according to CGA B149 See Tables 1 3 for correct gas piping size If gas pressure is excessive on natural gas applications install a pressure regulating valve in the line upstream from t...

Page 9: ...re air Always refer to the thermostat instructions as well as our unit wiring diagram and wire accordingly Avoid mounting the thermostat in the following locations 1 Cold Areas Outside walls or areas...

Page 10: ...10 ELECTRICAL CONNECTIONS continued Figure 5d Tubular Units Equipped with Natural Gas and Propane LP Gas...

Page 11: ...11 ELECTRICAL CONNECTIONS continued Figure 5e Tubular Unit Sizes with Optional 2 Stage Ignition...

Page 12: ...its in areas under negative pressure due to large exhaust fans or air conditioning When required a flue vent fan should be installed in accordance with the instructions included with the fan 10 Vent c...

Page 13: ...et Adjacent public walkways 7 feet above grade The venting system for these appliances shall terminate at least 4 feet 1 2m below 4 feet 1 2m horizontal from or 1 foot 0 3m above any door window or gr...

Page 14: ...odes or in the absence of local codes with current CGA B149 1 Installation Codes for Natural Gas Burning Appliances and Equipment or CGA B149 2 Installation Codes for Propane Gas Burning Appliances an...

Page 15: ...15 Figure 8A Figure 8B VENTING continued...

Page 16: ...16 VENTING continued Figure 9A Figure 9B...

Page 17: ...e period ends the power venter motor is de energized 6 The fan operation is delayed 30 seconds once the thermostat is closed and continues operation for 30 seconds after the thermostat opens NOTICE Th...

Page 18: ...unit heaters must be orificed to 90 of the normal altitude rating and be so marked in accordance with ETL certification Check the gas input rate as follows Refer to General Safety Information section...

Page 19: ...ssure altitude of the unit installation and the technician s name and date on the label using a permanent marker Refer to Installation Instruction section on Adjustments Gas Input Rate for adjusting t...

Page 20: ...t openings 3 Clean heat exchanger Refer to Installation 4 Determine cause and repair accordingly 1 Inspect all gas piping and repair 2 Check to ensure gas test ports are seated 3 Clean heat exchanger...

Page 21: ...tat 1 Replace or tighten 2 Clean power ventor wheel 3 Realign power ventor wheel 1 Check and tighten wires on fan circuit 2 Test for 115v on terminal ACB Heat and L2 if voltage is present replace moto...

Page 22: ...heat If not present and all checks are normal replace 1 Check power ventor circuit per wiring diagram 2 Check motor voltage and amp draw to motor name plate replace if motor found defective 3 Check f...

Page 23: ...er 3 5 Amp fuse on circuit board 1 Common side of transformer grounded to chassis 2 Loose spark ignitor 1 Gas supply off or gas supply pressure too low 2 Flame sense rod contaminated or loose wire 3 G...

Page 24: ...l safety devices supplied with your unit NOTICE The heater and vent system should be checked once a year by a qualified technician All Maintenance Service information should be recorded accordingly on...

Page 25: ...ogenated hydrocarbons precipitated in the air d to any workmanship of the installer of the Product 3 This limited warranty is conditional upon a advising the installing contractor who in turn notify t...

Page 26: ...ICATION OF PARTS PROPELLER UNIT HEATERS Figure 13 Heat Exchanger Assembly Figure 14 Electrical Control Panel Figure 11 Propeller Parts Figure 12 Component Parts D4430 Fan Guard Fan Blade Hardware Hard...

Page 27: ...er Assembly 300 400 Unit Sizes Shown HOW TO ORDER REPLACEMENT PARTS Please send the following information to your local representative if further assistance is needed contact the manufacturer s custom...

Page 28: ...n installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GENER...

Reviews: