RESETCON (Temperature Reset and Demand Limit)
SCHEDOVR (Timed Override Setup)
SETPOINT
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
COOLING RESET
Cooling Reset Type
0 = No Reset
1 = 4-20 mA input
2 = External temp – OAT
3 = Return Fluid
4 = External temp - SPT
0
CRST_TYP
4-20 MA RESET
4-20 – Degrees Reset
–30 to 30
0.0
∆∆∆∆
F
420_DEG
REMOTE RESET
Remote – No Reset Temp
0 to 125
125.0
°°°°
F
REM_NO
Remote – Full Reset Temp
0 to 125
0.0
°°°°
F
REM_FULL
Remote – Degrees Reset
–30 to 30
0.0
∆∆∆∆
F
REM_DEG
RETURN TEMPERATURE RESET
Return – No Reset Temp
0 to 125
10.0
∆∆∆∆
F
RTN_NO
Return – Full Reset Temp
0 to 125
0.0
∆∆∆∆
F
RTN_FULL
Return – Degrees Reset
–30 to 30
0.0
∆∆∆∆
F
RTN_DEG
DEMAND LIMIT
Demand Limit Select
0 = None
1 = External switch input
2 = 4-20 mA input
3 = Loadshed
0
DMD_CTRL
Demand Limit at 20 mA
0 to 100
100
%
DMT20MA
Loadshed Group Number
0 to 99
0
SHED_NUM
Loadshed Demand Delta
0 to 60
0
%
SHED_DEL
Maximum Loadshed Time
0 to 120
60
minutes
SHED_TIM
Demand Limit Switch 1
0 to 100
80
%
DLSWSP1
Demand Limit Switch 2
0 to 100
50
%
DLSWSP2
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
Schedule Number
0 to 99
1
SCHEDNUM
Override Time Limit
0 to 4
0
hours
OTL
Timed Override Hours
0 to 4
0
hours
OVR_EXT
Timed Override
No/Yes
No
TIMEOVER
DESCRIPTION
VALUE
DEFAULT
UNITS
POINT NAME
COOLING
Cooling Setpoint 1
–20 to 70
44.0
°°°°
F
CSP1
Cooling Setpoint 2
–20 to 70
44.0
°°°°
F
CSP2
ICE Setpoint
–20 to 32
32.0
°°°°
F
CSP3
RAMP LOADING
Cooling Ramp Loading
0.2 to 2.0
1.0
CRAMP
Brine Freeze Point
–20 to 34
34.0
°°°°
F
BRN_FRZ
Summary of Contents for AquaSnap 30RA010
Page 6: ...6 Fig 1 Typical Control Box for 30RA010 030 022 030 Shown ...
Page 7: ...7 Fig 2 Typical Control Box for 30RA032 055 042 055 Shown ...
Page 8: ...8 Fig 3 Wiring Schematic 30RA010 018 30RA010 018 AQUA SNAP ...
Page 10: ...10 Fig 4 Wiring Schematic 30RA022 030 30RA022 030 AQUA SNAP ...
Page 11: ...11 Fig 4 Wiring Schematic 30RA022 030 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 022 030 ...
Page 12: ...12 Fig 5 Wiring Schematic 30RA032 040 30RA032 040 AQUA SNAP ...
Page 13: ...13 Fig 5 Wiring Schematic 30RA032 040 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 032 040 ...
Page 14: ...14 Fig 6 Wiring Schematic 30RA042 055 30RA042 055 AQUA SNAP ...
Page 15: ...15 Fig 6 Wiring Schematic 30RA042 055 cont AQUA SNAP LOW VOLTAGE CONTROL SCHEMATIC 042 055 ...